| 1 | Supply , install testing and commissioning of centrifugal monoblock pump set ,horizontal foot mounted electric motor driven, 3 phase, 415 volts, 50 Hz supply induction motor and PCC foundation discharge not less than 660 LPM ± 10%, at a head not less than 22 mtrs, Insulation Class ‘B’, and max losses at 50% and 100% load shall be as per ECBC 2017, Degree of protection IP 44, Ambient temp of 50°C conforming to IS 12615:2011, IEC 60034-30-2008 complete all as specified and directed by Engineer-in-charge. |
| 2 | Supply , install testing and commissioning of centrifugal monoblock pump set ,horizontal foot mounted electric motor driven, 3 phase, 415 volts, 50 Hz supply induction motor and PCC foundation discharge not less than 1500 LPM ± 10%, at a head not less than 30 mtrs, Insulation Class ‘F’, and max losses at 50% and 100% load shall be as per ECBC 2017, Degree of protection IP 44, Ambient temp of 50°C conforming to IS 12615:2011, IEC 60034-30-2008 complete all as specified and directed by Engineer-in-charge. |
| 3 | Supply and fix in repair CI Foot Valve conforming to IS 4038, 100 mm (4”) dia complete all as specified and as directed. |
| 4 | All as per Item No 03 above but of size 80 mm dia. |
| 5 | S&F DOL starter suitable for 5 HP motors, 415 volts, confirming to IS/IEC 60947-4-1, degree of protection IP-54 FRLS copper internal wiring, air break class H insulation, with 16 A rating contactor and 6.0 A to 9.3 A overload relay complete including wiring from motor to DOL starter with suitable size of copper conductor cable complete all as specified and directed.(Make: Havells Cat No IHADOAH1K or equivalent in ABB/L&T/Schneider/C&SNote: Wiring from motor to starter with copper conductor will be measured and paid separately under relevant items |
| 6 | S&F automatic star delta starter suitable for 15 HP motors confirming to IS/IEC 60947-4-1, degree of protection IP-54 FRLS copper internal wiring, air break class H insulation, with 22 A rating contactor and 12.0 A to 18 A overload relay, including timer, single phase preventor, indicating push button, etc. complete ncluding wiring from motor to starter with suitable size of copper conductor cable complete all as specified and directed.(Make: Havells Cat No IHHASDTBW or equivalent in ABB/L&T/Schneider/C&SNote: Wiring from motor to starter with copper conductor will be measured and paid separately under relevant items |
| 7 | Supply and fix GI pipe heavy grade of 100 mm dia for pump suction including all accessories like bend, socket, nipple, union etc, necessary threading complete all as specified and as directed |
| 8 | Supply and fix GI pipe heavy grade of 80 mm dia for pump suction including all accessories like bend, socket, nipple, union etc, necessary threading complete all as specified and as directed |
| 9 | M&L sub main wiring with six runs of single core, PVC insulated, unsheathed multi standard copper conductor cable of size 6 Sqmm, 1100 volts grade (FRLS) drawn through and including suitable size flexible PVC conduit with all necessary accessories complete all as specified and as directed. (Note :- Six runs of 6 Sqmm cable, and one run of flexible PVC conduit with all necessary accessories will be measured as one length). |
| 10 | M&L sub main wiring with six runs of single core, PVC insulated, unsheathed multi standard copper conductor cable of size 4 Sqmm, 1100 volts grade (FRLS) drawn through and including suitable size flexible PVC conduit with all necessary accessories complete all as specified and as directed. (Note :- Six runs of 4 Sqmm cable, and one run of flexible PVC conduit with all necessary accessories will be measured as one length). |
| 11 | M & L earthing complete with GI earth plate Electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth plate not less than 2.25 Metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanished earth strip 25X4 mm by means of bolts, nuts check and washers of G I or steel all as shown in electrical plate No. 3 of SSR Pt -I connected to earthing test point all as specified or indicated including GI pipe 15 mm dia light grade for earth wire protection, necessary excavation, earth work in any type of soil, PCC chamber and RCC cover slab, connecting lead wire from test point to starter panel complete all as specified & as directed. |
