| 1 | Erection of MDP in GF North Wing Master Electrical Room: Installation, testing, and commissioning (IT&C) of available cubicle-type Main Distribution Panel (MDP), comprising a 630A incomer and 4 Nos. of 250A outgoing feeders, by supplying all necessary accessories and supporting structures as required. The available panel shall be suitable for incoming and outgoing cable entry from both top and bottom. Installation can be as per the site requirements. |
| 2 | Erection of SDPs, Model-I: IT&C of available cubicle-type sub-distribution panels (SDPs) in GF South, FF South, SF South, and SF North Electrical Rooms, comprising 250A incomer and 4 Nos. 125A outgoing feeders. The work includes supply and fixing of all necessary accessories and supporting structures. The available SDPs shall be suitable for both top and bottom cable entry for incoming and outgoing cables. Installations can be as per the site requirements. |
| 3 | Erection of SDPs, Model-II: IT&C of available cubicle-type SDPs in FF North and GF North Electrical Rooms, comprising 200A incomer and 6 Nos. 63A outgoing feeders. The work includes supply and fixing of all necessary accessories and supporting structures. The available SDPs shall be suitable for both top and bottom cable entry for incoming and outgoing cables. Installations can be as per the site requirements. |
| 4 | Lighting and Power DB (LPDB): SIT&C of 7-Segment, 8-Way, TPN DB-double (metal) door type, powder coated finish, IP-43 protected, suitable for 415 V, 3-phase, 4-wire system, conforming IS 8623-3.One complete DB set shall be provided for each of the six Electrical RoomsIncomer 4P MCB 63A, C-Curve, 4P, 10kA (Breaking Cap.), MCB, conforming to IS 60898-1 - 1 No.Sub Incomers RCCB 63A, DP, 30mA RCCB conforming to IS 12640-1 -3 NosOutgoing SP MCBs 6A/10A/16A/20A/32A SP 10kA, C Curve MCBs conforming to IS 60898-1 - 24 Nos. Blank Plates - 0 Nos. |
| 5 | HVAC DB: SIT&C of 8-way VTPN DB: double (metal) door type, powder coated finish, IP-43 protected, 415 V, 3-phase system, Conforming to IS 8623-3. One complete DB set shall be provided for each of the six Electrical RoomsIncomer MCCB 100A TPN, 16kA MCCB, conforming to IS 60947-2 - 1 NoOutgoing 3P MCB 3P 40A/63A, C curve MCB, 10kA, conforming to IS 60898-1 - 4NosOutgoing SP MCB 6A/10A/16A/20A/32A SP 10kA, C Curve MCBs conforming to IS 60898-1 - 12NosBlank Plates - 0 Nos |
| 6 | UPS MAIN DB: SIT&C of 6-way VTPN DB: double (metal) door type, powder coated finish, IP-43 protected, 415 V, 3-phase system, Conforming to IS 8623-3.Each one set for FF South Wing Electrical Room and FF North Wing Electrical Room. Incomer MCCB 63A TPN, 16kA MCCB, conforming to IS 60947-2 -1 No.Outgoings 3P MCB 40A, 3P, D-curve. 10kA MCB conforming to IS 60898-1 - 3NosOutgoing SP MCBs6A/10A/16A/20A/32A SP D Curve, 10kA MCB, Conforming to IS 60898-1 -9 NosBlank Plates - 0 Nos. |
| 7 | UPS Output DB: SIT&C of 8-way SPN DB: double (metal) door type, powder coated finish, IP-43 protected, 240V, 1-phase system, Conforming to IS 61439-3. In five different halls of different wings/floors.Incoming DP MCB 32A DP 10kA D curve MCB, Conforming to IS 60898-1 -1 No.Outgoing SP MCBs 6A/10A/16A SP D Curve, 10kA MCB, Conforming to IS 60898-1 -6 Nos.Blank Plates -0 Nos. |
