| 1 | Excavating in trenches not exceeding 1.50 m wide and 1.50 m depth. for laying HT cables (0.50m wide & 1.0m depth) for laying pole pit (1.0m wide & 1.5m depth) getting it out soft/loose soil. Note: Digging by JCBs are not allowed. |
| 2 | Excavating in trenches beyond 1.50 m depth but not exceeding 3.0 m depth, getting it out soft/loose soil (for pole pit). |
| 3 | Sand cushioning in cable trenches 20cm thick including material & labour. |
| 4 | Supplying & laying un-reinforced precast concrete cable cover class HV type 1 flat size 300mmx180mmx40mm with identification of cable cover with material & labour. |
| 5 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm. |
| 6 | GI pipe medium grade confirming to IS no. 1239 (part I & II) 100mm dia with all fittings and fixed completely to poles & laid in trenches with material & labour. |
| 7 | Demolition & dismantling Cement concrete in ground floors & pavings not exceeding 15 cm thick below or above ground level. |
| 8 | M&L PCC Type B2, mixed by volume 1:2:4 with 40 mm normal size graded coarse aggregate. |
| 9 | Supply & fixing Cable jointing kit for 11 KV (Earthed ) grade cable for outdoor termination heat shrinkable type complete with jointing material and accessories suitable for 3 core XLPE armoured alluminium conductor cable of size 120 to 185 Sq.mm material & labour. Make: M seal/Raychem/Cabseal. |
| 10 | Danger Notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with M.S.clamps, bolts and nuts of approved size for HT 25x20 cm size as per IS 2551 with material & labour. |
| 11 | Supply & fixing cross arm of MS channel bracings,supports,clamps and back plates fabricated from structural steel section including nuts & bolts, washers,welding,bending, cold or hot, drilling holes for bolts in any shape or size as indicated or directed & inclusive of one primer coat, one under coat & one finishing coat of paint with material & labour. |
| 12 | S & L of XLPE insulated (confirming to IS no. 7098 part 2) screened PVC bedded galvanized steel strip or wire armoured, electric power cable (Heavy duty) with aluminium conductor 11000 Volt grade size 185 Sq.mm 3 core including termination of both the ends with proper lugs. Make of cable: Unistar/Finolax/Havells/Sterlite/KEI/V-gaurd/Polycab/Unistar or Equivalent. |
| 13 | Boring holes 3m deep and 300mm diameter in soil for under reamed piles and getting out and disposal of spoil to a distance of n exc. 50 m |
| 14 | M&L Reinforced cement concrete (Design mix) of type M- 20, 1:1½:3 (20mm graded aggregate) in foundations, footings, under reamed piles etc. conforming to quantitative analysis report of the materials to be submitted by the contractor before execution of concretting work. |
| 15 | M&L Reinforced cement concrete columns, pillars, plers (Design mix) of type M- 20, 1:1½:3 (20mm graded aggregate) conforming to quantitative analysis report of the materials to be submitted by the contractor before execution of concretting work. |
| 16 | M&L, Form work to sides of pillars, columns (square or rectangular) etc for fair finished surfaces. |
| 17 | Mild steel TMT bars 10 mm dia cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not lass than 0.9 mm dia or securing with clips. Complete all as specified & directed. |
| 18 | Mild steel TMT bars 6mm to 8 mm dia cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not lass than 0.9 mm dia or securing with clips. Complete all as specified & directed. |
| 19 | M&L Reinforced cement concrete (Design mix) of type M- 20, 1:1½:3 (20mm graded aggregate) in beams, lintels over 1.5m span. conforming to quantitative analysis report of the materials to be submitted by the contractor before execution of concretting work. |
| 20 | M&L, Form work to sides and soffits of roof beams, lintels etc. for fair finished surfaces. |
| 21 | Earthing complete with GI plate electrode 600x600x6.0mm thick burried directly in ground (earth plate not less than 2.25m below ground level) including excavation of soil, with top edge of the plate not less than 1.5m below normal ground level and duly filled with alternate layer of char coal & salt from 150mm below the plate to 150mm above the plate (total 900mm thick) connected to GI earth strip size 25x4mm in GI protection pipe of size 40mm dia upto 7.5m long by means of nuts, bolts, washers, check nuts of GI steel, fitted with funnel complete all as per procedure and as shown in SSR electrical plate No. 3. Connected to earth test point/earth bus (to be provided near incoming mains) all as specified and testing including RCC earth pit chamber duly cement plaster finished and RCC pit cover 1mX1mX150mm, PCC hard standing surrounding the earth pit chamber, location of the earth pit marked on the nearest wall to be written with paint (for distance & value of earth pit) with material and labour. Earth pit chamber will be made 0.5m above the ground level. |
| 22 | M&L Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-64 (12 metre long) (confirming to IS no. 2713 part 1 & 3) |
| 23 | Supply & fixing Cable route marker of Cast Iron size 150mm x 100mm x 3mm thick, embosing 11000 volt, U/G HT cable & size, fixed with nuts & bolts on MS angle iron size 40mmx40mmx5 mm, length 1700 mm, burried 500mm in the ground with cement concrete (1:3:6) of size (200mmx200mmx300mm) with material & labour. |
| 24 | Boring holes/ auguring not exceeding 150mm dia 1m deep for passing HT/LT under ground cable across the road/gantry. complete all as specified & directed. Please Enable Macros to View BoQ information |