| 1 | Part A-33/11 KV GSS-Grass cutting and surface dressing including removal of unwanted/rubbish plants with roots from open ground /yard and other Nigam premises with stacking of grass/plants at desired place near the ground. |
| 2 | Levelling of ground above 30 cm.to 90 CM.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) |
| 3 | Excavation of pit in Hard soil (A) Height of poles/R.S.Joist/M.S. Rail Size of pit 9 Mtr/ 1.2mx0.6mx1.50 m deep |
| 4 | Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms .Liftup to 1.5 Meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 Meter. Hard soil mixed with boulders |
| 5 | Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate mix .Note: 1. The rates are all lead of cement,lime,ballast, sand,surkhi and grit etc.at site of work2. For all concrete work coarse sand shall be used no extra will be paid.3. Concrete mix prepared by power driven mechanical mixer shall be used.4. Under exceptional coditions, where mechanical mixer and vibrator are not used(with the approval of Engineer Incharge reduced by 3% for mechanical mixer and 2% for Vibrator5. Thickness of the cement concrete should not exceeed 100 mm |
| 6 | Plaster on new surface on walls in cement ,sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick. Note: 1. The rates for complete work including racking of joints,curing,grinding,mixing and finishing T&P and scaffolding material and cost of material with all lead and lift2. The rates cover protection of all place and things,requiring protection and cleaing such places and thing of all droppings and splashes of mortar etc |
| 7 | Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete 75 mm thick with 20 mm thick nominal size aggregate. |
| 8 | Masonry for foundation and plinth Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges. |
| 9 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr.long 400 Kg. PCC pole within 10 Kms.- |
| 10 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr.long 400 Kg. PCC pole Above 10 Km. & upto 30 Km. add for each Km. or part thereof |
| 11 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr.long 400 Kg. PCC pole Above 30 Km. add for each Km. or part thereof |
| 12 | Safe carriage of PCC poles including loading / un-loading (c) 9 Mtr.long 200 Kg. PCC pole within 10 Kms.- |
| 13 | Safe carriage of PCC poles including loading / un-loading (c) 9 Mtr.long 200 Kg. PCC pole Above 10 Km. & upto 30 Km. add for each Km. or part thereof |
| 14 | Safe carriage of PCC poles including loading / un-loading (c) 9 Mtr.long 200 Kg. PCC pole Above 30 Km. add for each Km. or part thereof |
| 15 | Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading.from store to site c) Above 25 & 40 KVA Within 10 Kms. |
| 16 | Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading.from store to site c) Above 25 & 40 KVA Above 10 Kms. & upto 30 Kms Add for each Km.or part thereof. |
| 17 | Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading.from store to site c) Above 25 & 40 KVA Above 30 Kms. Add for each Kms. or part thereof. |
| 18 | Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores Within 10 KMs. |
| 19 | Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores Above 10 Kms. and upto 30 Kms.Add per each km,or part thereof |
| 20 | Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores Above 30 Kms. and upto 50 Kms.Add per each km,or part thereof |
| 21 | Safe loading of power/ distribution transformer. (A) 33/11 KV power transformer. Above 1.6 MVA & upto 3.15 MVA |
| 22 | Safe unloading of power/distribution transformers(A) 33/11 KV power transformer.Above 1.6 MVA & upto 3.15 MVA |
| 23 | Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. (GSS POLE/ STAY /SPPORTS) 0.64 each |
| 24 | Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing ofhardware andstrips. |
| 25 | Fixing of 33kv pin insulator with pins. |
| 26 | Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. (B)G.O. switch . without earthing blade. 33kv G.O.switch |
| 27 | Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. (B)G.O. switch . without earthing blade. 11kv G.O.switch |
| 28 | Assembly and installation of Horn Gap fuse set (set of 3nos)on erected structure as per design, complete in all respectwith post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. 33kv Horn Gap fuse set. |
| 29 | Assembly and installation of Horn Gap fuse set (set of 3nos)on erected structure as per design, complete in all respectwith post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. 11kv Horn Gap fuse set. |
| 30 | Installation of lightening arrestors on erected structure /support (set of 3 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, (A)sub-station type 33 KV L.A. set |
| 31 | Installation of lightening arrestors on erected structure /support (set of 3 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, (A)sub-station type 11 KV L.A. set |
| 32 | Installation testing as per Nigams norm & commissioning of 11/0.4KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire/strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, Above 25 AND 40 KVA |
| 33 | Three nos. Earthing of each 11/0.4 KV distribution transformer /sub-station with M.S.Rod 20mm dia 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16\\" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm/(having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence. |
| 34 | Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.as under:Excavation of trench of 0.65Mtrs.depth and 0.5Mtr.width Hard Soil |
| 35 | Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust. |
| 36 | Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust. |
| 37 | Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil:Where drilling is not required |
| 38 | Earthing of new 33/11 KV S/S with bentonite compound (including material ) involving following activities. |
| 39 | Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates. (B) IN RURAL AREAPCC Poles 9 Mtr. Long |
| 40 | Laying / stringing of bus bar with ACSR Dog & jumper connection using tie rod ,33KV /11KV insulator strings,required hardware,P.G.clamps/T clamps etc.as per requirement including Y- connections at bus bar jumpering point as per the direction of engineer in-charge. ACSR DOG/RABBIT |
