| 1 | Supply of Equipment and accessories |
| 2 | 33 kV, 31.5 kA, 2000A, Vacuum Gang operated Circuit Breaker complete with mounting structure and all accessories including Terminal connectors |
| 3 | 33 kV, 31.5 kA, 1250A motorised isolators with single Earth Switch complete with all fittings and accessories including Terminal connectors as per specification |
| 4 | 33kV, 31.5 kA, 1250A motorised isolators without Earth Switch complete with all fittings and accessories including Terminal connectors as per specification. |
| 5 | 33kV, 400-200/1-1A, 2-Core Single Phase CT complete with all fittings and accessories including Terminal connectors and marshalling box as required(0.2S-5P20 Class, live tank type) as per specification |
| 6 | 30 kV, 10 kA, Class-2 station class lightning arrester and surge monitor complete with all fitting and accessories including terminal connectors and base insulator as per specification |
| 7 | 33 kV, 8 KN post insulator with all fitting including terminal connectors as per specification (creepage dist,- 31 mm/kV) |
| 8 | Industrial grade Air Conditioner as per specification |
| 9 | Supply of Bus and outgoing bay Steel Structures except equipment mounting structures (Columns) |
| 10 | Column Type C7 (2 Nos) (430.53 Kgs/Column) |
| 11 | Column Type C5 (1 Nos) (897.14 Kgs/Column) |
| 12 | Supply of Bus and outgoing bay Steel Structures except equipment mounting structures (Beams) |
| 13 | Beam Type B7 (1 Nos) (603.90 Kgs/Beam) |
| 14 | Beam Type B6 (1 Nos) (603.90 Kgs/Beam) |
| 15 | Tower Bolts & Nuts |
| 16 | Foundation Bolts & Nuts |
| 17 | Mounting Structures with mounting & foundation bolts as per drawing. |
| 18 | 33kV Motorised isolators without Earth Switch |
| 19 | 33kV CT |
| 20 | 33kV LA |
| 21 | 33kV PI |
| 22 | 33kV Motorised isolators with Earth Switch |
| 23 | CRP & SAS |
| 24 | 33kV Feeder Control and Relay Panel (Simplex Type) suitable for integration to existing ALSTOM make SAS |
| 25 | Bay level Managed Ethernet switch, rack mounting type in panel with suitable OF PATCH cable of sufficient length for SAS Integration |
| 26 | SAMAST compliant ABT energy meter including installation |
| 27 | OFC Patch Cord: ST-ST |
| 28 | Insulator strings, Clamps & Connectors (UPG, T Etc.) with complete fittings |
| 29 | UPG clamp for terminal connector (Panther to Panther) |
| 30 | 4 Disc tension insulator strings complete with all hardware fittings, clamps etc. for 33 kV bus of twin ACSR panther |
| 31 | Spacer clamps(panther) |
| 32 | T clamps for connection to 33 kV Bus(Twin panther to panther) |
| 33 | Armoured Control Cable(Copper) |
| 34 | a) 4Cx2.5 sqmm |
| 35 | b) 7CX1.5 sqmm |
| 36 | d) 19CX 1.5 sqmm |
| 37 | Armoured Power Cable(Aluminium) |
| 38 | a)2Cx6 sqmm |
| 39 | b) 4Cx16 sqmm |
| 40 | c) 3.5 Cx 35 sqmm |
| 41 | ACSR Panther Conductor |
| 42 | Earthmat Extension and grounding of equipments |
| 43 | Main earth mat (65x12 GI flat) |
| 44 | 40mm dia, 3 m long MS rod Earth Electrode |
| 45 | LED flood lights(60W) for switchyard illumination, including fitting and fixing |
| 46 | Supply of AC Marshalling Kiosk including construction of foundation, installation and cable foundation.1. 2No 63A, 4P (Incomer)2. 3No 25A, 4P (Outgoing)3. 8No 16A, 4P (Outgoing)4. 8No 10A, 4P (Outgoing)5. 5No 10A, 2P (Outgoing) |
| 47 | Mandatory Spares |
| 48 | Operating Mechanism for 33kV VCB |
| 49 | Trip Coil for 33kV VCB |
| 50 | Closing Coil for 33kV VCB |
| 51 | Spring charging Motor for 33kV VCB |
| 52 | 33kV, 31.5 kA, 1250A Isolators female/fixed contact (entire assembly) |
| 53 | 33kV, 31.5 kA, 1250A Isolators male/moving contact (entire assembly) |
| 54 | 33kV, 400-200/1-1A, 2-Core Single Phase CT (0.2S-5P20 class, live tank type) as per specification |
| 55 | 33kV Lightning Arrester |
| 56 | Numerical Backup Relay as per the required specifications |
| 57 | Master trip Relay as per the required specifications |
