| 1 | Excavation in trenches n.exc. 1.5m wide and n.exc1.5m depth for foudation,trenches for laying of pipe line etc. and getting out in soft/loose soil all as specified and directed. |
| 2 | Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5 m above the starting point all as specified and directed. |
| 3 | Returning, filling in, incl. spreading, levelling, watering and well ramming in layers not exc 25cm in any type of soil all as specified and directed. |
| 4 | Supply and laying 3 layer PP-R pipes SDR 7.4 UV stabilized and antimicrobial welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings of all size as per ground requirement laid in trenches/open/wall complete including taking out old unserviceable pipes all as specified and directed. for the following size of pipes :- Note: (i) Union shall be provided at every 100mtr length of pipe.(ii) Union shall be provided at elbow joints, all kind of Tees & before Gate valves to the water tank.(iii) Pipes fixed on wall shall be clamped by using GI clamps with suitable saddles.(iv) PP-R fittings shall be of all size and type varying from 16mm to 110mm including elbow, reducer elbow, male/female brass threaded elbow, Tee, Reducer Tee, Brass threaded reducer Tee, ma/female ended bends, sockets, end plugs etc, flanges etc. Brass threaded male and female fittings shall be used in all connection where GI pipeline is existing. No extra cost shall be paid to the contractor for the PP-R fittings.(v) PPR pipes of white colour or other than green colour shall be incorporated at site for easy identification of general purpose water and drink water supply at this station. |
| 5 | (a) PP-R pipe 110 mm outer dia 100mm inner dia. |
| 6 | (b) PP-R pipe 63 mm outer dia 50mm inner dia. |
| 7 | (c) PP-R pipe 50 mm outer dia 40mm inner dia . |
| 8 | Making connection of PP-R distribution branch with PP-R main of following sizes by providing and fixing Tee including cutting and making fusion joint etc. for the following sizes:- |
| 9 | (a) PP-R pipe 16mm to 40mm outer dia . |
| 10 | (b) PP-R pipe 50mm to 75/110mm outer dia . |
| 11 | Supply and fixing the following PP-R gate valves (brass insert & brass threaded) with round head wheel for operation including removing old unserviceable one all as per directed . |
| 12 | (a) PP-R valve 63 mm outer dia . |
| 13 | (b) PP-R valve 50 mm outer dia . |
| 14 | Supplying and laying 50mm nominal inner dia Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR 11, having thermal stability for hot & cold water supply including all & Plain CPVC SDR 11 brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement & testing of joints complete all as specified and directed by Engineer- in-Charge. |
| 15 | Supplying and laying 40mm nominal inner dia Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR 11, having thermal stability for hot & cold water supply including all & Plain CPVC SDR 11 brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement & testing of joints complete all as specified and directed by Engineer- in-Charge. |
| 16 | Supplying and laying 25mm nominal inner dia Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR 11, having thermal stability for hot & cold water supply including all & Plain CPVC SDR 11 brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete all as specified and directed by Engineer- in-Charge. |
| 17 | Supplying and laying 20mm nominal inner dia Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR 11, having thermal stability for hot & cold water supply including all & Plain CPVC SDR 11 brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete all as specified and directed by Engineer- in-Charge. |
| 18 | Supply and fix in repairs CPVC ball valves, high pressure, with polythene float and flynut complete, screwed for CPVC pipes and fixed 50mm bore complete all as specified and directed. |
| 19 | Supply and fix in repairs CPVC ball valves, high pressure, with polythene float and flynut complete, screwed for CPVC pipes and fixed 40mm bore complete all as specified and directed. |
| 20 | Supply and fixing ball valves high pressure of CPVC with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed suitable for 25 mm ISI marked complete all as specified and as directed. |
| 21 | Supply, install, test and commission of LT Control panel board, indoor type, double door, cubical type, padestal mounted, of suitable size, CPRI approved having, IP 64, independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of of 3.15 mm thick CRCA Sheet & MS angle iron section of 50X50X6 mm frame, front operated with locking arrangements suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar of 315.Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and outgoing accessories all as approved and comprising as under : The LT Panel comprising of the following:- |
| 22 | (a) MCCB 200 A,415 Volts, 4Pole, 25 KA- 01 Nos (Incomer)(b) MCCB 25 A,415 Volts, 4Pole, 16 KA fitted in eperate compartments each - 08 Nos (out Going)(c) Copper cable 6 sqmm PVC sheathed, industrial grade from MCCB to DOL starter (for all terminals) including connection & Vertical bus bar to MCCB (for all terminals)(d)DOL starter 10 HP capacity, 3 phase, 415V, with thermal and overload relay of capacity ranging between 15 Amp to 20 Amp or as per existing - 08 Nos(e) R Y B phase indicating lamp LED type -01 Sets of 03 Nos Please Enable Macros to View BoQ information |
| 23 | (a) MCCB 200 A,415 Volts, 4Pole, 25 KA- 01 Nos (Incomer)(b) MCCB 25 A,415 Volts, 4Pole, 16 KA fitted in eperate compartments each - 08 Nos (out Going)(c) Copper cable 6 sqmm PVC sheathed, industrial grade from MCCB to DOL starter (for all terminals) including connection & Vertical bus bar to MCCB (for all terminals)(d)DOL starter 10 HP capacity, 3 phase, 415V, with thermal and overload relay of capacity ranging between 15 Amp to 20 Amp or as per existing - 08 Nos(e) R Y B phase indicating lamp LED type -01 Sets of 03 Nos Please Enable Macros to View BoQ information |