| 41 | Erection of OCB/Kiosk/VCB complete with accessories including use of special tools & conducting all pre-commissioning test before energization, filling oil etc. complete in all respect with erection & grouting of structure (excluding civil works). The relays will be tested by Discom. 11 KV VCB (Outdoor ) |
| 42 | Fabrication of steel structures of M.S angle ,M.S.channel & M.S.Flat including cutting ,drilling as per design and drawing. 33/11 KV Rural Sub-Station Structure (4086.879 Kg) |
| 43 | Fabrication of steel structures of M.S angle ,M.S.channel & M.S.Flat including cutting ,drilling and continunous welding joint as per design and drawing. Other steel items |
| 44 | Drilling of holes in MS Channel / Angle /Flat 15/16\\" dia holes(23.81 mm dia.) |
| 45 | Supply of MS nuts & bolts |
| 46 | PART-B- 33 KV Line Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. |
| 47 | Trimming of tree branches/plants and preparing route approchases for proposed line. |
| 48 | Excavation of pit in Hard soil (A) Height of poles/R.S.Joist/M.S. Rail Size of pit 9 Mtr/ 1.2mx0.6mx1.50 m deep |
| 49 | Excavation of pit in Hard soil(B) Lattice Tower /Size of pit 12.8/12.6 Mtr/ 1.5mx1.5m x2.10 m deep |
| 50 | Excavation of pit in Hard soil ( C) Stay set/ depth of pit 8'x314\\"-0.75x0.5x1.6m |
| 51 | Providing and laying cement concrete Including compaction etc,complete using stone aggregate 40mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate. |
| 52 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole Within 10 Kms. |
| 53 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(5.26X 20KM) |
| 54 | Safe carriage of PCC poles including loading / un-loading a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole Above 30 Kms. Add for each Kms. or part thereof |
| 55 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Within 10 Kms. |
| 56 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(20x5.11KM) |
| 57 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Above 30 Kms. Add for each Kms. or partthereof. (20 x 3.16KM) |
| 58 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Within 10 Kms. |
| 59 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(20X6.16KM) |
| 60 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Above 30 Kms. Add for each Kms. or part thereof. (3.16) |
| 61 | Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. Including loadlng/unloadlhg and stacking in the Nigam. Stores at work site. Within 10 Kms. |
| 62 | Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. Including loadlng/unloadlhg and stacking in the Nigam. Stores at work site. Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof. |
| 63 | Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. Including loadlng/unloadlhg and stacking in the Nigam. Stores at work site. Above 30 Kms. Add for each Kms. or partthereof. |
| 64 | Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. The cost muffing and grouting will be paid extra. Lattice Structure |
| 65 | Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. (B) IN RURAL AREA PCC Poles 9 Mtr. Long (400 Kg)/200 Kg |
| 66 | Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specflcatlon for which the payment will be made at the prevailing Discern store issue rates. PCC Poles 9 Mtr. Long(400 Kg.)/11Mtr.long |
| 67 | Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire 8\\"x3/4\\" with 7/8 SWG stay wire |
| 68 | Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing of hardware and strips. |
| 69 | Fixing of 33kv pin insulator with pins. |
| 70 | Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. (B) IN RURAL AREA, ACSR DOG |
| 71 | Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. G.I.Earth wire 6 SWG |
| 72 | Fabrication of steel structures of M.S angle,M.S.channel & M.S.Flat including cutting,drilling and continunous welding joint as per design and drawing. Other steel Item |
| 73 | Supply of MS nuts & bolts |
| 74 | PART-C- 11 KV Line Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. |
| 75 | Trimming of tree branches/plants and preparing route approchases for proposed line. |
| 76 | Excavation of pit in ordinary rock . (A) Height of poles/R.S.Joist/M.S. Rail Size of pit 9 Mtr/ 1.2mx0.6mx1.50 m deep |
| 77 | Excavation of pit in ordinary rock . © Stay set/Depth of pit 6'x 5/8\\" -0.75x0.5x1.35 m |
| 78 | Safe carriage of PCC poles including loading / un-loading b) 9 Mtr. Long PCC pole 200 KG Within 10 Kms. |
| 79 | Safe carriage of PCC poles including loading / un-loading b) 9 Mtr. Long PCC pole 200 KG Above 10 Kms. & upto 30 Kms. Add for each Km. or part thereof. (5.26X20KM) |
| 80 | Safe carriage of PCC poles including loading / un-loading b) 9 Mtr. Long PCC pole 200 KG Above 30 Kms. Add for each Kms. or part thereof (2.71x 85) |
| 81 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Within 10 Kms. |
| 82 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(20x5.11KM) |
| 83 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site Above 30 Kms. Add for each Kms. or partthereof. (20X3.16KM) |
| 84 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Within 10 Kms. |
| 85 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(20X6.16KM) |
| 86 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. Above 30 Kms. Add for each Kms. or part thereof (2.71x 85) |
| 87 | Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. PCC Poles 9 Mtr. Long (200Kg) |
| 88 | Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. PCC Poles 9 Mtr. Long (200Kg) |
| 89 | Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire 6\\"x5/8\\" with 7/10 SWG stay wire |
| 90 | Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1nos.disc.& 1set of H/ W ) on terminal point including fixing of hardware and strips. |
| 91 | Fixing of 11 KV pin insulator with pins. |
| 92 | Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. (B) IN RURAL AREA, ACSR Rabbt |
| 93 | Fabrication of steel structures of M.S angle,M.S.channel & M.S.Flat including cutting,drilling and continunous welding joint as per design and drawing. Other steel Item |
| 94 | Supply of MS nuts & bolts Please Enable Macros to View BoQ information |