| 1 | Supply, install, testing & commissioning of LT control panel board \\"out-door type\\" of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands and lugs of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) complete all as specified & as directed with & including the following accessories : |
| 2 | (X-MER Panel)(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing/New LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 A - 01 Nos. Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand /Siemens/Havells. |
| 3 | OUTGOINGS :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 Amps - 02 (01W+1S) Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells.(e) MCB SPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens/Havells.(f) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. |
| 4 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 5 | All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:(Stn HQ Panel, RHQ Panel & ORs Mess and Line Panel)(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells(b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 200 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO22000OOOO or techno-commercially equivalent in ABB/ Siemens. |
| 6 | OUTGOINGS :(a) MMCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 03 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 03 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(c) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells.(d) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. |
| 7 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 8 | All as per item 1 here in before but of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:( MI Room Panel)(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a)MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells(b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 160 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO21600OOOO or techno-commercially equivalent in ABB/ Siemens. |
| 9 | OUTGOINGS :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 Nos Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 05 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(c) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells.(d) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens/Havells. (e) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells. |
| 10 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 11 | All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:-(Officer Mess Panel & 62.5 KVA DG Set EB Panel )(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 01 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells. |
| 12 | OUTGOINGS :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 02 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 A - 02 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 04 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(d) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells.(e) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 63 Amps - 03 No. Make : L&T /Legrand /Siemens/Havells. |
| 13 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 14 | All as per item 1 here in before but of size 1800 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:-(125 KVA DG Set Panel)(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a)MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 200 to 250 A - 01 Nos. Make : L & T, Cat No : CM90642OOPO or techno-commercially equivalent of Legrand /Siemens/Havells.(b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 200 Amps, 415 Volts, 4 Pole, AC - 01 No. Make : L & T, Cat No : CO22000OOOO or techno-commercially equivalent in ABB/ Siemens. |
| 15 | OUTGOINGS :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 160-200 A - 02 Nos. Make : L & T, Cat No : CM90642OONO or techno-commercially equivalent of Legrand /Siemens/Havells. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 02 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells.(c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(d) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells.(e) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T /Legrand /Siemens/Havells. |
| 16 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 17 | All as per item 1 here in before but of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories:-(Mandir Panel & JCO Mess Panel)(i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 125 to 160 Amps - 01 . Make : L & T, Cat No : CM90642OOMO or techno-commercially equivalent of Legrand /Siemens/Havells. |
| 18 | OUTGOINGS :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 04 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens/Havells.(b) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete . Make : L&T, Cat No (AUTS02DIG00- timer, CS94190-contactor) or techno-commercially eqvt of Legrand /Siemens/Havells.(d) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 No. Make : L&T/Legrand /Siemens/Havells.(e) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 02 No. Make : L&T /Legrand /Siemens/Havells. |
| 19 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : L & T, Cat No: WL411010OOOO or techno-commercially equivalent of Elmeasure /Secure.(b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 20 | Supply, install, testing & commissioning of LT busbar junction box \\"out-door type\\" of size 750 mm (height) x 600 mm (breadth) x 300 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The box shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar of Size 300mm x 70mm x 6mm , min spacing of 75mm between the busbars & wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming cable rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including I/C & O/G cable opening on bottom & at both sides including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl Incoming MCCB of 63 Amps in seprate portion complete all as specified & as directed. Please Enable Macros to View BoQ information |
| 21 | Supply, install, testing & commissioning of LT busbar junction box \\"out-door type\\" of size 750 mm (height) x 600 mm (breadth) x 300 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The box shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar of Size 300mm x 70mm x 6mm , min spacing of 75mm between the busbars & wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming cable rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including I/C & O/G cable opening on bottom & at both sides including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl Incoming MCCB of 63 Amps in seprate portion complete all as specified & as directed. Please Enable Macros to View BoQ information |