| 1 | Outdoor Lighting Installation, Steel Tubular Pole, M.S. Pipe, G.I. Pipe, Pole CAP etc Supplying of Swaged Steel Tubular pole as per IS 2713, Pt. II, 1980 for following designation and of following dimensions.(Outside dia & thickness are given in Annexture -1)e) 410 SP - 9 ; 7.5 Mtr., 110.00 Kg. |
| 2 | SCHEDULE OF RATES FOR OH LINE INSTALLATION (LT DISTRIBUTION).Erection of Poles.Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work(site including filling up the excavated earth pit with shifted soil and ramming properlyUpto 9.0 mtr. Size 0.6x0.6x1.70 mts |
| 3 | SCHEDULE OF RATES FOR OVERHEAD LINE INSTALLATION - REPAIR 13. Providing CC (6:3:1) muffing 450x450x600 mm in size or equivalent size of cylindrical muffing above ground level around the pole base complete with 3 mm thick neatly finished cement plaster all round after dismantling the unserviceable muffing if any incl. fixing only loop box if necessary (a) Without Loop Box |
| 4 | SCHEDULE OF RATES FOR EARTHING INSTALLATIONS.Earthing Installation ... with Pipe Electrode.Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (HOT Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:(a)By ISI Medium GI pipe. |
| 5 | Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of(approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. FOR receiving fresh coat of paint.Above 9.0 mtr. long pole.(iii)2nd coat of synthetic enamel paint over the 1st coat |
| 6 | Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of(approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. FOR receiving fresh coat of paint.Upto 9.0 mtr. long pole.ii2nd coat of aluminium paint over 1st coat |
| 7 | SUPPLY AND DELIVERY OF 200 WATT LED FLOOD LIGHTS ( MAKE-PHILIPS/CROMPTON/HAVELL'S OR EQUIVALENT ) |
| 8 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required |
| 9 | Supplying Al.conductor PVC insulated and sheathed unarmoredcable (1.1KVgrade, Gloster/Havells/Polycab). 10sqmm x 2core |
| 10 | Laying through Underground Trech.(a)Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 11 | Supplying & Erection of medium size feeder pillar box of Size (1200 x 750 x 450 mm) made up of 2 mm thick MS Plate along with suitable M.S. Angle. The P.B. have double hinge door at the front & back with suitable locking arrangement. The box will be painted by 2 cores of aluminiam paint over 1 coat of red oxide paint. Suitable arrangement should be provided for fixing of Timer unit, fuse unit & other accessories. Leg of the pillar box will be 900 mm in length by made up of (35 x 35 x 3 mm MS Angle with suitable base Plate. Legs of the Pillar box will be erected at 300 mm below the ground level with cement concrete (6:3:1). Rest portion coverd by 5\\" Brick Wall with plastering & net cement & bottom portion filled with silver sand as drawing & direction of E.I.C |
| 12 | S/F bend type arm bracket 2.7m long 40m dia G.I. pipe (ISI medium) with M.S> pole (up to 115mm dia) having a pojection of 1.35m at an angle of 105 degree by means of clamps (450mm x 40 x 60mm) and necessary bolts, nuts,clamps etc. as required.The work is to be done as per direction of Engineer-in- Charge |
| 13 | Erection of Galv. (HOT Dip) Cross arms/ `D... Iron Clamp7).Supplying & Erection of Galv. `D... iron complete with suitable pole clamp 75mmx88mm porcelain shackle insulator & 15 mm dia Galv. bolts & nuts. incl. painting |
| 14 | SCHEDULE OF RATES FOR INSTALLATION OF LIGHTNING CONDUCTOR 12. (a) Making soldered joints between conductor/ conductor & air terminals by 7/10 stranded GI (Hot Dip) wire incl. supply of jointing materials & painting with 2 (two) coats of Bituminous paint |
| 15 | Sub Total |
| 16 | GST 18% |
| 17 | CESS 1% Please Enable Macros to View BoQ information |