| Sl. No. | Item Description |
| 1 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 2 | 20 mm |
| 3 | 25 mm |
| 4 | 32 mm |
| 5 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 6 | 2 x 1.5 sq.mm |
| 7 | 3x 1.5 sq.mm |
| 8 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 9 | 4 x 6.0 sq.mm |
| 10 | 2 x 6.0 sq.mm |
| 11 | P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 12 | 200mm x 150mm x 60mm |
| 13 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 14 | Single pole MCB (With B/C curve tripping Characteristics) |
| 15 | 6 A to 32 A rating |
| 16 | Double pole MCB(With B/C curve tripping Characteristics) |
| 17 | 40 A rating |
| 18 | Four pole MCB (With B/C curve tripping Characteristics) |
| 19 | 50/63 A rating |
| 20 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 21 | Metal door (Three phase) IK-09 and IP-43 with Metal end box |
| 22 | 6 Way |
| 23 | 8 Way |
| 24 | 12 Way |
| 25 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). |
| 26 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 27 | Recessed Mounting |
| 28 | Minimum lumen output 1950 lm |
| 29 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 30 | High Power LED Flood Light Minimum lumen output 25000 lm |
| 31 | PART B (Air conditioning work) |
| 32 | Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having 100% hermetically sealed inverter type Scroll Compressor(s) with and minimum two compressors along with two Condensing fan, above 14/18 HP modules, microprocessor based Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The EER at 100% load with AHRI conditions shall not be less than 3.5 and Including OEM supplied Piping connection Kit etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 33 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature . (Make will be same as of Outdoor). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 34 | 3.2 TR |
| 35 | 4.6 TR |
| 36 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow compact VRV/VRF Cassette ( 2' x 2' ) Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 37 | 1.2 TR |
| 38 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 39 | Supply, installation, Testing & commissioning of VRV/VRF compatible OEM make AHU KIT' including expansion valve and controller for connecting AHU with VRF. |
| 40 | Supplying and installation of high-pressure grade required size OEM make copper connection Y or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 41 | Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 42 | 0.60 mm |
| 43 | 0.80mm |
| 44 | Supply , installation, testing & balancing of 20 Gauge G I Damper with brass bushes and 6\\" pitch multiblade box type galvanised sheet steel construction volume control damper for Ducting and air washers to be provided with suitable links and quadrants for control of volume of air as per specifications complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 45 | Supply and fixing of acoustic lining of ducts with chemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in all respect. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 46 | 15 mm thick |
| 47 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 48 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 49 | 25 mm |
| 50 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 51 | 100 mm dia per running inch length |
| 52 | 150 mm dia per running inch length |
| 53 | Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. All as per pre approved by Engineer in charge. |
| 54 | 13mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 55 | P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibration with GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 56 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 57 | Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 58 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 59 | 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 60 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 61 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 62 | 10.0 Sq. mm |
| 63 | 4 core |
| 64 | Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 35 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 65 | four pole 300 mA sensitivity |
| 66 | 63 A rating |
| 67 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of required shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 68 | 50 mm dia |
| 69 | 80 mm dia |
| 70 | 100 mm dia |
| 71 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C' class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supports including cutting, welding etc & forged steel fittings like elbows, tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 72 | 150 mm dia |
| 73 | Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 74 | 100 mm dia |
