| 1 | SUB HEAD 1 -- DISTRIBUTION WIRINGDistribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC[ 1(a)/(i)/E-14 ] |
| 2 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC[ 1(a)/(ii)/E-14 ] |
| 3 | 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC [ 1(a)/(iv)/E-14 ] |
| 4 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes as per GS.1.5 Sq mm [ NS ] |
| 5 | 2.5 Sq mm [ 9(i)/ F-5 ] |
| 6 | 4 Sq mm [ 9(ii)/ F-5 ] |
| 7 | 6 Sq mm [ 9(iii)/ F-5 ] |
| 8 | SUB-HEAD 2-- PLUGS & SOCKETSSupply & Fixing 240 V, 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board incl. S & F 100x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws as per GS. -- [ 17(b)/E-6 ] |
| 9 | SUB-HEAD 3 -- BDB,PDB,VTPN ETCSupplying and fixing Sheet steel Main Switches on flat iron frame on wall.240 V, 32 A DP Main Switch with fuse on L&N ( Make - Havells ) [ 1(a)/D-1 ] |
| 10 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment2 Way Enclosure [ 11/D-9 ] |
| 11 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs as per GS. --6-32 A SP MCB [ Make - Legrand/L&T ] [ 7/D-6 ] |
| 12 | 6-32 A DP MCB [ Make - Legrand ] [ 7/D-6 ] |
| 13 | SUB HEAD 4 -- SUPPLY OF CABLESSupply & Delivery of 2 Core PVC/XLPE Insulated & Sheathed Armoured Aluminium Conductor Cables for Working Voltage up to 1100 Volts of following sizes. [ Make - Polycab/Gloster/RR ]2 core 10 Sq mm. cable. [ NS ] |
| 14 | SUB HEAD 5 -- LAYING OF CABLESLaying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as per GS. -- [ 2(a)/F-1 ] [ For 2 core 10 Sq mm. ] |
| 15 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damagesas per GS. --From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. [ 5(i)/F-3 ] [ For 2 core 10 Sq mm. ] |
| 16 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre as per GS. -- [ 1(a)/F-2 ] [ For 2 core 10 Sq mm. ] |
| 17 | Laying of cable as below, on existing Cable Tray and binding withsuitable size GI wire.Up to 50 sqmm [ 6(i)/F-3 ] [ For 2 core 10 Sq mm. ] |
| 18 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry as per GS.2 core 10 Sq mm. cable gland. [ 7(a)/F-4 ] |
| 19 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make) as per GS.2 core 10 Sq mm. cable [ 8(b)/(iii)/F-5 ] |
| 20 | SUB HEAD 6 -- COMPOUND LIGHTS AND FEEDER PILLERFixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire as per GS. [ 18/ C-3 ] |
| 21 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as require [ 20(b)/ C-3 ] |
| 22 | Fixing only LED Street light/Flood light type fittings incl. making holes/providing clamping arrangement & necy. GI reducer as required on the existing arm brackets of the 9 mtr. height pole/Mini Pole Structure as per the direction of EIC. [ NS ] |
| 23 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmmPVC/A cable and having lined with rubber gasketted GI top coverwith brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. as per GS. -- [ 5/H-5 ] |
| 24 | Supplying and Fixing GI water proof looping cable box havinghinged GI Top Cover having 4 mm thick with rubber gasketlining, railway type mechanical locking arrangement, earthingterminal with lug etc. of the following sizes as indicated below,Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL onporcelain insulator etc. and housing the same in pole muffingincl. addition and alteration to the existing CC muffing (6:3:1)after dismantling the damaged looping cable box etc. wherenecy. incl. painting -- 250 x 250 x 100mm [ 16(b)/I-2 ] |
| 25 | Providing CC (6:3:1) muffing 600x600x760 mm in size or equivalent size of cylindrical muffing above ground level around the pole base complete with 3 mm thick neatly finished cement plaster all round after dismantling the unserviceable muffing if necessaryWithout Loop Box [ 12(a)/I-1 ] |
| 26 | Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emerypaper, cleaning etc. for receiving fresh coat of paint. -- Upto 9.0 mtr. long pole.1st coat of aluminium paint over 1 coat of RO priming. [ 4(a)/(i)/H-2 ] |
| 27 | 2nd coat of aluminium paint over 1st coat. [ 4(a)/(ii)/H-2 ] |
