| 1 | DSR 1.15 Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 2 | Group A |
| 3 | DSR 1.16 Rewiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 4 | DSR ITEM NO.1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required. |
| 5 | 3 x 1.5 sq.mm |
| 6 | 3 x 2.5 sq.mm |
| 7 | 3 x 4 sq.mm |
| 8 | 3 x 6 sq.mm |
| 9 | DSR item No.1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 25 mm |
| 11 | DSR 1.33 Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 12 | DSR 1.38 Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 13 | DSR 1.23 Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 14 | 5/6 A switch |
| 15 | 3 pin 5/6 socket outlet |
| 16 | 15/16 A switch |
| 17 | 6 pin 15/16 socket outlet |
| 18 | 2 way 5/6 A switch |
| 19 | DSR 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Single pole |
| 21 | Triple pole and neutral |
| 22 | DSR ITEM No.2.16 Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 23 | DSR 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 24 | 4 way (4 + 12), Double door |
| 25 | DSR 5.2 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 26 | DSR 5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 27 | Supply and Erection of B.L Holder (ISI marked) of make Anchor Penta/ Havells (Reo)/ Goldmedal/ Lauritz Knudsen only on the existing junction box/ wooden block including making the connection etc as required. The job includes the all labour and petty material charges required to complete the job to the entire satisfaction of E.I.C. of work. |
| 28 | Supply & Erection of 3 mm thick white glazed bakelite sheet on existing M.S. box. The job includes the cost of sheet and making holes & cutting and fixing with screws as required to complete the job. The bakelite should be of Superhylam/ Formica/ Greenlam (ISI marked) make only. |
| 29 | S/E of LED Bulk Head Luminaries weather proof frosted light with PMMA/ PC reflector and silicon gasket to be installed on surface. The LED fitting should have minimum system Lumen output minimum 1000 Lumen at 100 lm/ watt (minimum) and the driver of the fitting should be workable on 140-260 Volt. The colour temperature of LED should be minimum 5000 degree Kelvin. The fitting should be of Philips/ Bajaj/ Wipro/ Havells/ Jaquar/ Crompton/ Panasonic/ Surya/ LT/ Trilux make only. The fitting should be of IP-65/66. The LED should have a life of 50000 burning Hours. The fitting should have THD<15% and power factor 0.9 or above. The job includes the cost of testing, commissioning and making connection with copper wire from adjacent light point, other petty material and labour etc. as required to complete the same to the entire satisfaction of Engineer In Charge. |
| 30 | DSR 9.2 Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion)less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 31 | Making hole for installation of exhaust fan of size upto 450mm sweep by demolishing brick work manually/ by mechanically means including disposal of malba with in 50 mtr lead and making good the wall by plastering etc as required. |
| 32 | Supply & erection of Exhaust Fan (heavy duty motor with copper wound metallic body) following size complete with motor, metallic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation, epoxy powder coating along with metallic louver to be installed in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 33 | Size 12 inches (300mm) Sweep, 900 RPM Heavy Duty Exhaust fan (Single Phase) with louver of Havells make (Turbo Force SP)/ Crompton make ( EXHD300-6-1)/ Bajaj make (Supreme Plus)/ Orient make (Industrial Heavy Duty)/ Usha Make (Turbo HDEF) make only. |
| 34 | Supplying and fixing Socket type stepped up electronic fan regulator on the existing Bakelite sheet switch box including connections but excluding Bakelite sheet etc. as required. Please Enable Macros to View BoQ information |