| 1 | Supplying, installing, testing & commissioning of 3 phase, 11/0.433 kV, 50 Hz.,100 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40℃ by thermometer in oil and 45℃ by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) , with standard accessories complete with test certificate with losses below 475 Watts at 50%load, 1650 Watts at 100% load as per IS:1180 (part 1) : 2014, with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL (MSEDCL APROVRD MAKE) |
| 2 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 3 | Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ ( NOTE: 13 MTR LONG POLE 12 NOS. & 11 MTR LONG POLES 2 NOS.) |
| 4 | Supplying & laying (including excavation) half round reinforced cementconcrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in properline, level and slope including providing and fixing collars in cement mortar 1:2and curing etc. complete. |
| 5 | Supplying and erecting porcelain disc type insulator 45/70 KN with necessaryhardware suitable for 11kV line, complete as per specification no. OH-INS/DI |
| 6 | Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose). |
| 7 | Supplying and erecting V cross arm with ISM channel of 75x40x6mm for 11kV HTOHline with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height of V cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VC |
| 8 | Providing & Erecting iron work for various works.( NOTE : AS PER SP MSEDCL EST. ,MS Cheenl 75x 40x6 mm, MS Angle 50x 50x6 , GI nut bolt, MS guarding channel) |
| 9 | Supplying & erecting barbed wire two ply with 12 SWG ply and 12 SWG barbm with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg. |
| 10 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete |
| 11 | Supplying and erecting 11 kV outdoor type gang operated air break, triple pole switch 400 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of \\"C\\" class G.l. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. |
| 12 | Supplying & erecting inline cut point end pole D. P. Structure for 11/0.415 kV, 100 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 200 Amps as incomer & 6 Nos.100 Amps Kitkat /MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O.fuse Set & L.A. Set. 2 Nos. Top channel of size 100 mmx 50 mm for erection ofn A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 x mm for erectingm Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box, Transformer Belt etc. as per drawing (min. 176 Kg. iron work) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with cautionboard & barbed wire. D.P. Structure shall be erected in c.c. foundation complete. |
| 13 | Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP |
| 14 | Providing & ercting pipe earthing with 25mm dia. 1.5 m long GI pipe & G I wire 3 mtr by driving /buried |
| 15 | Supplying and erectingporcelainpin type insulatorwithGI pin suitable for 11kV line, complete as per specification no. OH-INS/PN |
| 16 | Supplying and erecting GI wire 8 swg / 6 swg of high purity of required sizes used for earthingor any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/conduit with screws complete |
| 17 | Supplying & erecting G.I. pipe ‘A’ class 75 mm dia. erected for enclosingXLPE armoured cable on wall/pole as per specification no. CB-CE |
| 18 | Supplying, erecting & terminating XLPE insulated unarmoured cable 1100 V 1 core 95 sq. mm. aluminium conductor complete DTC metering with box & other allied materiels |
| 19 | denger board In yard (LABOUR + METERIAL COST) |
| 20 | Strain Hardwarec for Dog 0.1 orEqu ACSR |
| 21 | Supplying and erecting ACSR conductor of size- 6/1-4.72 mm (Dog)complete. (394.00 kg/km) as per specification No. OH-CON/ACSR |
| 22 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP |
| 23 | Painting of steel tubular / rail / RSJ pole above 6.0 m length along with street light pole brackets, clamps etc by scrapping the existing paint complete as per specification no CW -PTG/PTP. |
| 24 | Supplying and erecting 75x40 x6mm with 4.4mm thick web and 7.3mm thick flange channel (top pin) with clamp of suitable length so as to maintain vertical clearance of 1065mm for 11kV, 1320mm for 22kV between insulators for erection of top pin insulators complete as per specification no. OH-PL/VCA |
| 25 | Supplying and erecting pole clamp made from 50x6mm MS flat for pole or pipe, post erected with 15mm bolts and nuts duly painted with one coat of red oxide and two coats of aluminium paint complete |
| 26 | Supplying and erecting pole clamp made from 50x10mm MS flat for pole or pipe, post erected with 15mm bolts and nuts duly painted with one coat of red oxide and two coats of aluminium paint complete. Please Enable Macros to View BoQ information |