| 75 | Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 76 | 100 mm Dia. x 150 mm Oal |
| 77 | Providing & fixing sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 78 | 1200 mm Long |
| 79 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 80 | 3 core 185.0 Sq.mm |
| 81 | Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 82 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 83 | (b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts |
| 84 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 85 | (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. |
| 86 | (d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. |
| 87 | (e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 88 | 25 mm thick and 3 Mtr. Long |
| 89 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 90 | 25mm x 6mm G.I. ( Hot Dipped ) Strip |
| 91 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 92 | 8 SWG copper Wire |
| 93 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 94 | 4 pole MCCB With Thermal Magnetic release |
| 95 | 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 96 | 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 97 | Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 98 | Ring type tape wound CT |
| 99 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
| 100 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 101 | Red/yellow/Green colour |
| 102 | Blue / white Colour |
| 103 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 104 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 105 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 106 | 6.0 Sq. mm |
| 107 | 4 core |
| 108 | 185.0 Sq. mm |
| 109 | 3.5 core |
| 110 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 111 | 3.5 x 185.0 sq.mm |
| 112 | Supply, Fabricating & installing following sizes of Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with rungs at span of 250mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with M.S. suspenders etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 113 | 150mm x 50mm x 1.6mm |
| 114 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 115 | Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 116 | Cat 6, Un-sheilded Information Outlet |
| 117 | Supply, Installation, Testing and Comissioning of Rack mounted 19\\" 1U, Cat6 24 Port loaded, 1.5-1.6 MM CRS chasis, powder coated, sheet steel, made of plastic (ABS), Modular Patch Panels with Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 118 | Modular Patch Panel Loaded with Cat -6 I/O |
| 119 | Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns), continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. |
| 120 | Poles with Octagonal Cross Section |
| 121 | 3 Mtr. |
| 122 | Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . A) Excavation of Pit for Foundation Size upto required depth from Ground level B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days. H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face. |
| 123 | Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. |
| 124 | Providing & Fixing of IK08 IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with sand blast reflector. The System level Luminous efficacy ≥ 100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA. Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 125 | Minimum lumen output 4000 lm Post top Luminarie |
| 126 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 127 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in char e. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 128 | Electrolytic grade Aluminium bus bar 6010 grade |
| 129 | SITC of Monoblock motor pump set ISI marked (IS:9079-2002) with TEFC motor, motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011. with Stainless steel Impellor, Stainless steel shaft, Mechanical seal, Single/Three phase ( 240 - 440 V ) permanent split capacitor type (PSC), fitted with thermal overload protection, Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 130 | 5.0 HP, 3-Ø, (24-44)Mtr, (680-370) LPM |
| 131 | SITC of Drain Sewage pump Non-clog fully floodable submersible pump suitable to handle raw sewage suitable for up to 40 mm solid with Cast iron CED coated Impellor, CI body & housing, SS shaft, Mechanical seal etc. as required. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively complete in all respect. Appropriate type test certificate / OEM test report shall be submitted.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 132 | 1.0 HP, 3-Ø, (6 - 12)Mtr, (333 - 45) LPM |
| 133 | SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect. |
| 134 | For single phase Submersible / Monoblock pump |
| 135 | 0.5 HP to 1.5 HP (DOL starter) |
| 136 | For Three phase Submersible / Mono block pump |