| 28 | Painting Block Letters or Digits within a circle/square as required, with ”Black Japan” paint of approved make & brand, the size of letters and digits as given below. Size -- 50 mm and upto 75 mm. [ 6(b)/H-2 ] |
| 29 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe - 2 x 36/0.3 (2.5 Sq mm.) + 1 x 22/0.3 (1.5 Sq mm.) as ECC incl. S & F 19 mm. dia. heavy gauge polythene pipe from loop box of Pole to fittings. [ 1(s)/E-9 & 51/K-2 ] |
| 30 | S & F of Compound Light Timer Control Box with Double door 10 Way SPNDB enclosure on wall as per -- ( Make - L&T) incl. interconnection with suitable size of PVC insulated copper wire and neutral link & proviosion for earthing attachment. incl. proper socketting with required size of copper lugs and following accessories -- i) 240/415 V, 32 A DP MCB of Breaking Capacity 10 KA & ''C'' Charecteristics ( Make - L&T/ABB/Legrand/Siemens ) - 1 nos. ii) 25 A, 2 Pole Power Contactor with 220 coil voltage ( Make -L&T/ABB/Siemens ) - 1 nos. iii) Digital Time Switch ( Make - L&T/ABB/Legrand/Siemens ) -1 nos. iv) One no. Red and One no. Green 240 V LED indicator lamp for indicating purpose of Auto & Bypass indication ( Make -- L&T/ABB/Siemens ) v) Auto/Manuual Toggle Switch -- 1 nos vi) S & F 4 way terminal lead on existing enclosure over the pvc insulated chairs with necy. nuts, bolts & washers. -- 2 nos. [ NS ] |
| 31 | Supply & Delivery of Street light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 7700 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips (Signify) /Havells/Wipro/Make - Crompton Greaves,) Colour - White |
| 32 | Supply & Delivery of Street light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 11000 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips (Signify) /Havells/Wipro/Make - Crompton Greaves,) Colour - White |
| 33 | Supply & Delivery of Street light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 13200 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips (Signify) /Havells/Wipro/Make - Crompton Greaves,) Colour - White |
| 34 | Supply & Delivery of Flood light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 6600 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips/Crompton/Havells/Wipro) |
| 35 | Supply & Delivery of Flood light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 13200 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips/Crompton/Havells/Wipro) |
| 36 | Supply & Delivery of Flood light luminaire (IP 66) with peanut lens and high poer LED to ensure uniform distribution and higher spacing between poles, 10 KV SPD, THD<10%, PF> 0.95, BIS approved silicon filled potted driver, minimum LPW : 110 lumen/watt and minimum system output 22000 lumen suitable for use with 230 Volt, 50 Hz. ( Make - Phillips/Crompton/Havells/Wipro) |
| 37 | SUB HEAD 7 -- MISCELENEOUSDismantalling of the existing old electrical wiring from existing old MCBDBs, dismantling of existing damaged outdoor light fittings - fixtures, old cables, damaged loop boxes, damaged main switches etc. and mending good the damages by necy. plaster works to these all damaged areas as per the requirement of site situation as per the direction of EIC. [ NS ] |
| 38 | Making holes on RCC ceiling 125 mm depth having dia of following sizes :125 mm depth, 50 mm dia [ 9(b)/E-3 ] |
| 39 | Additional charges for cutting the RCC Road and mending good the damages as to original finish after laying the cable through the existing GI Pipe protection as per size given below -- 40 mm dia [ NS ] |
| 40 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. -40 mm dia [ 11(c)/F-6 ] |
| 41 | SUB HEAD 8 -- EARTHINGExcavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil [ 1(a)/G-1 ] |
| 42 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI - Medium GI Pipe [ 2(a)/ G-1 ] |
| 43 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall as per GS. [ 4(b)/G-2 ] |
| 44 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Solid G.I. wire -- No. 4 SWG GI wire. [ 5(a)/(i)/G-2 ] Please Enable Macros to View BoQ information |