| 12 | Taking down GI water tubing and connections from walls/ceiling/from trenches for clearing of any blockage for relaying or refixing of size 20 mm dia bore complete all as specified and directed by Engr-in Charge.Note: (i) Excavation, earth work and PCC work will be measured and paid separately under relevant items. |
| 13 | All as per item no 12 here in before but of size 25 mm dia bore |
| 14 | All as per item no 12 here in before but of size 40 mm dia bore |
| 15 | All as per item no 12 here in before but of size 50 mm dia bore |
| 16 | All as per item no 12 here in before but of size 80 mm dia bore |
| 17 | All as per item no 12 here in before but of size 100 mm dia bore |
| 18 | M & L for refixing or relaying of GI tubing taken down from trenches or walls/ceilings/floors etc in same or different locations as directed of size 20 mm dia bore complete all as specified and directed by Engr-in ChargeNote: (i) The rate quoted shall be inclusive of replacing the rusted or damaged collars/Tees/elbows/bends/unions/nipples, however any cutting, threading or screwing for alterations shall be measured and paid in relevant items. |
| 19 | All as per item no 18 here in before but of size 25 mm dia bore |
| 20 | All as per item no 18 here in before but of size 40 mm dia bore |
| 21 | All as per item no 18 here in before but of size 50 mm dia bore |
| 22 | All as per item no 18 here in before but of size 80 mm dia bore |
| 23 | All as per item no 18 here in before but of size 100 mm dia bore |
| 24 | M & L for cutting and screwing existing steel/GI tubing for alterations or additions (each cut measured) of size 20 mm complete all as directed |
| 25 | All as per item no 24 here in before but of size 25 mm dia bore |
| 26 | All as per item no 24 here in before but of size 40 mm dia bore |
| 27 | All as per item no 24 here in before but of size 50 mm dia bore |
| 28 | All as per item no 24 here in before but of size 80 mm dia bore |
| 29 | All as per item no 24 here in before but of size 100 mm dia bore |
| 30 | Supply, laying and connection of GI pipe medium grade with all fittings laid in trenches complete all as specified and directed of 20 mm dia size. Note:- Excavation and earth work shall be measured and paid separately |
| 31 | All as per item no 30 here in before but size of pipe 25 mm |
| 32 | All as per item no 30 here in before but size of pipe 40 mm |
| 33 | All as per item no 30 here in before but size of pipe 50 mm |
| 34 | All as per item no 30 here in before but size of pipe 80 mm |
| 35 | All as per item no 30 here in before but size of pipe 100 mm |
| 36 | Supply & lay GI tubing medium grade galvanised with all fitting complete fixed to walls and ceillings or laid on floors all as directed of 20 mm bore dia |
| 37 | All as per item no 36 here in before but of size 25 mm dia |
| 38 | All as per item no 36 here in before but of size 40 mm dia |
| 39 | All as per item no 36 here in before but of size 50 mm dia |
| 40 | All as per item no 36 here in before but of size 80 mm dia |
| 41 | All as per item no 36 here in before but of size 100 mm dia |
| 42 | Dismantling the existing unserviceable gate valves ,S & F gun metal globe/gate valve with inner wheel head, screwed both ends for iron pipes and fixed of 20 mm dia size complete all as specified and directed:- |
| 43 | All as per item No 42 above but 25 mm dia |
| 44 | All as per item No 42 above but 40 mm dia |
| 45 | All as per item No 42 above but 50 mm dia |
| 46 | Dismantling the existing unserviceable CI pipes and Supply, Lay and testing 100 mm dia cast iron pipes with spigot and socket ends centrifugally cast, class LA, in any length, laid in trenches.Note:- Excavation and earth work, CI fittings, run lead joints/push on joint will be measured and paid separately under relevant items |
| 47 | M&L cast iron bends (any type, radius and angle) tapers any type. (Straight, bend, increasing, decreasing or double socket etc) Tee pieces single branch, 'Y' junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs upto 150 mm bore. |