| 137 | 7.5 HP to 10.0 HP ( Star / Delta starter ) |
| 138 | Providing and constructing masonry chamber 90 x 90 x 100 cms inside with brick work in cement mortar 1:5 (1cement : 5fine sand) for water meter ,M.S. cover (6mmthick sheet with locking arrangement, 600 x600 with M.S. frame etc. all epoxy coated and R.C.C. top slab 1:2:4 mix(1 Cement : 2 coarsesand : 4 graded stone aggregate 20mm nominalsize) including necessary excavation, back fillingfoundation concrete 1:5:10 mix (1 cement : 5 fine sand and 10 graded stone aggregate 20mmnominal size) leaving a pocket of 30x30 cmwith out concrete and filled with pebbles andinside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finishedwith a floating coat of neat cement and outside plaster finished rough complete. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 139 | Providing and laying Non Pressure NP-3 class R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth & Back filling with compaction is to be Paid Extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 140 | 450 mm dia. |
| 141 | Providing and fixing of Fire / Electrical Shaft Door made from powder coated (50 Micron) aluminium partialy glazed with 6 mm thick glass and Partialy / Fully Louvered with Outer frame of Aluminium Section of Size 100 mm x 45 mm x 1.5 mm and Shutter's Top, Middle & side Section of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mm Complete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 142 | Providing & Fixing of IP65 IK08 rated Integrated High power LED ( each LED between 3 to 5 watt power with secondary lencs on each LED) Highbay light fixture made from Pressure Die Cast Aluminium housing, toughned glass diffuser, potted driver, Eye bolt for mounting, system lumen efficacy ≥140 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. surge protection 4 KV inbuilt & 10 KV external inside fixture. |
| 143 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 144 | Minimum lumen output 16500 lm |
| 145 | SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 146 | 320 KVA |
| 147 | NON BSR |
| 148 | SITC of factory assembeled Ceiling suspended/Floor mounted double skin Air Handling Unit having specifications as per A, B, C, D, E & F |
| 149 | A. Mixing Box : Mixing box with manually operated fresh air and return air dampers in aluminium construction |
| 150 | B. Pre filter section : Pre-Filter (EU-4) section complete with 50mm thick washable synthetic fibre filters. Velocity across the filters shall not exceed 500 FPM. Filters shall have efficiency not less than 90% down to 10 Microns (EU-4/MERV-8). Filter material shall be non combustible type. |
| 151 | C. Coil Section : Coil section with 6 rows (3+3) deep chilled water cooling coil/ DX cooling coil of copper tube & copper header and aluminium fins construction having wall thickness of tubes not less than 0.5mm. Drain pan shall be made out of 18 gauge SS-304 duly insulated with 13mm thick closed cell elastomeric insulation with class 'O' fire retardant properties. Face velocity across cooling coil shall not exceed 500FPM. - Space Provision for coil to be provided. Drain Pan with drain arrangement to be provided for coil at this stage. |
| 152 | D. Fan Section : Fan Section comprising of belt driven, DIDW forward / Backward curved AMCA certified centrifugal fan with maximum air outlet velocity of 10m/s suitable for required cfm at 50 mm static pressure (Total static of the unit shall be verified by the OEM before the design & supply of the units). Fan & Motor should be mounted over Aluminium channel of suitable thickness and should be isolated from the unit's bottom panel. |
| 153 | E. Motor : TEFC High efficiecny IE-3 class motors suitably designed for VFD with pulley, belt , Guard |
| 154 | F. The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 48 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins. ,The AHU shall be with thermal break profile with internal coving section complete with inspection doors, marine light, limit switch and control wiring as required. AHUs shall have access for all parts. noise level shall not exceed 70 dB, necessary vibration Isolation arrangement like spring hanger etc. as required. |
| 155 | more than 2000 cfm to 4000 (cfm 4 nos 2400 cfm) |
| 156 | SITC of cabinet type(sound insulated casing) Inline fans for ventilation including motor, with forward curved Direc driven DIDW fan, motor and drive suitable for 220 ± 10% volts, 1 phase, 50 Hz A.C supply, thermal overload protection, including making connections, ancilliary structure to suspend it from beam/slab, vibration isolator etc. as required of following sizes. (cost of canvass connection to be paid extra ) etc .as required. |
| 157 | 2501 cfm to 3000 cfm at 20 mm static |
