| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority: Executive Engineer(E) PWD M-253 Name of Work:- RMO of Electrical and Mechanical installations at Saheed Rajguru College at Vasundhara Enclave, Delhi (SH:- E.I work of changing room in basement and other associated works) NIT No.:125/EE(E)/PWD M-253/2025-26 Estimated Cost:-9,21,329/- Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Sub Head Item Code / Make Quantity Units Estimated Rate inRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group C |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 5 | 6 x 1.5 sq. mm |
| 6 | 3 x 4 sq. mm |
| 7 | 6 x 4 sq. mm |
| 8 | 3 x 6 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 10 | 25 mm |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 12 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 13 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without CB/RCCB/Isolator)16 way , Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 15 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.100 A, 16 KA,TPMCCB |
| 16 | Supplying and fixing following rating, 240 / 415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A DP MCB |
| 17 | 63 A TP MCB |
| 18 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C)Powder coated die cast /Extruded aluminium Body including trim12 -15 watt |
| 19 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI>80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hourswith, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)36 watt |
| 20 | Supplying & fixing following size PVC trunking along with cover & accessories on surface etc. complete as required.38 mm x 25 mm |
| 21 | 50 mm x 50 mm |
| 22 | 100 mm x 50 mm |
| 23 | Supplying, laying & fixing of following size one number XLPE insulated and PVC sheathed armoured aluminium conductor power cable of 1.1 kV grade conforming to IS 7098 (Part 1) 1988 on existing cable tray / wall surface as required.3 x 10 sq. mm |
| 24 | Supplying, installation, testing & commissioning of 20W LED Mirror light of polycarbonate housing with diffuser & integrated electronic driver having system lumen efficacy: ≥90 lm/W THD: ≤10%, PF: ≥0.90, CRI: ≥80, Colour Temperature: 5700K/6500K, LED life ≥ 25,000Hrs i/c connection with 1.5 sq mm FRLS PVC insulated connection sq mm FRLS PVC insulated copper conductor, single core cable and earthing complete as required. |
| 25 | Supplying, installation, testing & commissioning of 300mm Sweep, 900 rpm, single phase heavy duty exhaust fan complete in the existing opening, including making good the damage etc as required. |
| 26 | Supplying, installation, testing & commissioning of 200 mm sweep Air Flow Capacity 520cc/min 1350 RPM plastiic body Exhaust fan complete with louver/shelter i/c cutting the suitable size round hour for above fan making good the damage etc as required. |
| 27 | Supplying installation testing and commissioning of swing type three speed wall fan of 400mm sweep suitable for operation on 230 Volt 1-Ph 50 Hz AC Supply including wall mounting arrangement, connection etc. as required. |
| 28 | Supplying installation testing and commissioning of swing type three speed wall fan of 300mm sweep suitable for operation on 230 Volt 1-Ph 50 Hz AC Supply including wall mounting arrangement, connection etc. as required. Total in Figures 921329.0 23 Nine Lakh Twenty One Thousand Three Hundred & Twenty Nine Only Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |