| 1 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 2 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 3 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 4 | Providing and laying of HDPE PIPE OF 40 mm outer dia PN 4 rating by hand Moling/Mannual method Confirming to IS 4984. |
| 5 | Supply of XLPE insulated PVC sheathed Al. conductor Armoured Cable 1.1 KV grade conforming to IS 7098 of following Size. 2*6 sqmm |
| 6 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 7 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 8 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 9 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm |
| 10 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 6 x 1.5 sq. mm |
| 11 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) .Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surgeprotection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 45 Watt |
| 12 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 100 Watt |
| 13 | Fabrication, Suppling, Installation, testing, commissioning, of 12 mts. High mast system with its accessories, Mast shaft shall be in one section, hot dip galvanized 4mm thick(single dip) inside and out sides & suitable for wind velocity as per IS 875 part3. There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories for High Mast head frame, 2 point suspension system with steel wire rope 5mm dia.(7/19 construction) single drum winch, galvanized lantern carriage arrangement suitable for 4/6 nos. flood light luminaries symmetrically and its control gear boxes and lighting finial, the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L)x1m wide and 2m deep i/c excavation of earth , providing cutting, bending and placing in position, reinforcement of cold twisted bar of 12 mm dia-2100mm long (approx.)-16 nos. and reinforcement of cold twisted bar of 8 mm dia- 3700 mm (approx.)-13 nos. (with 150 mm spacing ) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the high mast considering the safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4 nos S.P MCB, 63Amp. DP isolator etc as reqd. Logo/Name of manufacturer shall be embossed on the pole, Galvanization as per relevant IS. |
| 14 | Fabrication, supply & erection of 5.0 mtr height, minimum 3 mm thick, bottom dia of 130mm & top dia of 70mm base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full verticle window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor – 4 nos. & shorting links on DIN channel i/c providing fixing DIN channel of suitable length,, 6 Amp. SPMCB ‘C’ Curve characteristics, earth stud, cable support clamp suitable for Upto 4x25 sqmm cable. Logo/Name of manufacturer shall be either embossed or Rivited plate on the Pole. Galvanization as per relevant IS code etc as required |
| 15 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm(L) x 450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -960mm long (approx.) - 8 nos. and reinforcement of cold twisted bar of 8 mm dia - 1400 mm (approx.) - 6 nos. (with 150 mm spacing) as required with supplying and positioning of 4 nos foundation bolts size 16 mm dia & 600mm long. J type i/c 2 nos. template anchor plates of size 225mmx225mmx3mm providing DWC HDPE for cable entry and exit as required for 3 m and 5mtr pole. |
| 16 | Fabrication supplyiing and fixing class B Galvanised single overhang arm bracket made out of 250 mm long galvanized top tube with cap & 1000mm long 40 mm dia galvanized pipe with tightening bolts complete as reqd |
| 17 | Fabrication supplyiing and fixing class B Galvanised double overhang arm bracket made out of 250 mm long galvanized top tube with cap & 1000mm long 40 mm dia galvanized pipe with tightening bolts complete as reqd |
| 18 | Providing and fixing of Stainless steel name plate of size 6x8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required |
| 19 | Supplying and erection of galvanised 'D' iron clamps complete with shackle insulator (75 mm X 90 mm), G. I. bolts, nuts and washers, coach screws etc. as required. |
| 20 | Supply and fabrication of pole protection system made up of 8 SWG steel wire mesh of size 25mm x 75mm rectangular with 50mm x 50mm x 6mm MS angle iron for supporting the mesh i/c MV danger plate and grounding the protection system in suitable quality of CC etc as reqd. Please Enable Macros to View BoQ information |