| 1 | Part - AProvision of 5 nos. 16 mtr Highmast light in the Campus of Engineering College, Poreyahat, Godda. |
| 2 | Supply of 16mtr. High mast in two section Construction S355 grade as per BS-EN 10 025 Top Dia 150mm, bottom dia 360mm, plate thickness 3mm, 20side polygon, galvanisation as per BS EN ISO 1461, base plate dia 520mm, base plate thickness 25mm, GI single spike lighting protection, maximum wind speed 47 m/s with 6 nos foundation bolts of PCD 445mm TS 600/ 24mm dia/850 mm long. Luminaries carriage : Material for 40 NB ERW Class B – M.S. Pipe, dia of carriage ring 450mm (ID) with 8/12 arm, welded, 2 sections having carrying capacity upto 8/12 luminaries. Trailing Cable : 5 core 2.5sq.mm. PVC flexible copper conductor Winch/Power Tool : Double drum, SWL 350 kg with 1HP 6 pole single speed integral motor Rope : Grade AISI 304, 7/19 construction, dia 5mm, BLC 1450 x 2 having 2 nos of continues rope. Aviation obstruction light : twin dome aviation obstruction lights LED type as required. Make- Bajaj, RR ISPAT, Valmount, Utkarsh or equivalent. |
| 3 | Feeder Pillar : control panel housing 63A TPN MCB incomer, single dial timer, 45A contactor circuit for the automatic control of luminaries power tool control with 2 no 9A contactors and raise lower push button, incoming 35sq.mm. and outgoing 16 & 2.5 sq.mm. terminals. |
| 4 | S/F 240 watt L.E.D Flood Light Make- Halonix, Havells, Bajaj, Surya, Crompton |
| 5 | ITC of the high mast and light fixture with the help of suitable tools and plants, wiring of luminaries with all wiring material like PVC insulated PVC sheathed flexible cable of suitable copper conductor lugs, MCB and all labour & construction of shallow foundation with M25 grade concrete for the high mast considering safe soil bearing capacity of 10T/ mtrs sq. for 16 M High mast. |
| 6 | Earthing with copper earth plate 600mm x 600mm x 3mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) as required. |
| 7 | Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required. |
| 8 | Supply of XLPE insulated sheathed (heavy duty) armoured electric cables with Aluminium conductor for working voltage 1100 volts conforming to IS:7098 (part-1)/IS:1554(a) 4x16 sq mm |
| 9 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 35 sq mm directr in ground including excavation, and refilling the trench etc as rquired, but excluding sand cushioning and protective covering. |
| 10 | S/F 40 mm dia, medium class G.I pipes for road crossing |
| 11 | Part - BProvision of Security light in the Campus of Engineering College, Poreyahat, Godda. |
| 12 | 7 Mtr. height galvanized pole( BOP - 7030) with top dia 70 mm, bottom dia 130 mm & made of 3 mm thick sheet, base plate dimensions 200 X 200 X 12 mm ( L x B x T) including suitable sizes of foundation bolt all complete as reqd. (Without Arm) |
| 13 | 1 m Double Arm suitbale for 70mm Top |
| 14 | 1 m Single Arm suitbale for 70mm Top |
| 15 | Installation, Testing & Commissioning of the 7 Mtr. Octagonal Pole & light fitting with the help of suitable tools and plants, wiring of luminaires with all materials and construction of shallow foundation with M25 grade concrete considering safe soil bearing capacity of 10T/mtrs sq. but excluding wire and MCB |
| 16 | S.I.T.C of floowing rating LED Street lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existing pole/pipe for supply voltage 100-270V AC, 50Hz. Luminarie shall be confirm to IS: 10322 part-5/section-3 and shall be complete with all neccssary accessories as required |
| 17 | 90/100W LED Street light |
| 18 | S/F 200W LED Flood light on building |
| 19 | S/F sintex box with MCB |
| 20 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 21 | 2 Way single door |
| 22 | Supplying and fixing 6 amps to 32 amps rating, 240 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, esting and commissioning etc. as required. |
| 23 | a) 40 amps, DP MCB |
| 24 | Supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit as required |
| 25 | a) 3 x 1.5 sq mm |
| 26 | Supplying and laying of XLPE insulated PVC sheathed aluminium armoured cable working voltage upto 1100 volts as per IS: 7098 (Part I) of followings sizes. |
| 27 | a) 2 core 10 sq mm (For flood light wiring on building) |
| 28 | b) 4 core 16 sq mm |
| 29 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 35 sq mm directr in ground including excavation, and refilling the trench etc as rquired, but excluding sand cushioning and protective covering. |
| 30 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 31 | S/F 25 mm dia ISI marked PVC conduit standing of cable trench to junction box |
| 32 | S/F 40 mm dia, medium class G.I pipes for road crossing |
| 33 | 63 amp TPN side handle |
| 34 | Supplying and fixing 6 amps to 32 amps rating, 240 volts, 10 KA, “B” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, esting and commissioning etc. as required. |
| 35 | Earthing with copper earth plate 600mm x 600mm x 3mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) as required. |
| 36 | Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required. |
| 37 | CGST@9% |
| 38 | SGST@9% |
| 39 | Add Labour Cess@1% Please Enable Macros to View BoQ information |