| 158 | Supply & Laying of 2 Core size 0.5 sqmm copper shielded Cable for connectings Microphones with related conduits / fittings / termination, etc complete as required. |
| 159 | SITC of Radiator Cooled Silent DG Set (As per latest CPCB-IV+ emission norms) having specifications as per A, B, C, D, E, F & G : |
| 160 | A) Diesel Engine : Turbo charged Diesel Engine ( conforming to BS:649/5514), multi cylinder, dynamically balanced flywheel, electric start of suitable BHP at 1500 rpm capable of taking 10% over loading for one hour after 12 hours of continuous operation., Dry exhaust mainfold with silencer and Diesel oxidation catalyst & selective catalyst reduction system (isolated from main DG chamber), up to 1.50 M exhaust piping (with LRB insulation & Alum. cladding ) as required .Diesel engine should have Precise emission control by treatment with Diesel exhaust fluid (DEF)/Aqueous urea tank (above 82.5 KVA) as per CPCB 4+ norms |
| 161 | B) Alternator : AC Brush less SPDP Synchronous alternator rated of appropriate KVA, 415 volts at 1500 rpm, 3 phase, 50 Hz, ac supply with 0.8 lagging power factor. Alternator conforming to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). |
| 162 | C) Canopy : CPCB / ARAI approved Standard canopy with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from CRCA sheet steel (structure) including sidewals & filled with glasswool (96Kg/m3) /PU Foam. as per IS8183 and the thickness of the doors should be 28/40/50/85 mm as per rating . All doors/opening are sealed with neoprene /EPDN gaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs along with DEF tank (as per OEM standards). There should be provision of protection and tripping of DG set for temperature greater than 50 degree centigrade. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. in open free field environment as per ISO 8528 part 10 duly certified by authorised agency etc. |
| 163 | D) Instruments : Electronic / Mechanical governor, Manual & electric Start ,Batteries with battery charger, Electronic fuel system, advanced after treatment system (ATS), Exhaust gas recirculation(EGR) System along with Diesel oxidation catalyst(DOC) and Selective catalytic reduction (SCR) , supply module and DCU to control and monitor DEF. Engine instruments panel should have microprocessor based Genset monitoring system capable of displaying Running Hour, RPM, lubbrication oil pressure indication, lubrication oil temperature, battery charging indication, overspeed indication, fuel level etc. The control Panel should equipped with MCCB/ACB of suitable rating. |
| 164 | E) Base frame and foundation : Both the engine and alternator shall be mounted on suitable base frame made of MS channel & coupled through a flexible coupling or close coupled which shall be installed on existing cement concrete foundation and vibration isolation arrangements as per recommendation of manufacturer. |
| 165 | F) First filling of the FUEL Tank and DEF tank shall be done by contractor. |
| 166 | G) DG set will be offered for Inspection and Testing at OEM's Works ( as per approved QAP ) in presence of Departmental Engineers .In case of 13 hour running testing at OEM's works, cost of actual consumables will be reimbursed. |
| 167 | Note: 1. During the DLP, the contractor shall arrange for servicing of the DG set through authorized dealer of OEM, as per the manufacturers guidelines. The actual cost of consumables used during servicing will be reimbursed to the contractor by the end user department.2. Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. |
| 168 | 320 KVA at 0.8 pf 415V 50Hz 3-ǿ with 6 Cylinder Engine |
| 169 | SITC of following capacity BIS certified 1Phase Input, 1Phase Output advance DSP controlled IGBT based rectifier Online UPS with Inbuilt Isolation Transformer having 0.99 Input power factor & 0.8 Output factor, Input voltage & frequency range of 180-300V on full load/ 110-300V on 50% load & 50 Hz +/- 5% and output voltage & frequency of 230V+/-1% & 50 +/- 0.1 Hz. Overall efficiency of upto 92% (without Transformer Loss), Overloading of 105 - 110% 30 mins, 111 - 130% 5 mins,131 - 150% 10 sec, THDv of < 3% for Linear & < 5% for Non linear load.UPS should have LED Panel with LCD display showing load level, Battery Voltage Level, Input & Output Voltage, Input & Output Frequency. UPS should have protection from Input High / Low;Over Load;Short Circuit; Over Temperature and give audible alarms on Battery Mode;Low Battery;Fault;Over Load & Bypass Mode. SMF Batteries of 12V VRLA for 30 mins with MS Rack and necessary cable for UPS to Batteries Installation. UPS should have valid Certification like Type III environmental declarations from third party renowned agency complying to ISO 14025, CE, ROHS,BIS,EN 62040-1, EN 62040-2, IEC 62040-3 Etc. as required. |