| 8 | Inverter Feeder DB: 8-way SPN DBIncoming DP RCCB 40A DP 30mA, 10kA RCCB, conforming to IS 12640-1 -1 No.Outgoing DP MCBs 16A/20A DP 10kA, B Curve MCBs conforming to IS 60898-1 -3 Nos.Blank Plates - 0 Nos. |
| 9 | Inverter Load DB: 8-way SPN DBIncoming DP RCCB 40A DP 30mA, 10kA RCCB, conforming to IS 12640-1 -1 No.Outgoing SP MCBs 6A/10A/16A/20A SP 10kA, B Curve MCBs conforming to IS 60898-1 -6 Nos.Blank Plates - 0 Nos. |
| 10 | UPS/Home Inverter Charging Points:Metal Enclosure: Two module metal enclosure, conforming with IS 61439-3, IP43 rated, suitable for both Surface and Flush mounting, made by high-quality CRCA sheet steel, powder-coated for corrosion resistance, 40A/32A rated. 1 No.MCB40A/32A DP D curve, 10kA MCB conforming to IS 60898-1 1 No.For charging the UPS inside five halls (5 nos.) and home inverter in GF south and north power rooms (2 nos.), making a total of seven DB sets |
| 11 | Single-phase Split A/C Points:Metal Enclosure: 6 Module Industrial Plug & Socket Enclosure, CRCA sheet steel and powder-coated (IS 61439-3), must accommodate a 25A MCB and Metal Clad Plug & Socket 1 No.MCB25A DP C curve, 10kA MCB confirming to IS 60898-1 1 No.Metal Clad Plug & Socket 3-pin, 32A IP44 rated Metal Clad Plug & Socket conforming to IS 12943 1 No. |
| 12 | Three-phase A/C Points:Metal Enclosure: 4-Module Enclosure, CRCA sheet steel and powder-coated, must accommodate a 32A MCB, conforming to IS 61439-3. 1 No.MCB32A, 4P, C curve, 10kA MCB conforming to IS 60898-1. 1 No. |
| 13 | Laying, Dressing, Testing and Commissioning (LDT&C) of available 3.5C, 150Sq.mm Al Ar Cable in 2 RunsMain incoming cable to MDP (1 no.) |
| 14 | LDT&C of available 3.5C x95 Sq.mm Al Ar Cable MDP to SDPs (6 nos.) |
| 15 | SLDT&C of 3.5C, 70Sq.mm Al Ar Cable SDPs to HVAC DBs (6 nos.) |
| 16 | SLDT&C of 4C, 25Sq.mm Al Ar Cable SDPs to LPDBs (6 nos.) and SDPs to UPS main DBs (1 no. at each wing FF electrical room) |
| 17 | SLDT&C of 3C 10 Sq.mm Al. Ar Cable UPS main DB to UPS charging points (5 nos.) and UPS main DB to Home Inverter charging points (2 nos.) |
| 18 | SLDT&C of 4C 6Sq.mm Cu Ar CableHVAC DB to 3-phase Tower A/C points (13 nos.) |
| 19 | SLDT&C of 3C 4Sq.mm Cu Ar CableHVAC DB to 1-phase Split A/C points (9 Nos.) |
| 20 | Glands for 3.5C x150Sq.mm Al Ar Cable |
| 21 | Glands for 3.5C x95 Sq.mm Al Ar Cable |
| 22 | Glands for 3.5C x70Sq.mm Al Ar Cable |
| 23 | Glands for 4C x25Sq.mm Al Ar Cable |
| 24 | Glands for 3C 10 Sq.mm Al.Ar Cable |
| 25 | Glands for 4C 6Sq.mm Cu Ar. Cable |
| 26 | Glands for 3C 4Sq.mm Cu Ar. Cable |
| 27 | Cable tray: 150 mm (W) x 50 mm (H) x 1.6 mm (T) Perforated type cable tray made from JSW prime quality steel. The tray shall be Hot-Dip Galvanized (HDG) after fabrication as per IS 2629/IS 4759 (minimum 65-80 microns coating). The scope includes a matching GI Tray Cover, GI Coupler Plates, Zinc-plated/GI Hardware (Nuts, Bolts, Washers), and necessary support systems (C-channel/Angle/Threaded Rods) as per site requirements.For all six electrical rooms between SDP and DBs – 6x12 =72Mtr |
