| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group B |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 4 | Group B |
| 5 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 6 | 20 mm |
| 7 | 25 mm |
| 8 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
| 9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 3 x 1.5 sq. mm |
| 11 | 3 x 6 sq. mm |
| 12 | 3 x 4 sq. mm |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 14 | 5/6 amps switch |
| 15 | 15/16 amp switch |
| 16 | 3 pin 5/6 amp socket outlet |
| 17 | 6 pin 15/16 amp socket outlet |
| 18 | Bell Push |
| 19 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. |
| 20 | 3 Module (100mmX75mm) |
| 21 | 6 Module (200mmX75mm) |
| 22 | 8 Module (125mmX125mm) |
| 23 | 12 Module (200mmX150mm) |
| 24 | Supplying, Installation, testing and commissioning of 1200 mm sweep ceiling fan including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable suitable for 230 volt 50 Hz AC Supply etc. as required. |
| 25 | Supplying, installation, testing and commissioning of 6 Pole heavy duty 300 mm sweep 900 rpm metallic body Exhaust Fan having copper wound motor suitable for opertion on 230 volt 50 Hz AC supply complete with shutter and louver in the existing opening/ making the hole to suit the size of the fan, making good the damage, including connection with 3x1.5 sqmm wire complete etc. as required. |
| 26 | Supplying, installation, testing and commissioning of 200 mm sweeep plastic body Fresh Air Fan having copper wound motor suitable for opertion on 230 volt 50 Hz AC supply complete with shutter and louver in the existing opening/ making the hole to suit the size of the fan, making good the damage, including connection with 3x1.5 sqmm wire complete etc. as required. |
| 27 | Supplying, installation, testing and commissioning of 150 mm sweeep plastic body Fresh Air Fan having copper wound motor suitable for opertion on 230 volt 50 Hz AC supply complete with shutter and louver in the existing opening/ making the hole to suit the size of the fan, making good the damage, including connection with 3x1.5 sqmm wire complete etc. as required. |
| 28 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 29 | 40 watt |
| 30 | Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium |
| 31 | 18 watt |
| 32 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 33 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 34 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 35 | Single pole |
| 36 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 37 | 63 amps |
| 38 | Supplying ,installation & testing & commissioning of 10W 2ft. LED Mirror Light (6500K) luminarie having integrated LED Driver with high transitivity opal diffuser for direct lighting i/c wiring and making connections with 1.5sq.mm. PVC insulated FRLS, copper conductor single core cable including loop earthing suitable for operation on 230 volt 50 Hz AC supply complete with all accessories/attachments etc. as reqd. |
| 39 | SITC of 2.5 mfd capacitor in the existing ceilling fans in the various Qtrs in GK-1 as when required |
| 40 | Supplying and fixing 9-12 W LED Bollard fitting made with extruded aluminium profiles die cast aluminium base / components, U.V. resistance diamond shape polycarbonate diffuser, primer coated and painted with polyurethane paint having IP66 protection and 800 mm to 900 mm overall length suitable for single phase 230V, 50Hz electric supply complete with testing and commissioning etc. as required. |
| 41 | Supplying and fixing Havells 5 W LED E14 Ball|Energy Efficient| Frosted diffuser| Non-Dimmable| Shatter Resistant|Saves Upto 85% Energy|Elegant Design|Upto 4KV Surge Protection|BIS Approved|Pack of 1 supply complete with testing and commissioning etc. as required. |
| 42 | Supplying, installation & testing & commissioning of decorative wall mounting fixture with Opal Glass diffuser suitable for 9-20 W LED Lamp i/c wiring and making connections with 1.5sq.mm. PVC insulated FRLS, copper conductor single core cable including loop earthing complete etc. as required, suitable for 230 volt 50 Hz AC supply complete with all accessories/attachments etc. as reqd. |
| 43 | Supplying and fixing 40 W LED post top lantern having IP66 rating on the existing pole of 65mm diameter suitable for single phase 230V, 50Hz electric supply complete with testing and commissioning etc as required. |
| 44 | Credit for Dismantle |
| 45 | Ceiling Fan |
| 46 | Assorted LED Fittings |
| 47 | Assorted Copper Wire with insulation |
| 48 | Assorted Conduit |
| 49 | Assorted Switch / Regulator/Socket/Boxes/MCB/DB |
| 50 | Assorted Exhaust fan |
| 51 | Bollard |
| 52 | Post Top Please Enable Macros to View BoQ information |