| 1 | SUB-HEAD 1 -- SITC of VTPNDB |
| 2 | Supplying and fixing double door 4 way Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment |
| 3 | 4 way upto 160 A (Legrand/ABB/L&T) |
| 4 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. |
| 5 | FP- 125 A (Legrand/ABB/L&T) |
| 6 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection |
| 7 | SP- 6-32A |
| 8 | TP- 63 A (Legrand/ABB/L&T) |
| 9 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment |
| 10 | 6 way |
| 11 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required |
| 12 | 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC |
| 13 | SUB-HEAD 2 -- Supply & Laying of Cable |
| 14 | Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] |
| 15 | 4 CORE 16 SQMM |
| 16 | 4 CORE 50 SQMM |
| 17 | Laying of cable on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 18 | 4 core 16 sqmm (from VTPN to AC Outdoor Unit ) |
| 19 | 4 Core 50 Sqmm (from Building Panel to VTPN) |
| 20 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 21 | 4 core 16 sqmm (from VTPN to AC Outdoor Unit ) |
| 22 | 4 Core 50 Sqmm (from Building Panel to VTPN) |
| 23 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 24 | 4 core 16 sqmm (from VTPN to AC Outdoor Unit ) |
| 25 | 4 Core 50 Sqmm (from Building Panel to VTPN) |
| 26 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. |
| 27 | 200x50x1.25mm (18SWG) [ With 25x25x3 mm angle iron support] |
| 28 | SUB-HEAD 3 -- Earthing |
| 29 | Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil) |
| 30 | Earthing with 50 mm dia ISI-M GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as to GS. |
| 31 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe |
| 32 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode |
| 33 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 34 | Insulating the 65x8 mm MS flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaring the PVC sleeve as per direction of the EIC |
| 35 | Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. |
| 36 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages |
| 37 | No. 8 SWG |
| 38 | SUB-HEAD 4 -- SITC of Air Conditioning /VRF |
| 39 | Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . (12 HP x 4) |
| 40 | Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remotecontrol, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. |
| 41 | Mid Static Ductable units (minimum 45 pascal external static pressure) |
| 42 | 2.8 TR |
| 43 | Low static ductable units (minimum 25 pascal external static pressure) |
| 44 | 1.6 TR |
| 45 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as perspecifications etc. as required : |
| 46 | 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation for Out Door Gas Pipe. |
| 47 | 12.7 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation for Out Door Liquid Pipe. |
| 48 | 6.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Indoor Liquid Pipe. |
| 49 | 12.7 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation for Indoor Gas Pipe |
| 50 | 9.5 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Indoor Liquid Pipe |
| 51 | 15.86 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Indoor Gas Pioe. |
| 52 | Supply & Laying of 4 core 2.5sq.mm 1.1 KV insulation grade sheathed Cu cable with gas line as per direction of EIC for making interconnection/communication between Indoor to Outdoor unit of Split type AC m/c.(Make- Polycab/RR Kabel/Havells/KEI as approved by E.I.C) |
| 53 | Supply and fixing of Al powder coated continuous Grill. (Make:-System Air/ Premire /Air Master as approved by E.I.C) |
| 54 | Supply and laying 25mm PVC drain pipe |
| 55 | Supply and fixing flexible canvass connection for concealed for 2.0 Tr split air-conditioners. |
| 56 | Supply & fixing 240 V, 50 Hz, 1ph OLP 3+ starter with digital display for Split AC machine (1.5/2 Ton) having rated current 21 A Voltage range 160V-270V, IP 20, and provision to display voltage , current, and any fault indication (Make- Electron) incl. necessary connection (incl. supply material like MS Box, wire, lugs etc if required) and commissioning the same. |
| 57 | Supplying, fabrication & fixing of trap door made for maintenance of IDU of Air conditioning system by frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect as per direction of EIC |
| 58 | Supplying, fabrication & fixing 6 Nos. M.S. Angle of size (40 mm x 40 mm x 6mm) for making platform for installation of outdoor unit of 2.0 TR Concealed split AC incl. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 40 mm x 40mm x 6 mm in each platform in outer/below edge for transmitting the load centrally through 4 Nos. (40 mm x 40 mm x 6 mm) Angle grouted in the roof with fastner with necessary muffing. The entire structure should be iron cage type with locking arrangement & shade arrangement above the grills with corrugated tin shade, necessary anti-rust painting as per direction of EIC. Area of the structure is (40\\"x 36\\"x24\\") or as per Machine configuration & load with adequate service access as per direction of EIC |
| 59 | Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes.[For Muffing of Legs of MS structure base of Outdoor Unit][16 nos of size 600 mm X300mm X600 mm] |
| 60 | a) Pakur Variety |
| 61 | Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees. Please Enable Macros to View BoQ information |