| 58 | Bay control unit as per the required specifications |
| 59 | OFC Patch Cord: ST-ST |
| 60 | Clamps & Terminal connectors |
| 61 | CT Terminal Clamp (Panther) |
| 62 | LA Clamp (Panther) |
| 63 | Isolator clamp (Panther) |
| 64 | CB Terminal connector (Panther) |
| 65 | Supply of Equipment and accessories |
| 66 | 33 kV, 31.5 kA, 2000A, Vacuum Gang operated Circuit Breaker complete with mounting structure and all accessories including Terminal connectors |
| 67 | 33 kV, 31.5 kA, 1250A motorised isolators with single Earth Switch complete with all fittings and accessories including Terminal connectors as per specification |
| 68 | 33kV, 31.5 kA, 1250A motorised isolators without Earth Switch complete with all fittings and accessories including Terminal connectors as per specification. |
| 69 | 33kV, 400-200/1-1A, 2-Core Single Phase CT complete with all fittings and accessories including Terminal connectors and marshalling box as required(0.2S-5P20 Class, live tank type) as per specification |
| 70 | 30 kV, 10 kA, Class-2 station class lightning arrester and surge monitor complete with all fitting and accessories including terminal connectors and base insulator as per specification |
| 71 | 33 kV, 8 KN post insulator with all fitting including terminal connectors as per specification (creepage dist,- 31 mm/kV) |
| 72 | Industrial grade Air Conditioner as per specification |
| 73 | Supply of Bus and outgoing bay Steel Structures except equipment mounting structures (Columns) |
| 74 | Column Type C7 (2 Nos) (430.53 Kgs/Column) |
| 75 | Column Type C5 (1 Nos) (897.14 Kgs/Column) |
| 76 | Supply of Bus and outgoing bay Steel Structures except equipment mounting structures (Beams) |
| 77 | Beam Type B7 (1 Nos) (603.90 Kgs/Beam) |
| 78 | Beam Type B6 (1 Nos) (603.90 Kgs/Beam) |
| 79 | Tower Bolts & Nuts |
| 80 | Foundation Bolts & Nuts |
| 81 | Mounting Structures with mounting & foundation bolts as per drawing. |
| 82 | 33kV Motorised isolators without Earth Switch |
| 83 | 33kV CT |
| 84 | 33kV LA |
| 85 | 33kV PI |
| 86 | 33kV Motorised isolators with Earth Switch |
| 87 | CRP & SAS |
| 88 | 33kV Feeder Control and Relay Panel (Simplex Type) suitable for integration to existing ALSTOM make SAS |
| 89 | Bay level Managed Ethernet switch, rack mounting type in panel with suitable OF PATCH cable of sufficient length for SAS Integration |
| 90 | SAMAST compliant ABT energy meter including installation |
| 91 | OFC Patch Cord: ST-ST |
| 92 | Insulator strings, Clamps & Connectors (UPG, T Etc.) with complete fittings |
| 93 | UPG clamp for terminal connector (Panther to Panther) |
| 94 | 4 Disc tension insulator strings complete with all hardware fittings, clamps etc. for 33 kV bus of twin ACSR panther |
| 95 | Spacer clamps(panther) |
| 96 | T clamps for connection to 33 kV Bus(Twin panther to panther) |
| 97 | Armoured Control Cable(Copper) |
| 98 | a) 4Cx2.5 sqmm |
| 99 | b) 7CX1.5 sqmm |
| 100 | d) 19CX 1.5 sqmm |
| 101 | Armoured Power Cable(Aluminium) |
| 102 | a)2Cx6 sqmm |
| 103 | b) 4Cx16 sqmm |
| 104 | c) 3.5 Cx 35 sqmm |
| 105 | ACSR Panther Conductor |
| 106 | Earthmat Extension and grounding of equipments |
| 107 | Main earth mat (65x12 GI flat) |
| 108 | 40mm dia, 3 m long MS rod Earth Electrode |
| 109 | LED flood lights(60W) for switchyard illumination, including fitting and fixing |
| 110 | Supply of AC Marshalling Kiosk including construction of foundation, installation and cable foundation.1. 2No 63A, 4P (Incomer)2. 3No 25A, 4P (Outgoing)3. 8No 16A, 4P (Outgoing)4. 8No 10A, 4P (Outgoing)5. 5No 10A, 2P (Outgoing) |
| 111 | Mandatory Spares |
| 112 | Operating Mechanism for 33kV VCB |
| 113 | Trip Coil for 33kV VCB |
| 114 | Closing Coil for 33kV VCB |
| 115 | Spring charging Motor for 33kV VCB |
| 116 | 33kV, 31.5 kA, 1250A Isolators female/fixed contact (entire assembly) |
