| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. D.S.R 1.10.3 |
| 2 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit asrequired.1x 1.5 sq.mm for inverter D.S.R 1.17.1 |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). D.S.R 1.56 |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. D.S.R 1.13 |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. DSR 1.32 |
| 6 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X1.5 sq. mm + 1 X 1.5 sq. mm earth wire D.S.R 1.14.1 |
| 7 | 2 X2.5 sq. mm + 1X2.5 sq. mm earth wire D.S.R. 1.14.2 |
| 8 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire D.S.R. 1.14.3 |
| 9 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire D.S.R. 1.14.4 |
| 10 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire D.S.R. 1.14.5 |
| 11 | Supplying and fixing call bell/ buzzer suitable forsingle phase, 230 V, complete as required. D.S.R. 1.38 |
| 12 | Supplying & fixing suitable size Gl box with modular plate and cover in fronton surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. D.S.R. 1.57 |
| 13 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. D.S.R. 1.33 |
| 14 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. D.S.R. 1.58 |
| 15 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet D.S.R. 1.24.7 |
| 16 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. D.S.R. 1.19 |
| 17 | Supplying and fixing of 25mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. D.S.R. 1.21.2 |
| 18 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Up to 450 mm sweep D.S.R. 1.50.1 |
| 19 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). D.S.R. 2.4.1 |
| 20 | Supplying and fixing 12 way , Double door single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) |
| 21 | Supplying and fixing 8 way , Double door single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) |
| 22 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole D.S.R. 2.10.1 |
| 23 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole D.S.R. 2.10.3 |
| 24 | Providing and fixing of 4kg capacity ABC stored pressure type fire extinguisher bearing ISI Mark for fighting ABC Class of fir.The extinguisherwill be manufactured strictly as per BIS:15683:2006 Bearing ISI mark.EN3615 Approved Powder.ABC 87%MAAP.Value with additional facilities like operating temperature marking on value.Automatic safety release valve &noon returnable valve PWD approved make like Ceasefire kanex and safex or equivalent |
| 25 | Earthing with G.l. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. D.S.R. 5.2 |
| 26 | Providing and fixing 25 mm X 5 mm G.l. strip on surface or in recess for connections etc. as required. D.S.R. 5.15 |
| 27 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt)Powder coated die cast / Extruded aluminium Body (Thickness≥ 1.20 mm)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range-50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker shouldbe below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥120 <135 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast / Extruded aluminium Body (Thickness≥ 1.20 mm)18- 22 watt D.S.R 8.10.1 |
| 28 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy ≥120 and <135 lm/Watt)Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C).70 watt D.S.R. 8.16.2 |
| 29 | Brush Less Direct Current (BLDC) Fan without Remote.Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminiumalloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value(CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion)less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required\\"1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)\\" D.S.R. 9.2.3 |
| 30 | Supply & layimg and fixing og one number PVC insulated and PVC sheared/XLPE power cable of 1.1kv grade of size25 sqmm 3-1/2 core on wall surface as required SOR 20.1.10 |
| 31 | SITC of 25 L Havells(GHWCAITIV025)storage type electric geyser, 230V, single phase, complete with thermostat, safety valve and connections etc. as required. |
| 32 | Supply and installation of split type 5 star invertor type O-General(CETA-B Series) and equivalent |
| 33 | 5KVA Voltage stabilizer for Air Conditioner upto 2. TR (130-300Range) |
| 34 | SITC of Suction/discharge copper pipe line in split A.C 1.8/2.0 Ton capacity including brazing.Nitrile rubber insulation 6mm Thick class O Etc complete 3/8\\"(9.50 mm) and 5/8 (15.90mm) |
| 35 | S/F of outdoor unit stand for split A.C. |
| 36 | S/F OF Heavy duty PVC plastic braided 20mm OD flexible pipe for condensed water drain with clipping accessories complete |
| 37 | 2.5 Sqmm 3 core round cable for AC connecting indoor/outdoor unit |
| 38 | Supply & fixing of 100 amp 4 pole manual vhange over complete in all respect |
| 39 | Supplying and fixing 63 A rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. D.S.R. 2.13.2 |
| 40 | Supply of AC 300mm Sweep, 230/250 Volts, 50 Hz exhaust fan (Light Duty) with blades,cover etc. complete as required |
| 41 | Supply and fixing of single Light wall bracket with opal glasspaint finishing upto 6 watt LED complete in all respect. |
| 42 | Supply of LED Tube Light with batten suitable for up to 1 X 10 watt LED tube light fitting including tube on Surface complete in all respect.(2ft) CAT- AAA |
| 43 | Supply of water tight oblong 10 Watt LED bulk head luminaire having die cast housing with driver set confirming to IP 65 and above Protection.Complete in all respect. |
| 44 | Dismantling and safe removal of old electrical installations from the Inspection House, including removal of wiring, fixtures, fittings and accessories, stacking at site, and restoration/repair of disturbed surfaces, complete in all respects as required. |
| 45 | All dismantled serviceable and unserviceable materials such as cables, fixtures, switchgear, conduits etc. shall be the property of the department and shall be deposited in departmental store or adjusted at assessed scrap value as directed by the Engineer-in-Charge. Please Enable Macros to View BoQ information |