| 170 | 10KVA UPS with 9072 VAH Battery |
| 171 | Supplying, Installation, Testing and commissioning of indoor Wireless Access Point for Low Density use having features and specifications etc. as mentioned here under - Dual-band Wi-Fi6 (802.11ax) 574Mbps (2.4GHz) + 1200Mbps (5GHz), WI-FI 6 Certified, 1 x RJ45 console port, 1G LAN POE Port, factory reset, WPA/WPA2/WPA3TM Personal/Enterprise, WEP 64/128-bit, SSID broadcast disable, MAC address access control, Internal RADIUS server, SNMP, Customizable Captive Portal, Auto Channel, Works as Access Point, WDS, WDS with AP, Wireless Client, Web (HTTP), Secure Socket Layer (SSL), Traffic control, Support ATF/Fast Roaming/Band Steering, Supports enhanced security – WPA-PSK/WPA2- PSK/WPA3-PSK and RADIUS client, and Cipher negotiation, and MAC/ IP ACL for networks, Certifications: MTCTE, CE, FCC. Should also work as Standalone and must be Compatible with S/W & H/W Controller with addtional features like - Real-Time Monitoring and Alerts, Rich Advanced Features, Centralized Device Management, Role-Based Administration, Real-Time Monitoring, VLAN and Access Control, Auto RF Management and Bandwidth Optimization, Multi-SSID and Captive Portal Authentication.OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. |
| 172 | Supplying, Installation, Testing and commissioning of indoor Wireless Controller having features and specifications etc. as mentioned here under- The network controller shall be a dedicated hardware appliance designed for centralized management of wireless access points, It must support the management of up to 500 networking devices, The system should be on-premise, ensuring data privacy and complete control over network configurations. It must include an intuitive user interface for real-time monitoring, device discovery, firmware upgrades, scheduling, and mass configuration deployment. Features such as role-based administration, multi-site management. AP to controller communication shall be use of industry standards-based (IEEE or IETF) CAPWAP or any tunneling protocols as per guidelines of DoT.The controller should support Layer 2 and Layer 3 device discovery, VLAN configuration, MAC ACL groups, IGMP snooping, and bandwidth optimization. Automatic radio frequency (RF) management and access policy enforcement are required for reliable wireless performance. The solution must offer a comprehensive dashboard with network topology, floor plan views, client and device lists, and alert notifications. For authentication, it should support a range of methods including local database, external RADIUS, LDAP, and passcode or MAC-based access. It should provide detailed traffic analytics, logs, and customizable reporting for network visibility and planning. Firmware and configuration backup and restoration functions must be available, with USB- based log storage supported. Physical specifications should include a compact form factor with a minimum of one 2.5G Ethernet port and USB 3.0 port, and it must be MTCTE,CE, FCC, and RoHS certified. The controller should operate reliably within a 0°C to 40°C temperature range and 10–90% non-condensing humidity. /Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. |
| 173 | SITC of IP20 recess mounting accent lighting luminaire with dia cast aluminium heat sink and sand grain finishing reflector with DALI dimmable driver round LED down lighter not less than 40 watt wide beam ,3000 k ,≥100 lm/w system . |
| 174 | SITC of Digital Podium; Integrated Central Teaching Platform, (a) Main Cabinet System - Metallic structure customized to house hardware/software with powder coated fitted with following specification as below :- Display -Interactive Panel (23.8\\" active diagonal size)/ 21\\"/ 19\\" (As per requirement), Resolution 1920 X 1080, 10 Points Multi-touches Free stylus with eraser switch, Video I/O port, four shortcut keys, 1173-degree adjustable tilt stand with accessoriesIntegrated Controller Touch panel control minimum 7\\" or better (must be fitted in Podium) Min 1 VGA Input, Min 1 VGA Output / HDMI Out / USB Type C port Min 2 Screen control port Min 2 RS 232 Port IR receiver for IR Control Min 2 Hybrid Relay Ports Min 1 LAN Port |