| 117 | 33kV, 31.5 kA, 1250A Isolators male/moving contact (entire assembly) |
| 118 | 33kV, 400-200/1-1A, 2-Core Single Phase CT (0.2S-5P20 class, live tank type) as per specification |
| 119 | 33kV Lightning Arrester |
| 120 | Numerical Backup Relay as per the required specifications |
| 121 | Master trip Relay as per the required specifications |
| 122 | Bay control unit as per the required specifications |
| 123 | OFC Patch Cord: ST-ST |
| 124 | Clamps & Terminal connectors |
| 125 | CT Terminal Clamp (Panther) |
| 126 | LA Clamp (Panther) |
| 127 | Isolator clamp (Panther) |
| 128 | CB Terminal connector (Panther) |
| 129 | Erection of Mounting structure as required, labour cost etc. and structure earthing |
| 130 | 33 kV VCB |
| 131 | 33 kV CT |
| 132 | 33kV Isolator (one with earth switch & one without earth switch) |
| 133 | 33 kV LA |
| 134 | 33 kV PI |
| 135 | Erection of Bus and outgoing bay Steel Structures except equipment mounting structures(Columns) |
| 136 | Column Type C7 (2 Nos) (430.53 Kgs/Column) |
| 137 | Column Type C5 (1 Nos) (897.14 Kgs/Column) |
| 138 | Erection of Bus and outgoing bay Steel Structures except equipment mounting structures(Beams) |
| 139 | Beam Type B7 (1 Nos) (603.90 Kgs/Beam) |
| 140 | Beam Type B6 (1 Nos) (603.90 Kgs/Beam) |
| 141 | Tower Bolts & Nuts |
| 142 | Foundation Bolts & Nuts |
| 143 | Erection, testing and comissioning including laying of control cables and equipments earthing as required |
| 144 | 33 kV VCB |
| 145 | 33 kV CT |
| 146 | 33kV Isolator (one with earth switch & one without earth switch) |
| 147 | 33 kV LA |
| 148 | 33 kV PI |
| 149 | Instalation of earthing system |
| 150 | Instalation of earth electrode for LA with test links including construction of covered earth pad(Note : Considered For other structures also) |
| 151 | Construction of extended earth mat using GI flats and connection to risers for equipment earthing as directed |
| 152 | Instalation and commissioning of the C&R panel |
| 153 | Erection, testing and commissioning of C&R panel and integration with existing ALSTOM(GE) make SAS |
| 154 | Supply and installation of ancillary items for AC (copper refregerents pipe, PVC drain pipie, wiring etc. As required. |
| 155 | Stringing of 33kV ACSR panther twin bus conductors including all fittings and necessary arrangements. |
| 156 | Construction of Foundation including supply of all foundation materials and labor as required for Equipment structures |
| 157 | Construction of Foundation including supply of all foundation materials and labor as required for Post Insulator. |
| 158 | Construction of Foundation including supply of all foundation materials and labor as required for Lighting arrestor. |
| 159 | Construction of Foundation including supply of all foundation materials and labor as required for current transformer. |
| 160 | Construction of Foundation including supply of all foundation materials and labor as required for Isolator with earth switch. |
| 161 | Construction of Foundation including supply of all foundation materials and labor as required for Isolator without earth switch. |
| 162 | Construction of Foundation including supply of all foundation materials and labor as required for Circuit Breaker . |
| 163 | Construction of Foundation including supply of all foundation materials and labor as required for Lattice Steel Column |
| 164 | Construction of cable trench including supply of all foundation materials and labour as required |
| 165 | (i) Main cable trench, 1000 x 600 |
| 166 | (ii) Type D |
| 167 | Construction of 80 mm thick PCC in 1:2:4 mix proportion including 80 mm graveling including supply of all foundation materials and labour as required |
| 168 | Construction of 3.5 m wide Approach road with side drain at both side including supply of all foundation materials and labour as required as per specification Please Enable Macros to View BoQ information |