| 1 | Wiring for light point / fan point / exhaust fan point /call bell point with 1.5 mm. sq FRLS insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI Box and earthing the point with 1.5 mm. sq FRLS insulated Copper conductor single core cable etc asrequired. |
| 2 | Group-\\"C\\" |
| 3 | Rewiring for light point/fan point/exahust point/call bell point with1.5SQmm FRLS PVC insulated copper conducter S/c cable and1.5 sq.mm.FRLS PVC insulated copper conductor S/C cable as earth wire in existing surface/recessed steel /PVCconduit,i/c dismentling asrequired. |
| 4 | Group-C |
| 5 | Supplying and fixing suitable size G.I box with Modular Plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps. modular socket outlet and 5/6 amps modular switch, connections, painting etc.as required. |
| 6 | Supplying and fixing suitable size G.I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connections, painting etc.as required. |
| 7 | Supply & Drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit asrequired. |
| 8 | 3x2.5 sq.mm. |
| 9 | 6x2.5 sq.mm. |
| 10 | 3x4 sq.mm. |
| 11 | 5x4 sq.mm. |
| 12 | 6x4 sq.mm. |
| 13 | Supply & fixing of following sizes of medium class PVC conduit alongwith accessories in surface/recess i/c painting in case of surface conduit,or cutting the wall & making good the same in case of recessed conduit as reqd. |
| 14 | 20 mm |
| 15 | 25 mm |
| 16 | Supply & Fixing of metal box of following size (nominal Size) on surface or in recess with following size of phenolic laminated sheet cover in fronti/c painting etc.as required. |
| 17 | 200 mm x 250 mm x 60 mm deep |
| 18 | S & F two module stepped type electronic fan regulator on the existing modular plate switch box i/c connection but excluding modular plate etc.as reqd. |
| 19 | Supply & Fixing following size/module,GI box alongwith modular base & cover plate for moduler switches in recess etc.as reqd. |
| 20 | 8 Module (125 mm x 125 mm) |
| 21 | 12 Module (250 mm x 150 mm) |
| 22 | S & F following Modular base & cover plate on existing modular boxes etc.asrequired. |
| 23 | 8 Module |
| 24 | 12 Module |
| 25 | Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd. |
| 26 | 5/6 Amp.Switch |
| 27 | 15/16 Amp.Switch |
| 28 | 3 pin 5/6 Amp.Socket Outlet |
| 29 | 6 pin 15/16 Amp.Socket Outlet |
| 30 | Supply & Fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as reqd. |
| 31 | Supplying & Fixing 20 A,240 V, SPN Industrial type socket outlet with 2 pole & earth,metal enclosed plug top alongwith 20 A \\"C\\" curve,SP,MCB, in sheet steel enclosure, on surface or in recess,with chained metal cover for the socket out let & complete with testing & commissioning etc.as required. |
| 32 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 33 | 8 Way, Double Door |
| 34 | 12 Way, Double Door |
| 35 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 36 | 4 way (4 + 12), Double door |
| 37 | 6 way (4 + 18), Double door |
| 38 | Supply & Fixing Cable End Box (Loose Wire Box) suitable for following single pole & neutral,sheet steel,MCB distribution board,240 Volts,on surface/recess,complete with testing & commissioning etc,as required. |
| 39 | For 8 Way, Double Door SPN MCBDB |
| 40 | Supply & Fixing Cable End Box (Loose Wire Box) suitable for following Tripal pole & neutral,sheet steel,MCB distribution board,415 Volts,on surface/recess,complete with testing & commissioning etc,as required. |
| 41 | For 4 Way, Double Door TPN MCBDB |
| 42 | For 6 Way, Double Door TPN MCBDB |
| 43 | Supplying and fixing 5 A to 32 A rating, 240/415V,10 KA, \\"C\\" curve miniature circuit breaker suitable for inductive load of following pole in the existing MCB DB complete with connection testing and commissioning etc, as required. |
| 44 | Single Pole |
| 45 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioningetc. as required. |
| 46 | 40 Amp. |
| 47 | 63 Amp. |
| 48 | Supply and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connection, testing and commissioning etc, as required. |
| 49 | 63 Amp. |
| 50 | 100 Amp. |
| 51 | P & F of 6 SWG dia.G.I. wire on surface or in recess for loop earthing along with existing surface/recessedconduit/submain wiring/cable as reqd. |
| 52 | P & F 25mm x 5mm G.I.strip on surface or in recess for connection etc. as reqd. |
| 53 | Laying of one number pvc insulated and PVC sheathed/ XLPE power cable of1.1 kv grade of following size in the existing masonary open duct asrequired |
| 54 | Upto 35 sq.mm. |
| 55 | Above 35 sq.mm. & upto 95 sq.mm |
| 56 | Laying of one number pvc insulated and PVC sheathed/ XLPE power cable of1.1 kv grade of following size in theexisting surface as required |
| 57 | Upto 35 sq.mm.(Clamped with 1 mmthick saddle) |
| 58 | Above 35 sq.mm. & upto 95 sq.mm.(Clamped with 25x3 mm thickMS flat clamp) |
| 59 | Supplying and installing following size of perforated painted with powder coating MS Cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 60 | 100 mm width X 50 mm depth X 1.6 mmthickness |
| 61 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 62 | 100 Amp.16 KA,TPMCCB |
| 63 | 200 Amp.25 KA,TPMCCB |
| 64 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 65 | 4X50 sqmm.(35 mm) |
| 66 | 4X70 sqmm.(38 mm) |
| 67 | S/I/T/C of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000/4000/5700/6000/6500°K (As perANSI Bin), SDCM(Standard Deviation Color Matching <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum5 year OEM warranty. System lumen |
| 68 | 18 - 22 Watt |
| 69 | S/I/T/C of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS:- 374:2019 fan,Supply,earthing etc.as reqd. |
| 70 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min(Minimum) |
| 71 | S/I/T/C of Panel light 2x2 ft., of following body material and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR(Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM- 21-11 report, CCT 3000°K / 4000°K /5700°K /6000°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum |
| 72 | 36 Watt |
| 73 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPMwith desired color |
| 74 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*25 sqmm |
| 75 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*70 sqmm |
| 76 | Supply,Installation, testing and commissioning of power distribution board made out of 1.6 mm sheet steel, epoxy powder coated , specially designed Al bus bar 400A to 630A with heat shrinkcable colour coated sleeves suitable for accommodating MCCBs/MCBs /Isolators as incoming and outgoing as required (without MCCBs/MCBs/Isolators ) complete with digital meter module, including Voltmeter Ammeter with selector switch, CTs control fuse and indicating lights including connections etc. as required ( Conforms to IS:8623) |
| 77 | Supplying, Installation, testing and commissioning of earth pit of minimum dia. 100 mm size 3 mtr. Deep in hard rock soil, through machine or by any suitable means. Earth electrode consisting of 3 mtr. Long and 50 mm Dia. Size G.I electrode surrounded by highly conductive black fill compound chemical 2 bags (25 kg each) with necessary masonry encloser for 300 mm x 300 mm size GI earth pit cover complete as required. Please Enable Macros to View BoQ information |