| 175 | Squelch Control and frequency from 100 Hz to 15000 Hz (impedance less than 280 ohms) Temperature controlled fan Integrated Temperature controlled Cooling fans to help regulate the right temperature for the podium Mobility 4 Wheels or more as required Rack Storage 19U or more (to keep tablet/writing panel, CPU, video mixer, DSP, Amplifier, switch &Wi-Fi modem) Extra Ports on the podium- Power outlet, USB, LAN, RGB, Audio In, HDMISecurity Locking front and sliding cover doors, Keyboard Pull out the shelf for the keyboard Controller Movement of Screens, Projector, LCD Display, and Volume adjustment shall be controlled through the controller Video Output can be switched from Podium Desktop and Writing panel through controller Video Output can be switched from current location to remote location from the desktop/ laptop/ controller Video Output of tablet/ camera of the class can be viewed at the remote site Synchronization of student interaction mic with mixers/ DSP for every participating class Synchronization of different speakers / mic, video equipment and amplifiers in all the classes Fixed inside the podium/dias resolution : 800X480 Note: Any deviation/ alteration/ modification in the specification will not be considered valid. |
| 176 | Supply & fixing of FLEXI STRIP IP20 ALUMINUM PROFILE with opal diffuser helps to distribute light evenly having min. thickness 0.4 mm, min. width 17 mm, min. depth 10 mm as per site conditions complete with end cap mountig clamps etc. as required. |
| 177 | SITC of IP-20 high brightness flexible LED strips for Profile Light having operating voltage 140 V - 270 V AC, System Lumen efficacy of ≥ 85 lm /watt, life time of minimum 30000 Burning Hours with 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin), flexible PCB, dual layer base, with 2.5 kV surge protected isolated driver having open and short circuit protection and other safety tests as per IS 15885 part 2/Sec13 having efficiency > 85 % as required. wire is used to connect the product with Constant voltage driver through connector. |
| 178 | min. 4 W/mtr and having min. 60 LED/ mtr |
| 179 | Supply, Installation, Testing and Commissioning of Projector Laser phosphor, 1920X1200 native resolution, min. 11000 lumens, Contrast Ratio : 300000: 1, Illumination life 20000 hours, Motorized horizontal and vertical lens offset , Inputs: 3G-SDI x 1 (BNC), HDMI x 2(HDCP2.2), DVI-D x 1, ,HD base T , Controls: RS232 in/out, RS422 in, Ethernet (10/100), USB, device, should be complete including Lens with Short throw ratio 1.35 - 2.10:1 or better including all necessaries accessories as required. . |
| 180 | SITC of IP-20 min. 3 ft, min. 6 Watt LED (with alphabet or numbers) theatre step Mounted light made of integrated Powder Coated diecast/Extruded Aluminium body with down throw or step illumination having CCT 2700°K/3000°K provided with diffused film and reflector tape treatmnt for enhanced and uniform light glow, EPDM rubber anti skid strip shall be provided for safety and should have nylon side caps with overlapping design for better asthetics including driver and an openable pin hole to conceal screws as required. |
| 181 | Supply and Fixing of row number display for auditorium steps as required. |
| 182 | SITC of following diagonal size professional Display, 4k Resolution, Brightness(Typ.) 440 nit and above , Contrast Ratio-2000:1 and above, Viewing Angle(H/V)-178/178, Response Time(G-to-G) 8ms, Input: RGB- Analog D-SUB, Video- HDMI 2.0 (2), HDCP- HDCP 2.2, Audio- Stereo mini Jack, USB- Only F/W upgrade, Outputs: RGB- DP1.2(Loop- out), Audio- Stereo mini Jack, External Control- RS232C(in/out), RJ45, External Sensor Detachable type(IR Ambient). Operation Hour 24/7. mounting bracket etc. as required. |
| 183 | Supply, Installation, Testing & Commissioning of Size (Diagonal) 86” or higher Panel Technology Resolution (Minimum) IPS/ VA 4 K (3840 x 2160 ) Brightness Contrast Ration (Typical) 400 nits or better, 1200:01 or better 178*178 Viewing Angle (H x V) Response Time RAM 8 ms or less 4 GB or higher On-board Memory Input (Minimum) 32 GB or higher 2 x HDMI, 4 x USB (Out of which min 2xUSB3.0), 1 x Audio, 1 x OPS slot, 1 x USB Type- C Port Output (Minimum) Panel Life (Minimum) 1 x HDMI, 1 x Audio 30000 Hours or higher Wi-Fi Supports External Control Wi-Fi (802.11 a/b/g/n/ac) Support RS232C (1), RJ45 (1) Speaker Platform Built-in Speaker (15 W+ 15 W) or higher Android 13.0 or higher Detection Method Pen (Stylus) IR/IPV 2 nos. with dual pen support and Magnetic Fixtures Operating System Support Windows / Linux / Android Multi Touch Point Surface Hardness Minimum 20 Points with +/- 2.0 mm or better Minimum 3.0 MM Toughened Glass with level 7 MOHS Standard or higher surface hardness (configuration) Features Panel Features Smart Writing of different colors & annotation Interactive flat panel with Light Sensor / Manual Light & Brightness Control, Connectivity via wireless Screen Cast, Wireless Screen Sharing from Mobile, Tablet, Laptop/PC Model specific Certifications BIS, UL Compliance ROHS, ISO 9001 User Convenience Features Multi-Screen with PBP/PIP, min 2 split view, etc. Accessory Power Cable (IS), HDMI Cable, User Manual, Wall Mount Kit as per requirement |
