| 1 | Hire charges for Silent type D.G. Set, including change over switch. Control panel etc. and excluding POL with skilled operator to operate system as and when etc as required. of following capacity: 82.5 KVA |
| 2 | Supply and filling of POL for DG sets |
| 3 | Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected on C.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD.Centrifugal Monoblock Pump set (Double Stage)15.0 KW (20.0 HP) |
| 4 | SITC STAR DELTA Starter type LT Panel of following rating: all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle & Packing Material ) etc. and 100A/ 125A ,TPN, Aluminium Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge.STAR DELTA STARTER 15.0 KW (20.0 HP) : 2 motors (1 W+ 1S) I/C- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 100/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3)and O/G- MCCB 63A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (12-18A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) |
| 5 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. 16.0 Sq.mm, 4 core |
| 6 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 70.0 Sq. mm 3.5 core |
| 7 | P & F G.I. Pipes (External Work) with G.I. fittings excluding union (IS : 1239 Mark) including trenching & refilling earth etc.125mm dia nominal bore 'A' Class |
| 8 | Providing, lowering, laying, aligning, fixing in position CI Foot valves in pipe line as per IS:4038-1986 (amended upto date) suitable for potable water at all level/ depth including all material, labour hydraulic testing and commissioning as per technical specifications and as per direction of Engineer for following sizes:125 mm dia |
| 9 | Engaging of beldar, whitewasher, bhisti with mushak, chokidar, helper, farrash, sweeper etc. Please Enable Macros to View BoQ information |