| 1 | SITC of Tube-axial Smoke exhaust fan complete with cast aluminium impeller and all standard accessories like drive motor suitable for handling hot gas of temperature 350 Deg C for 2 hours, motorized isolating damper at fan inlet, rain protection cowl with bird screen/back draft damper at fan discharge, supports and supporting structures, for 4 point clamping with Vibration spring isolater and Motorized damper shall be rated for 240 V, 50 Hz, 1 Ph., AC supply.The Motor shall be of TEFC, IP-55 protection, Class 'H' insulation, motor shall be of IE-3 efficiency, suitable for 3 Phase, 415volts, 50hz power supply.Fan Shall be Oprating in Dual Mode in Normal Ventilation & another in Fire ModeFan Make - Airflow /Krugger/NikotraCapacity of each Fan : 12000 CFM IN FIRE MODE & 6000 CFM IN VENTILATION MODE Static Pressure : 25 mmWG |
| 2 | Area - Lift Corridoor & Its Adjoing Common Passage area . 15000 CFM IN FIRE , Location - AHU Room |
| 3 | 8000 CFM IN FIRE , LOCATTION - AHU ROOM |
| 4 | SITC of Wall mounted type Fresh air Fan Filter Unit consists of Tube Axial flow fan with High Efficiency Drive Motor (conforming to IS-12615) TEFC with Inlet Louver, supports and supporting structures, vibration isolators, nuts and bolts and short ducting with SA register (if required). Motorized damper shall be rated for 240 V, 50 Hz, 1 Ph., AC supply and The Motor shall be of TEFC, IP-55 protection, Class 'H' insulation, motor shall be of IE-3 efficiency, suitable for 3 Phase, 415volts, 50hz power supply.Fan Shall be Oprating in Dual Mode in Normal Ventilation & another in Fire ModeCapacity of each Fan : 10000 CFM IN FIRE MODE & 5000 CFM IN NORMAL VENTILATION MODE Static Pressure : 15 mmWG |
| 5 | Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BMS. All starters shall be provided with potential free Contact for Connections to Building Automation System.Over-load relay, suitable for motor duty and able to withstand fault level of suitable KA rating.single phase preventer (Electronics type) as per the ratings given below.Terminal block for power distribution.Power Contactor.Phase indicating lights and indicating light for ON/OFF/TRIP status phase sequence relay shall also be provided.Time delay relay for delayed automatic restart of motor (0-180 sec).Integration with fire alarm detection system and fire damper for starting / stopping the fan (in case of fire) / Power supply for damper control panel.For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation.All starters shall be provided with suitable potential free contract for connections to the Building Automation System.The number of control panels shall be as follows.Make (Swithcgear) - ( MCCB : Make-Legrand-(DPX3)/Schneider-(CVS)/Siemens-(3VA) /ABB (Tmax), MCB : Make-Legrand-(DX3)/Schneider-(Acti9)/Siemens-(betagard)/ ABB (SB200)16/25/32/63A 4P MPCB with 5/10/15 HP Three phase VFD with bypass star delta/DOL starter with overload relay and single phase preventer . Each of these compartment shall contain indicating lamp with ON/ OFF/ TRIP status for fan sections/axial fans. |
| 6 | Supply and fixing of emergency pushbutton for remote start and stop of smoke exhaust fan infront of ICU, SNCU, New born and other Critical care units. |
| 7 | S/I/T&Commissioning of LT intdoor floor mounted cubical type electrical panelmade out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder coated paint is designed as G.A drawing.as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.. 20X10MM Separate Aluminium Earth bus bar should be installed. All the feeders shall have ON/OFF/TRIP indication. .Provision of 40kA 3P+N type 2 SPD alongwith 63A, 4P, MCB, C series, 10kA is to be given in the incomer.Mandatory provision of cable alley is to be given.Incoming: 100 Amp. 4P MCCB 16 ka with with adjustable thermal setting, Ics=100%Icu ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ ABB Formula) Busbar : 04 numbers of 150Amps Aluminum busbar duly sleeved by color coaded PVC sleeve & supported by suitable size DMC insulator. .Outgoing: 32 Amp.4P MCB 10 KA, C series -5 NosInstrument- (i)The incoming feeder shall have phase indicating lamp for R,Y,B inndication with 2A SP MCB,C,10KA. ( Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200).(ii) 01 set of 3 ph digital type Voltmeter(Make-Siemens/Schneider/ABB/Legrand).(iii)01 set of 3 ph digital type Ammeter(0-150)A(Make-Siemens/Schneider/ABB/Legrand) with CTs 125/5A 3 nos class 1 typeMake of MCCB- LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ ABB FormulaMake of MCB- Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200Make of SPD-LEGRAND/SIEMENS/SCHNEIDER/ABB/OBO/DEHN |
| 8 | Supplying and laying of one number PVC insulated armoured and PVC sheathed XLPE property Copper conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge.4CX6 sqmm |
| 9 | supply installation testing commissioning of sel propelled scissor lift for emergency maintenance and evacuation from first floor level having following features:Proportional Joystick Controls, Self-Locking Gates, One-Way Platform,Extension Deck, Drivable At Full Height, Non-Marking Tires, 4×2 Drive, Four-Wheel Braking, Emergency Descent System, Tubing Explosion-Proof System, Onboard Fault Diagnostic System, Tilt Alarm, Motion Alarm, Horn, Hour Meter, Safety Arm For Troubleshooting, Standard Transport Forklift Holes, Charging, Protection System, Flashing LED Beacon, Foldable Guard Rails, Automatic Pothole Protection, Drive Enable, Automatic One-Way Platform Extension Deck, Manual Brake Release, Lanyard Attachment Point, Tie-Down And Lifting Points, BATTERY SCISSOR LIFT - SELF PROPELLED , Working height 13.80M, Platform Height 11.80M, Safe working load : 408 kg.Make-MT and T(Model No: S1412AC+)/JCB |
| 10 | Supply & Fixing of Air Distribution Duting fabricated with Class VI GI Sheet(180 GSM) Complete With Supports, dampers, guiding vanes, access doors, MS Angle, Fire inhibiting gaskets, Nuts, bolts and all oyher accessories in accordance with approved drawing and the Specification. (Make:- Jindal/ Sail/ Tata)24 gauge (0.63 mm thickness) |
| 11 | 22 gauge (0.80 mm thickness) |
| 12 | Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required..Fire Dampers (Make: Air Flow/ Systemair/ Dynacraft) |
| 13 | Actuators. (Make:- Belimo/ Siemens/ Danfoss) |
| 14 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 200mm(W) of Make- Profab/ OBO/ Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge. |
| 15 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. Make- Honeywell(MAX) /Siemens/ Bosch/ Edward/ NOTIFIER/ GST/ Schneider |
| 16 | Supplying & Testing of 1.1 KV grade Cu XLPE Un Armoured (Flexible) power cable of following size suitable for 415 Volt, 3Ph, 50 c/s supply. (Make:- Polycab/ Havells/ KEI/Gloster/Finolex/RR Kabel)4Cx1sqmm |
| 17 | SITC of MS Structure Work with MS member like C channel , ISMB Member , Angle of necessary size to Fabricate & Install . The Installed Structure shall be of the duly painted with primer & two coat paint |
| 18 | SITC of removing the False ceiling & making them Good for during the Work |
| 19 | SITC of HVLS fans for Floor Mounted fan with heavy duty wheels for transportation /Ceiling mounted of 2 mtr wide with fully enclosed suitable for the 50 sqmtr area . Fan shall be energy efficent system with speed control . Make- JCB/AUSTAR Technology/Marutair Please Enable Macros to View BoQ information |