| 48 | M&L for rubber gasket (pushon) joint of same make of CI/DI pipe having two section of diferent hardness for DI pipe spigot & socket ends and fittings of bore dia 100 mm complete all as specified and directed |
| 49 | M & L cutting CI/DI pipes in position for insertion of new Tees, branches etc of dia 100 mm complete all as specified and as directed. |
| 50 | Dismantling the existing unserviceable Sluice Valve complete and S & F cast iron sluice valve with flange ends and drilled bolt holes , type PN-1.6, and stainless steel spindle, non rising stem type as per IS -14846 including hand wheel, bolts, nuts and jointing materials complete of the size 80 mm. |
| 51 | Dismantling the existing unserviceable Sluice Valve complete and S & F cast iron sluice valve with flange ends and drilled bolt holes , type PN-1.6, and stainless steel spindle, non rising stem type as per IS -14846 including hand wheel, bolts, nuts and jointing materials complete of the size 100 mm. |
| 52 | Dismantling the existing unserviceable non return Valve complete and S & F cast iron Non return valve swing type/butterfly type with flange ends and drilled bolt holes including bolts, nuts and jointing materials complete of size 100 mm. |
| 53 | Excavation in trenches n. exc. 1.5 M wide and n. exc. 1.5M in depth and getting out in hard and dense soil for laying of GI/DI/CI pipe complete all as specified and as directed |
| 54 | Returning, filling in including spreading,levelling watering and well ramming in layers not excluding 25 cms in any type of soil. |
| 55 | Removing excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 M above the starting point all as directed. |
| 56 | M&L for PCC 1:3:6 type C1 with 20mm graded stone aggregate as in foundation for making good road surface where as road crossing of pipe lines , hardstandings etc. |
| 57 | M & L for disconnecting existing tanks, setting aside or lowering if required for repairs, cleaning etc and hoisting if required, reconnecting and refixing in position of capacity 500 ltrs complete all as specified and as directed. Note: Cleaning and repairing etc will be measured and paid separately. |
| 58 | All as per item No 57 above but 1000 ltr capacity |
| 59 | Supply and fix rotational moulded polythylene water storage tanks of capacity 500 ltrs (cylindrical vertical with closed top) hoistd and fixed in position all as specified and as directed. |
| 60 | All as per item No 59 above but 1000 ltr capacity. |
| 61 | Supply and fix ball valves of size 15 mm high pressure PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed (Minimum weight 142 gms) |
| 62 | Supply and fix ball valves of size 20 mm high pressure PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed (Minimum weight 210 gms) |
| 63 | Supply and fix ball valves of size 25 mm high pressure PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed (Minimum weight 455 gms) |
| 64 | Demolition of existing old unserviceable brick masonary valve chamber including demolition of unserviceable M.S iron cover and iron frame and Construction of brick masonry valve pit of size 90cm x 90cm X 90 cm (internal dimensions) with one brick thick wall in cement mortar 1:4 on 100mm thick PCC 1:4:8 type D2 ( using 40mm graded broken stone aggregate) as in foundation lean concrete, including PCC 1:3:6 type C-1 ( using 20mm graded crushed stone aggregate) as in benching and coping and 10mm thick cement plaster in CM (1:4) internally and externally upto 15cm below ground level providing valve pit cover 40x40x6mm angle iron frame all-round fixed by means of 4 Nos holdfast 150mm long made out of flat iron 40x6mm embedded in PCC block (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) of size 230x200x100mm incl provn of hinges welded with angle iron frame and MS cover 3mm thick sheet, MS handle of suitable length and size welded with MS cover and suitable locking arrangement and applying two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation and earth work in soft/ loose soil complete all as shown on drawing and as specified. Please Enable Macros to View BoQ information |