| 1 | `(i) Designing, P and F, commissioning and testing of vacuum- operated automatic switchover gas chlorination system with 1 Working Chlorinator plus 1 Standby Chlorinator compatible with the existing gas chlorination system with three months trial run and one year defect liability period.(ii) Designing, P and F, commissioning and testing of Chlorine gas dry scrubber consisting of support structures, ductwork of scrubber, blower, dry scrubbing tank, dry scrubbing media, necessary piping, motors, controls, exhaust stack and essential accessories with three months trial run and one year defect liability period. PandF of Prefab Porta Cabin of size 1.83 m. X 1.83 m. and height 2.3 m. with one side slope design with 50 mm PUF wall panels with Pre painted galvanized sheet and 20/60 mm corrugated PUF roof panels with Pre painted galvanized sheet with door, windows etc. complete in all respect.(iii) Designing, Pand F, commissioning and testing of Auto-shut off valve with three months trial run and one year defect liability period.(iv) P and F of Dual gas cylinder duly certified and approved by BIS and by explosive department of Govt. of India, Nagpur of 100 kg capacity cylinder As per IS 3196 part –IV.(v) Providing, fixing, installation, commissioning and testing of chlorine leak detector with alarm/hooter. (As per Technical specifications of gaseous chlorination system as per letter of EIC, PHED, Pkl. Memo No. 23070-23142-PHE/Mont. dated 28/02/2024 (copy attached). ` |
| 2 | HT. ALLUMINIUM CABLE: Supply erection testing of standard make XLPE 3 core HT / 11 KV grade ISI marked Stranded compact circular aluminium conductor, conductor screen with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, innersheath of PVC, galvanised steel flat strip armoured, and overall PVC sheathed cable conforming to is 7098 (part-2) 2011 with up to date amendments for making following connection a) from G.O switch to metering equipment . b) from metering equipment to transformer complete in all respect. Make: Indian Cables Ltd./ Polycab / RR Cables / Finolex / Havells Cables.35 Sqmm size |
| 3 | `HT Metering Panel: Supply Indoor Type 11KV VCB Control Cubical Panel with vertical Isolation Type Breaker as per Relevant IS as amended up to Date and Additional Specifications, having Capacities as Mentioned Below, Single break trip free mechanism, manually charged and Auto/Manually closing breaker suitable for use on 11kv, 3 phase 50hz AC, Supply with short circuit fault level of 500 Amps Capacity, breaker featured with local ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 2NO plus 2NC and equipped with following switchgears and accessories including making suitable structure arrangement for installation, control wiring and connections etc. as reqd. (1 IC plus 2 OG)a). VCB, 11KV, 630Amp, 50KA.b). 1ph 11KV/110 Volts PT (indoor type) Class 0.2 Accuracy and 100 VA burden -3 no’s.c). 33KV indoor dead type dual core dual ratio 3CTs of ratio 200-100/5-5 A of 15 VA burden, PS 5 P10 and accuracy class 0.2.d). Control panel- Cubicle type control panel suitable for floor mounting made out of 1.63 mm CR sheet duly powder coated and with following relays.e). Microprocessor based numerical relay for O/L, E/F and SC Protection suitable for above.f). Master trip relay -2 no’s.g). Indicator type Annunciator panel with buzzer.h). Digital Volt Meter- 0-11 KV.i). Digital Amp Meter- 0-100 Amp.j). RYB/ Trip/Closing/Spring charged indicator lamp.k). Fault Annunciator panel for O/L, WTI, OTI and Buchhloz Relay Alarm And Trip Auxiliary relay.l). TNC Switch for Operation.m). Multifunction Meter EM6400NG.n). TCS Relay for Safe` |
| 4 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site. 300 mm nominal diameter |
| 5 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in charge complete in all respect. Make:Finolex / Havells / RR Cables. (150 Sqmm size) |
| 6 | -Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 105 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At MBS near Yamuna River) |
| 7 | NS Item -LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Finolex / Havells / RR Cables. (300 Sqmm size). |
| 8 | -`Cloud based software comprising of Middleware, Database and Front-end web interface through suitable Dashboards, Aggregation screens and GIS assisted drill-down from macro to micro to be provided. Application data hosting and maintenance for Five years included in scope. Cloud servicesof Ministry of Electronics and Information Technology (Meity), Government of India empaneled cloud service providers shall be taken like Microsoft, Amazon, Google, BSNL etc. Cloud service provider must adhere the security standards and guidelines issued by Meity from time-to-time.As the data belongs to the State Government of Haryana, therefore the application and data hosted on Cloud must be kept and stored in data centres located in India only. Any change in application requirement or infrastructure shall be borne by the Implementation agency. Implementation agency shall carry out the Application Security Audit from a Certified Auditor (CA). Application and data shall be kept confidential and only the authorized users shall have the access to it.Implementation Agency shall be responsible for any data theft or data leakages.` |