| 184 | Supply, Installation, Testing & Commissioning of Size (Diagonal) 75” or higher Panel Technology Resolution (Minimum) IPS/ VA 4 K (3840 x 2160 ) Brightness Contrast Ration (Typical) 400 nits or better 1200:01 or better Viewing Angle (H x V) Response Time 178*178 8 Ms or less RAM Onboard Memory 4 GB or higher 32 GB or higher Contrast Ration (Typical) 1200:01 or better 178*178 Viewing Angle (H x V) Response Time RAM 8 ms or less 4 GB or higher On-board Memory Input (Minimum) 32 GB or higher 2 x HDMI, 4 x USB (Out of which min 2xUSB3.0), 1 x Audio, 1 x OPS slot, 1 x USB Type- C Port Output (Minimum) Panel Life (Minimum) 1 x HDMI, 1 x Audio 30000 Hours or higher Wi-Fi Supports External Control Wi-Fi (802.11 a/b/g/n/ac) Support RS232C (1), RJ45 (1) Platform Built-in Speaker (15 W+ 15 W) or higher Android 13.0 or higher Detection Method Pen (Stylus) IR/IPV 2 nos. with dual pen support and Magnetic Fixtures Operating System Support Windows / Linux / Android Multi Touch Point Surface Hardness Minimum 20 Points with +/- 2.0 mm or better Minimum 3.0 MM Toughened Glass with level 7 MOHS Standard or higher surface hardness (configuration) Features Panel Features Smart Writing of different colors & annotation Interactive flat panel with Light Sensor / Manual Light & Brightness Control, Connectivity via wireless Screen Cast, Wireless Screen Sharing from Mobile, Tablet, Laptop/PC Model specific Certifications BIS, UL Compliance ROHS, ISO 9001 User Convenience Features Multi-Screen with PBP/PIP, min 2 split view, etc. Accessory Power Cable (IS), HDMI Cable, User Manual, Wall Mount Kit as per requirement |
| 185 | Providing and fixing 12 mm thick Acrylic solid surface material of approved colour and make over the flexible plywood base of required shape.Preparation of Base : Concentric rings of 25mm thick BWP grade plywwod shall be placed at required intervals of Diameter required to achieve the desired shape and design. Aluminium pipes of size 25x50x2 mm to be closely installed vertically so that the flexible ply can be rolled over it. Then screw the 12 mm thick flexible ply over the aluminium frame to provide a smooth surface forming the central core of the pillar. Rings made of 25 mm thick BWP grade Ply are then fixed Horizontally along with vertical cleat members arranged so as to form a designer base required to achieve the desired shape and design. Flexible ply of 12 mm thickness is then fixed to this base and then finally cut to achieve the final design as per requirement.The Acrylic solid surface material is installed by cutting, seaming, bending and thermoforming pieces using a router and specialized adhesive including preparation of plywood surface by smoothening, layering, polishing etc. to achieve a seamless, high-quality finish on the solid surface.The top and bottom edges of the curves should be moulded to give a seamless and continuous surface round edge look.Thereafter placing the pre-fabricated Acrylic solid surface material pieces after thermoforming over the existing designer plywood base, align them using spacers for an even cut, and use a router with a straightedge to trim the edges so they meet perfectly. Apply the specialized joint adhesive to the cleaned and prepared seams. Bring the pieces together, clamp them firmly, and let the adhesive cure to create an inconspicuous seam. Once the adhesive is set, use a scraper or other tools to carefully remove any excess glue. Sand the seams to the desired finish to blend them into the surrounding material, using progressively finer grits of sandpaper. Finally the surface is polished to achieve glossy finished surface complete as per the design, specifications, directions and approval of Engineer-In-Charge. |
| 186 | Providing and fixing Stainless steel glass railing in curved shape, fixed on platform with required SS 304 grade brackets plates along with Stainless Steel 304 Grade Balusters of 40mm wide and 12 mm thick bar fixed on floor using 12 mm dia fastners connecting with the safety glass and 50mm SS 304 pipe railing as per design, specifications and directions of Engineer-in-charge. Firstly MS base plates are fixed using fasteners and levelled with MS packing like plates, square pipes for rigity of the base plate. The SS brackets are then fixed over the base plates. The Safety glass shall be made of Toughened glass (8+8mm with 2.5mm lamination). The contractor has to install a sample at his own cost and start the work only after approval of sample by the Engineer-in-charge. (Area of glass is to be measured for payment) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
| 9 | Click here to download tender document | Tender Documents |
| 10 | Click here to download tender document | Tender Documents |
| 11 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail