| 1 | Dismantling and shifting of Central verge Street Lights |
| 2 | Dismantling the existing pole above 6 m height with brackets, clamps, insulators, stay from the c.c. foundation and making the site clear by refilling the pits with excavated materials and bringing it to the ground level. |
| 3 | Dismantling of existing 16 m clear height motorized high-mast (Top-150mm, Bottom-410 mm) hot dipped galvanized material including all accessories etc complete. |
| 4 | Dismantling the existing W.T. fluorescent fitting/ S.V./ M.V. / M.H. lamp /LED fitting from pole with brackets complete. |
| 5 | Supply of Crane on hire basis with capacity of 3 M.T. for loading & Unloading of Street light poles with required manpower. |
| 6 | Providing Trailor 30 MT capacity with length 10 mtr on hire basis for transporting streetlight pole from Site to Shinde Pumping station premises including diesel driver etc. complete. |
| 7 | Making M-20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5m depth including supply of steel, concrete, excavation and including fixing nut bolts with the help of template, duly plastered as per design complete (for 9m & 10m high octagonal/conical GI pole). |
| 8 | Making M-20 cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 2m depth including excavation and including fixing nut bolts with the help of template, duly plastered as per design complete (for 12.5m raising lowering high mast). |
| 9 | Dismantling the existing cables of all types & size above 10 sq mm up to 50 sq.mm. |
| 10 | Erection of 9 mtr long GI octagonal pole with bracket , LED fittings , GI nut bolt in foundation etc complete in an approved manner. |
| 11 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 12 | Supplying, installing and testing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.I. cover complete with all accessories of G.I. materials & recording the results as per specification no. EA-EP |
| 13 | Supplying and erecting PVC insulated PVC round sheathed FR 1.5 sq.mm (30 no. x 0.25mm dia.) 3 core flexible multi stranded copper industrial cable for voltage grade up to 1.1 kV |
| 14 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 15 | Providing and erecting cover for terminal box as per specification |
| 16 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 17 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 35 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 18 | Supplying & erecting three phase, 415V, street light control panel upto the max load of 12kW, TPN MCB 63A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54, IK10 protection suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation as per specification SW-STCP. |
| 19 | Supplying and erecting integrated LED street light fitting 120W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 13000 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minium 2 Years warranty as per specification No. FG-ODF/SL. |
| 20 | Supplying and erecting integrated LED flood light fitting Max. 155W IP65 & IK07 class having pressure die-cast aluminium housing, having system lumens output of Min. 18600 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs at L70B50 including driver with U shaped bracket with minimum 2 Years warranty as per specification No. FG-ODF/FL. |
| 21 | Providing and laying Cast in situ/Ready Mix cement concrete in M20 of trap/ granite/quartzite/gneiss metal for bed blocks, foundation blocks and such other items including bailing out water, Steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.), with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 22 | Air Compressor with pnuematic chiesel attachmant / braker |
| 23 | Providing & erecting 9 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 155 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 24 | Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT |
| 25 | Supplying and erecting outdoor stand mounted feeder pillar for high-mast of the same manufacturer with 63A TPN MCB incomer, 24hr astronomical time switch with minimum 5 Years battery backup, 45 A TP contactor for automatic switching of luminaries, 2 no 9A contactors and raise/lower push button, and provision for termination of adequate size of incoming and outgoing cables complete erected in min. 14 SWG CRCA sheet box powder coated with supporting angles, self lock, gasket and slanting top erected on CC foundation complete. |
| 26 | Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA along with terminal plate suitable for 9 mtr octagonal street light pole in provided distribution board as per specification no. SW-MCB |
| 27 | Supplying, Erecting & Commissioning Street Light Terminal Box SMC grade fiber glass Window Cover with all required accessories etc.. |
| 28 | Credit for Dismantled MaterialPVC armoured/unarmoured cables and wires (Aluminium) |
| 29 | PVC armoured/unarmoured cables and wires (Copper) |
| 30 | I.C. / M.C. switches / D.P. / D.B./ T.P. / feeder pillar etc. |
| 31 | Street/flood light fittings. |
| 32 | H.G. / M.S. / G.I. Materials / Poles etc. Please Enable Macros to View BoQ information |