| 9 | NS Item -`Online Chlorine Sensor : Supply, Installation, Testing, Commissioning with five year maintenance of Online Chlorine Sensor. (For MBS) |
| 10 | NS Item -`RTU: Functional Integration at RTU-cum-Gateway for Motorized Control Valve in Pump Control Panel(For MBS)` |
| 11 | NS Item -`Electromagnetic Flowmeter: Supply, Installation, testing, Commissioning five year maintenance, Electromagnetic Flowmeter along with its installation complete in all respect as per specifications. Size as per site requirement.(IP-68), RS-485 ModBus. Line size 400 mm, installed at pump End / Source. (For MBS) |
| 12 | NS Item -`Automation Panel: `Automation Panel for integration with VFD with Pump Control Panel, along with Auto/Manual Selection Switch as well as On/Off push button to be provided. Manual selection between pump 1 and pump 2depending on which to be operated and which to be stand by to be provided, along with all relay interlocks and provision of operation of pumps through potential free/open collector digital outputs of RTU-cum-Gateway device. The panel will contain RTU-cum-Gateway with necessary I/Os and edge controller Motorized control valve in Local / Remote or Auto/ Manual modes of operation in tandem with Cloud Scheduler or Level sensor-based functions. Panel will contain SMPS with rechargeable battery backup (min. 24 hrs.) along with facility to connect all field instruments with 24 VDC power supply. `(For MBS |
| 13 | NS Item -`Radar and Water Level Transmitter: Supply, Installation, testing, Commissioning with five year maintenance of Radar and Water Level Transmitter alongwith according to water level in OHSR (for OHSR) Ingress Protection – IP 66, Measuring range – Up to 20 M, Process temp.- -40 to 60 deg. C, Full PVDF Body – For a long sensor lifetime. **Unit Rate given, actual quantity to be ascertained while placing order. (For MBS) |
| 14 | NS Item -SIM Card: SIM Cards for five year maintenance of all the instrument above as required. ( For MBS) |
| 15 | NS Item -`Butterfly Valve: Supply, Installation, testing, Commissioning with five year maintenance of Butterfly Valve with Electrical Actuator Body Material - CI/DIPressure Rating – PN16 Feedback - 100% Open and 100% close. **Unit Rate given, actual quantity to be ascertained while placing order 400 mm |
| 16 | Designing, Supply and erection of DG set of capacity given below with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through s set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standers panel, making second incoming cable connection from transformer, outgoing cable connection from changeover/ STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specification and directions of Engineer-in-Charge. The rating should be at 1500 RPM. a) Diesel Engine b) Alternator c c) Battery 24 v. d) Base plate. e) Suitable sq mm suitable core copper cable upto 40 meters. f) Tools, standard panel. g) Metering, set 415 VAC-1 set (Amp. Meter, volt meter, ASS, VSS, phase indicator, control fuse, frequency meter, CT’s) h) Metering set 60/5A//440V (Amp. Meter, volt meter). i) Overload protection for DC-1 No. j) Battery charger 24V DC k) Copper bus bar of suitable size l) KWH meter 96 sq mm size m) Starting fuse button and key switch9on/off n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, DC control and other required accessories complete in all respects to the satisfaction of Engineer-in-Charge’ 7. 160 KVA (As per parameters of CPCB 4) 160 KVA (As per parameters of CPCB 4) |
| 17 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Clear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 8400 LPM x 30.00 M Head (At MBS) |
| 18 | `NS Item -`Design, Construction, Erection and Commissioning of 1 Ranneywell (Radial collector well) of 10.00 MLD capacitywith minimum sinking depth of 30 mtr and 1000 mtr long Laterals pipe in 4 layers, all Civil, Mechanical and electricalworks including transformer as per design along with all accessories and cables, CubicaI type LT/HT Panels, VCBpanels, all types of cablings with cable tray, Chemical Earthings of all machineries, 4 VT Pumps (3W plus 1S) havingcapacity 180.00 m³/hr. x 30 m head, VFD Panels, M.S Header with all necessary fittings, Gantry as per design, Electromagnetic Flow meters at all outlets and inlets, Field office (4 mtr X 4 mtr with attach Toilet), Horticulture andlandscaping (3000 sqm) including purchase of 1.50 acre land (For Ranneywell, MBS and approach path from revenue rasta to well), earth filling in Ranneywell complex.1 High mast street light 12.5 mtr high pole with 8 Luminous lights, wire / cable, switch. MCB and proper foundation etccomplete in all respect. 10 CP Plus CCTV HD coloured night vision cameras and 1 360 degree Dome camera fitted at 11 m. high Pole along with proper foundation with HD night vision.PLC/SCADA based Automation and monitoring system. All the pumping machinery, panel board, flow meter, Levelsensor etc shall be controlled by PLC and SCADA and shall be synchronized with PLC panels at Ranneywell and MBS sitethrough broadband internet facility.The work will be carried out strictly as per detailed scope of works, specifications, conditions mentioned in the DNIT andentire satisfaction of Engineer-in-charge. (80 % Capital cost plus 20 % O/M cost payement schedule attached with DNIT.)` |
| 19 | HSR Itmes Please Enable Macros to View BoQ information |