| 1 | Dismantling and Taking out of existing octagonal/Swaged poles along with street light fittings upto 12/10/8 mtr length from Cement concrete foundation by the help of crane of suitable capacity and with manual labour i/c loading and carriage/ transportation by suitable truck from various sites upto distance of 25 Kms of PWD Roads to PWD Sub Division office at Rama Road JE(E) store and storage at safe place i/c. unloading etc. as reqd i/c taking permission from traffic police if required. if any mishappening will occur during entire work only the agency will be the responsible. (As and where basis) |
| 2 | Reinstallation of existing octagonal/Swaged poles along with street light fittings upto 12/10/8 mtr length from Cement concrete foundation by the help of crane of suitable capacity and with manual labour i/c loading and carriage/ transportation by suitable truck from PWD Sub Division office at Rama Road JE(E) store to various sites upto distance of 25 Kms of PWD Roads. if any mishappening will occur during entire work only the agency will be the responsible. (As and where basis) |
| 3 | Providing and laying in position 1:2:4 reinforced cement concrete foundation of size 600 mm.(L) X 600 mm. wide and 1500 mm. deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm. dia- 1660mm long (approx)- 8 Nos. and reinforcement ring of cold twisted bar of 8mm dia - 2200mm (approx) - 10nos. (with 150mm spacing) as required along with foundation bolt M-24 x 850mm EN 8 grade having 2 galvanised locking nuts with 2 galvanised plain washer (as per item below) including welding the nuts and providing 63 mm. (O.D) DWC, HDPE Pipe for cable entry & exit as required. (For 8,10 & 12 Mtr Pole) (As and where basis) |
| 4 | Supplying and fixing of 40 Amp terminal block suitable for 25sq.mm conductor -4 nos. & shorting links – 5nos. on DIN channel i/c pdg. and fixing DIN channel of suitable length – 2 nos. on the existing laminated sheet.a) Supplying and fixing 6 Amp, SPMCB, ‘C’ Characteristics Curve - 2 No. Earth stud-2Nos. welded at suitable height two nos. washers, springs washers & nuts.b) Cable support clamp suitable for 4 Nos of 4x25 sqmm cable.c) The nuts and bolts shall be welded.. |
| 5 | Supplying & Fixing of following size Aluminium thimble with proper connection and PVS Tape etc as required. |
| 6 | 16/25 Sqmm |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 8 | Upto 35 sq. mm |
| 9 | Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade in RCC/DWC Pipe/ by excavation of all type of soil having minimum depth 2 feet/Open Channel etc as required. |
| 10 | 4 x 25 Sqmm |
| 11 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 12 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.. |
| 13 | Supplying of reducer of GI for fixing on existing pole bracket and the outer dia minimum 40mm while fixing dia not less than 55mm with the provision of 4 Nos of fixed Nut Bolts for tightning. |
| 14 | Supplying and drawing following sizes of XLPE Insulated and PVC Round Sheathed Aluminium Conductor Heavy Duty Industrial Cables for Voltage Grade 1100 Volts as per IS: 694:1990. (Internal Wire) |
| 15 | 3 x 2.50 Sqm |
| 16 | Fabrication, Designing, Supplying & Fixing of 1000 mm long Single / double / triple/Circular arm bracket(Thickness minimum 3MM) over hang with tightening bolt etc. as per design approved by Engineer-In-Charge. |
| 17 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) |
| 18 | 150 Watt Please Enable Macros to View BoQ information |