| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep in loose / soft soil and getting out for under ground cable / errection of poles, stays etc complete all as specified and directed. |
| 2 | Excavation in trenches not exceeding 1.5 metre wide and exceeding 1.5 metre deep but not exceeding 3.0metre deep in loose / soft soil and getting out for under ground cable / errection of poles stays etc complete all as specified and directed. |
| 3 | Returning filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 4 | Removal of excavated soil to a distance not exceeding 50 Mtr depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge |
| 5 | Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed.Note:- Punned thickness 18cm shall be measured for payment purposes. |
| 6 | Supply and laying of un-reinforced precast concrete cable cover ,class HV, type-1 size 300X180X40mm complete all as specified and directed. |
| 7 | Supply and lay bricks, common burnt clay, sub class \\"B', old size, laid in vertical direction to cable as cable protection complete all as specified and as directed. |
| 8 | Material and labour of PCC 1:4:8 Type D-2 using 40 mm graded aggregate for bottom of Pit for bed concrete below base plat of steel tubular poles including necessary frame work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site by Engr-in-Charge. |
| 9 | Material and labour of PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed. |
| 10 | Material and labour of PCC 1:2:4 Type B-1 using 20 mm graded aggregate for coping of poles including necessary farm work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site. |
| 11 | Supply, fix and erection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, 09 meter long, providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr including 2 bands of radium tape of 2' width green & red colour above the coping of pole starting with black strip complete all as specified and directed by Engr-in-charge. Note (i) Earth work and PCC shall be measured and paid seperately. (ii) Street light pole No 1 to 06 will be printed on each pole without any extra cost with hole in poles for passing 3 core PVC cable for Street lights |
| 12 | Supply, fixing and transportation upto site of work and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and including marking alternate 05 Nos white and black strip 30cm height with two coats of synthetic enamel paint and 2 bands of radium tape of 2\\" width green & red colour complete all as specified and directed by Engr-in-charge. Note Earth work and PCC shall be measured and paid seperately |
| 13 | Supplying and laying, connecting & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95 Sqmm 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part - 2 for insulation and for conductors Class 2 to IS 8130 - 84, in trenches, floors, ducts passing through pipe for road crossing etc, complete all as specified and directed.(Note : Excavation, earth work, brick protection, sand cushioning and GI pipe etc shall be measured & paid for separately). Please Enable Macros to View BoQ information |
| 14 | Supplying and laying, connecting & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95 Sqmm 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part - 2 for insulation and for conductors Class 2 to IS 8130 - 84, in trenches, floors, ducts passing through pipe for road crossing etc, complete all as specified and directed.(Note : Excavation, earth work, brick protection, sand cushioning and GI pipe etc shall be measured & paid for separately). Please Enable Macros to View BoQ information |