Supply, Installation, Testing & Commissioning of ESE Lightning Air terminal with below specifications: -- Stainless Steel Material 316L which is suitable for corrosive environment- CPRI (Government of India) Laboratory or equivalent laboratory holding valid accreditation- Tested & Certified for 70kA (8/20 Micro Second)- Lightning Impulse Current Tested – 200kA (10/350 microsec) from NFC 17-102 Accredited International Lab or equivalent laboratory holding valid accreditation- Tested Laboratory- ITE LAB (SPAIN) which is Accredited/certified by ENAC and ILAC or equivalent laboratory holding valid accreditation- Triggering Time (delta T) = ∆60 micro seconds- Mechanical Test, Environmental test (Salt Mist Treatment, Humid Sulphurous atmosphere treatment)- 20 Year Warranty- CE Certified- Protection Radius- 107 meter (Level IV/ Standard)
3
Supply, Installation, Testing & Commissioning of 15-meter pole for fixing ESE Lightning arresters as per site condition.
4
Supply, Installation, Testing & Commissioning of 70sqmm Single Core Copper Insulated Flexible Down Conductor Cable (Which will be connected from Air Terminal to Earth Pit)
5
Supply, Installation, Testing & Commissioning of 6 Digit Mechanical Lightning Strike Counter with IP67 enclosure box, which will count the number of strike events.
6
Supply, Installation, Testing & Commissioning of Test Link Box with IP 67 enclosure box with accessories
7
Supply, Installation, Testing & Commissioning (SITC) of Maintenance Fee Copper Bonded Earthing Rod with 50kg (25kg x 2 Bag) back filing compound below specifications:-Copper Bonded Earthing Rod:- Certified by CPRI and NABL Accredited Lab- - ROHS certified- - Low Carbon high Tensile Steel Rod- - Length of Rod 3000 mm (3 Meter)- - Rod dia 17.2 mm- - Copper Plating Thickness 250 micron (Minimum)- - Connection Terminal Size 50*6*100mm (4G)Earth Enhancement Compound:- Compliance/Standard- IEC 62561-7- Compound Base- Heigh Conductive Carbon- Compound Resistivity- 0.12ohm/Meter- pH Value- 7-8- Compressive strength- Min 200kgf/CM2.- Thermal Strength- -10 c to + 60 c- Sulphur- 0.38%- Tested by NABL accredited Lab.Heavy Duty Fiber Reinforced Polymers Pit Cover:- Weight Carrying Capacity 5 Ton- Lockable arrangement- Top Dia 240mm- Bottom Dia 335mm- Height 260mmAs per IEC 62561-5 Tested by NABL Accredited LAB
8
Total impact of GST for the purpose of CTC Please Enable Macros to View BoQ information