| 28 | Cable tray: 300 mm (W) x 75 mm (H) x 1.6 mm (T) Perforated type cable tray manufactured from JSW prime quality Steel. The tray and all its accessories must be Hot-Dip Galvanized (HDG) after fabrication as per IS 2629 / IS 4759. The system shall be complete with a matching GI Tray Cover, GI Coupler Plates, Zinc-plated/GI Hardware (M8/M10 Bolts), and necessary support systems.In each wing’s east corridor, staring from respective wing’s electrical room, 1 run-6x 28 Mtrs 170Mtrs |
| 29 | Earthing Electrode: 40 mm diameter, 3-meter length, 80 to100 microns Copper Coating, high-tensile low-carbon steel core conforming to IS 3043. |
| 30 | Earth Enhancement Material: 50 Kg High Conductive \\"Earth Life\\" Compound. Non-corrosive, moisture-retaining, and swells to eliminate air pockets conforming to IS 3043 |
| 31 | SLC&C of 1C, 10 sq.mm Cu flexible FRLS PVC insulated, 1.1 kV grade wire conforming to IS 8130 & IS 694. |
| 32 | SLC&C of 8 SWG (4.06 mm Diameter) Bare Copper Wire for earthing. The wire shall be manufactured from High Conductivity Electrolytic Grade Copper (min 99.9% purity) as per IS 191. |
| 33 | SLC&C of 1C x 6 sq. mm Cu flexible FRLS PVC insulated, 1.1 kV grade wire conforming to IS 8130 & IS 694. |
| 34 | SLC&C of 25 mm (W) x 3 mm (T) tinned/bare Copper Earth Link of 500 mm length. The link shall be made of Electrolytic Grade Copper as per IS 191. It shall be pre-drilled with holes of 8 mm diameter to accommodate multiple earth terminations. |
| 35 | SLC&C of 25 mm x 3 mm GI Flat. The base material shall be Mild Steel conforming to IS 2062 and galvanized as per IS 2629, with a minimum zinc coating thickness ensuring protection against soil and atmospheric corrosion with all required accessories |
| 36 | Supplying and wiring (S&W) of power points with 2 Run 4 Sq. mm. (one each for Phase & Neutral) + 1 Run 2.5 sq.mm. (for earth) wires routed through PVC round conduit/uPVC casing-capping with necessary clamps, screws, etc. |
| 37 | Supplying and fixing (S&F) of 3 Nos. of 6/16A 3-pin Combined Socket controlled by 2 Nos. of 16A Switch with face plate and GI 8 Module back box in complete.Raw Supply Surface Power Outlet for printers and other loads |
| 38 | S&F of 2 nos. of 6A 5-pin Socket controlled by 2 nos. of 6A switch with 6M GI surface boxFor additional points at valuation hall, etc. |
| 39 | S&F of one no. of 6/16A Universal 5-pin Socket controlled by one 16A switch with 3M box.For additional points at water filter and other required places |
| 40 | S&W of Power Points with 3R 2.5 Sq. mm. PVC Insulated FRLS multistranded copper conductor wire or 3C 2.5 sq. mm copper cable routed through PVC round conduit/uPVC casing-capping with necessary clamps, screws, etc. |
| 41 | S&F of 3 Nos. of 6A, 5-pin Socket controlled by 1No. of 16A Switch, 1 module indicator included with 8M box (colour differentiating the box from the Raw Supply Surface Power Outlet boxes).UPS Supply Surface Power Outlet for Desktop Computers |
| 42 | Mains Wirng (LPDB to Switch Board): S&W of the Light Points with 3R of 2.5 Sq. mm PVC Insulated multistranded FRLS copper wires (one each for Phase, neutral and earth) conforming to IS 8130 & IS 694, routed through PVC round conduit/uPVC casing-capping with necessary clamps, screws, etc. |
| 43 | Primary Point (Switch Box to first Light /Fan Point). |
| 44 | Secondary Point (Light to Light /Fan Point). |
