| 1 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modulartype switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed]Average run 9 Mtr [4.d / E-25 ] |
| 2 | On Board [3.i / E- 20 ] |
| 3 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR'(Precision make) incl. necy. fittings as required.[E-14, 1.a]2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) [E-14, 1.a.iv] |
| 4 | 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC. [E-14, 1.a.iii] |
| 5 | 2 x 36/0.3 (2.5 sqmm)+ 1 x 22/0.3 (1.5 sqmm) [E-14, 1.a.ii] |
| 6 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC [E-9,C1 d1] |
| 7 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-5,9]2.5 sq mm [F-5,9,i] |
| 8 | 4 sq mm [F-5,9,ii] |
| 9 | 6 sq mm [F-5,9,iii] |
| 10 | 10 sq mm [F-5,9,iv] |
| 11 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works. 25 mm [ E-16,7b] |
| 12 | Supplying and fixing polythene pipe complete with fittings as necy. under ceiling/beam, bound with 22 SWG GI binding wire incl. supplying and drawing 1x18 SWG GI Wire as fish wire inside the pipes and fittings and providing 50 mm dia disc of MS sheet (20 SWG) having colour paint at one face fastened at the load point end of the polythene pipe with fish wire (synchronizing with roof/beam casting work of building construction)19mm dia 3mm thick Polythene Pipe [E-2,B-1.b] |
| 13 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good thedamages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [D-10,14]4 WAY [ SIEMENS-Enclosure (8GB32202RC04))/CRABTREE/LEGRANDEnclosure (607715)] |
| 14 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T) as per direction of EIC. ]63 A FP [D-5,6] |
| 15 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS.2+14 Way [Siemens Enclosure (8GB32102RC16) or equivalent model of Legrand/L&T] as approved by EIC. [ 13 / D- 9 & D-10 ] ( for switch board ) |
| 16 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as per GS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T) as per direction of EIC. ] 40 A DP [ 6 / D- 5 ] |
| 17 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connections per GS [Make-Legrand/ Schneider/Siemens/Crabtree/L&T) as per direction of EIC. ]6-32 SP [ 7 / D- 6] |
| 18 | Fixing only single/twin fluorescent light fitting suspended 25 cmbellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [ 17 / C- 2] |
| 19 | Supply & fixing of Industrial LED 20 W LED tube light Crompton make Cat no - LTT8-20 or equivalent as per EIC . |
| 20 | Supply & fixing of Industrial LED Batten double fiitings Crompton make Cat no - IGP162LT8-16 or equivalent as per EIC . |
| 21 | Supply & fixing of Industrial LED 20W LED tube Light Crompton make cat No.LTT8-20 or equivalent as per EIC. |
| 22 | Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991) [ 29/D-14 ] |
| 23 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS [ 21 (a) / C-3 ] |
| 24 | Engraving the deptt. number with 10 mm lettering on the body as per GS. [ 24 (a) / C-3 ] |
| 25 | Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS [ 26(a)/C-3 ] |
| 26 | Supply of ac ceiling fans of 1200mm sweep with burst-proof P2/S3 Capacitor complete with all accessories without regulator. ( Make - Usha-Striker or equivalent model of Havells/CG/Orient- Summer king XL as approved by E.I.C) |
| 27 | Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc [10/ E-18 ] |
| 28 | Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate ,false switch plate and making necy.connections with PVC Cu wire and earth continuity wire etc. [ 12/E-18 ] |
| 29 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.[ 5(a) / E-17] |
| 30 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [5(b) / E-17] |
| 31 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch boardand cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-19,17 |
| 32 | S&F of 250V timer DB (equivalent to 12 way SPNDB in size) with double door sheet steel enclosure, neutral bar, din rail, with IP43 protection comprises with 1 nos 25A DPMCB(C-curve 10kA) and 1 no 24 hr digital time switch(L&T,GIC) and 1 no 22A(L&T MNX 22-2P, cat no. - CS90238) power contactor, Starter(North West 11A to 18A ) complete with internal wiring (1.5 sq.mm - control wiring.4.0 sq.mm - power wiring , make - RR KABEL/KEI/POLYCAB/GLOSTER) with suitable size of copper wire including 1 no toggle switch(For Auto/Manual/Off), with Door locking arrangement by common panel keys as used in panel and 2 nos LED( RED color AC ON , GREEN color - AC OFF , must be written in engraving/steel/plastic plate by black color) indicator and earthing attachment as per direction of EIC (Make:- L&T/SIEMENS/ABB/Legrand or equivalent make as approved by E.I.C) . [Note : Timer Connection Scheme : auto/ manual/OFF , Contactor ON - after AC starter ON in auto/Manual Mode , Total Current will be passed through AC starter - AC Load current & Contactor Coil drawing Current] . |
| 33 | SITC of 2.0 ton capacity Hi-wall mount fixed speed split Air-conditioner machine fitted with tropical Rotary compressors suitable for Refrigerant-R410A/R-32, cooling capacity-24000 btu/hr, air flow-800 cfm of rated power supply 230 V-1 Ph- 50 Hz along with all accessories (Make-O-General ASGA24BMAA-B or mitsubishi electric or equivalent make approved by EIC). incl. Supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C. |
| 34 | Supply & Laying Extra Add-on items- 5/8\\" (for suction) & 1/4\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation, 4 core x 2.5 sq.mm. copper cable incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 2 TR A.C. Machine. and Supply & laying PVC Drain Pipe 25mm dia by shaddling on wall incl. PVC \\"T\\", elbow, bend etc as per direction of E.I.C |
| 35 | Supplying, fabrication & fixing 2 Nos. M.S u-channel of 6 mm thick of size (50mm x50mmx 6mm ms angle) of 1.5 mtr length for making Base frame for installation of AC ODU incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. as per direction of E.I.C incl. Platform. |
| 36 | S&F of 25mm Dia uPVC pipe for AC drain pipe on wall, ceiling with saddles and other accessories as required and mending good damages to building works |
| 37 | TERMS AND CONDITION1. THE AGENCY MUST PROCURE THE MATERIALS FROM THE MANUFACTURER/OEM OR FROM THEIR AUTHORIZES. SALES CHANNEL SO THAT THE STANDARD WARRANTY / SOPPORT OF THE MANUFACTURER / OEM BECOMES APPLICABLE TO THE PRODUCTS TO BE DELIVERED AND INSTALLED BY THEM.2. DOCUMENTS THAT AUTHENTICATES SUCH PROCUREMENT FROM THE MANUFACTURER/OEM OR FROM THEIR AUTHORIZES SALES CHANNEL SO THAT THE STANDARD WARRANTY / SOPPORT SHOULD BE SENT FROM THE e-MALE OF THE MANUFACTURER/OEM / AUTHORIZES SALES CHANNEL TO THE e-MALE OF ENGINEER-IN-CHARGE AND HARD COPY OF IT TO BE SUBMITTED DURING EXECUTION OF WORK/ SUBMISSION OF BILL.3. IF ANY REFURBISHED MATERIAL IS SIPPLIED ABD INSTALLED, PENAL ACTION WILL BE TAKEN AS PER EXISTING RULES. |
| 38 | NOTE:- Rate including GST & LWC Please Enable Macros to View BoQ information |