|
| 1 | SH - I (Maintenance of EI and Fans & Fittings)Day to day maintenance, operation and general up keep of all internal electrical installation such as wiring, switches, MCB's, DB's, fittings and fixtures, main boards, street/ compound lighting & recording and monitoring of the complaints round the clock on all working days excluding Sundays and Holidays complete in following locations as per terms and conditions and inventory of staff and duty time attached. Total staff required (a) Skilled (Wireman)-3 Nos. (b) Unskilled (Khallasi)-2 Nos |
| 2 | SH - II (Operation of DG set & SUB STATION)Operation & routine maintenance of HT substation having transformer of various capacity as mentioned in inventory attached including HT panel, LT panel, capacitor panel and stand by DG set of various capacity as mentioned in inventory attached including AMF panel round the clock on all days of the month including Sundays and Holidays in the following locations. Total staff required a) Wireman cum Operator -3 Nos. (Round the clock) b) Khallasi- 1 nos. |
| 3 | SH - III (Operation of wet riser/PA System / Water Supply Pump) Operation,running & maintenance of wet riser and sprinkler system, including filtered/ unfiltered/ sewage pumps installed at site on all days of the month including Sundays and Holidays complete as per terms and conditions, details of staff and inventory attached.- 1 Job Total staff required a) Wireman cum Operator -3 Nos. b) Khallasi-1 nos. |
| 4 | SH - IV (Operation of Lifts)Providing trained and experienced lift operators for operation of lifts of various passenger capacity as mentioned in inventory including cleaning and upkeeping of lift car and lift machine rooms at following location on all working days of the month excluding sundays and holidays complete as per terms and conditions and inventory of staff and duty time attached. Total staff required a) Operator - 3 Nos. |
| 5 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 1.5 sq. mm |
| 6 | b) 3 x 4 sq. mm |
| 7 | c) 3 x 6 sq. mm |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 amps switch |
| 9 | b) 15/16 A switch |
| 10 | c) 3 pin 5/6 A socket outlet |
| 11 | d) 6 pin 15/16 A socket outlet |
| 12 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.a) 1 or 2 Module (75mmX75mm) |
| 13 | b) 3 Module (100mmX75mm) |
| 14 | c) 6 Module (200mmX75mm) |
| 15 | d) 8 Module (125mmX125mm) |
| 16 | e) 12 Module (200mmX150mm) |
| 17 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. a) 1 or 2 Module |
| 18 | b) 3 Module |
| 19 | c) 6 Module |
| 20 | d) 8 Module |
| 21 | e) 12 Module |
| 22 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 23 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm |
| 24 | b) 25 mm |
| 25 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 26 | b) Double pole |
| 27 | c) Triple pole and neutral |
| 28 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) a) 8 way (4 + 24), Double door |
| 29 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 30 | S.I.T.C of 300 mm Sweep 1400 RPM Heavy Duty ISI Marked Exhaust fan i/c supply and fixing of gravity louvers & shutters in the existing opening, including making good the damage, connection, testing, commissioning etc. as reqd. |
| 31 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) a) 18- 22 Watt |
| 32 | Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/ 4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim .a) 12 -15 watt Please Enable Macros to View BoQ information |