| 45 | SIT&C of ISI certified 48inch (1200mm) Ceiling Fan, Star rated, Sole Copper Coil, induction motor, less than 60W, Aluminium blade and body, Matt Finish, Double Ball Bearing, Minimum of 210CMM Air Delivery, Speed more than 365 RPM, minimum 2 years warranty, with regulator and all standard accessories, conforming to IS 374. |
| 46 | S&F of 3ft to 4ft down rod suitable for Ceiling fan and S&F of anchor fastner fan hook, depending upon site condition. |
| 47 | SIT&C of 36 W T5 type 4 ft LED tube light with minimum luminous efficacy of 100 lm/W, providing uniform, glare-free illumination. Rated for 230 V AC, 50 Hz operation, with a minimum service life of 15,000 hours, Surge Protection up to 4kV, compliant with IS 16103 (for LED modules) and IS 10322 (for luminaires). |
| 48 | SIT&C of 36 W, 2' × 2' recessed LED panel light luminaire with a minimum luminous flux of 3,000 lumens, providing uniform, glare-free illumination. Correlated Colour Temperature (Nominal): 6500 K, light source colour: 840 (neutral white). Rated for 230 V AC, 50 Hz operation, with a minimum service life of 15,000 hours and surge protection up to 4 kV. The luminaire shall be compliant with IS 16103 (for LED modules) and IS 10322 (for luminaires), with a minimum service life of 25,000 hours, Surge Protection up to 2.5kV. |
| 49 | S&F accessories like Ceiling Rose, etc. which shall be assessed and appraised in the site visit |
| 50 | Supply and Laying (S&L) of 2000 mm. x 1000 mm x 3 mm rubber electrical insulating rubber mat, made from high-quality elastomeric material, suitable for use in electrical panels and switch rooms, with non-slip surface finish conforming IS 15652To be laid in front of the panel boards. |
| 51 | S&L of Chequered plates for EB Room: 6 mm thick MS chequered plate, hot-rolled, suitable for heavy-duty flooring applications, manufactured from structural steel conforming to IS 2062 Grade E250A, with raised chequer pattern for anti-skid surface, providing high strength, durability, and resistance to mechanical wear. |
| 52 | 25mm Diameter, Heavy Duty (wall thickness of 2.0mm to 2.2mm), Rigid PVC Round Conduit conforming to IS 9537-3.For LCD projector power cable |
| 53 | Rigid, Heavy-Duty (High Impact) PVC Conduits of [32mm/40mm] Outer Diameter, conforming to IS 9537-3, with low-friction internal finish and minimum wall thickness of 2.2mm (for 32mm) or 2.5mm (for 40mm)For LCD projector HDMI cable |
| 54 | S&L of High-Speed HDMI Cable with Ethernet (Version 2.0 or 2.1), 4K UHD @ 60Hz Support, 18Gbps Bandwidth, 24K Gold-Plated Connectors, Triple Shielded, and Oxygen-Free Copper (OFC) Conductors. Compliance: IS 13252-1 and HDMI 2.0/2.1 Standards |
| 55 | S&L of 2-Core, 1.5 sq. mm Flexible Speaker Cable with High-Purity OFC conductors, multi-stranded, PVC Insulated (FR/FR-LSH), conforming to IS 8130 for conductors and IS 5831 for insulation routed through PVC round conduit/uPVC casing-capping with necessary clamps, screws, etc. |
| 56 | Cutting and opening the false ceiling (gypsum board) to facilitate installation of fan rods, light fittings, and cable laying works; Refixing the gypsum board after completion of the work, and repainting with white colour to restore the original finish. This lump sum quantity shall be assessed and appraised in the site visit. Please Enable Macros to View BoQ information |