| 1 | Supplying, erecting, testing and commissioning ofKirloskar make horizontal split case pump 50 x 65mm suction/delivery, suitable for head of 35 meters and discharge of 200 cu.m./hr coupled to Kirloskar make 40HP/30KW foot mounted on separate base plate duly aligned inclusive of foundation. (Foundationwork includes excavation, rubble packing, P. C. C.,centering and plain concrete 1:11/2:3) and accessories like coupling, coupling guard, foundation bolts, pressure guage - 3Nos., etc. and air lock removal valve - 2 Nos. as per direction of engineer incharge. |
| 2 | 2 Supplying, installing,testing and commissioning of indoor type L.T. main panel board suitable for 40HP motor pumpsets - 2 Nos. with all accessories, suitable provision for three phase departmental energy meter and sealing arrangement. The panel board is flush front compartmentalized, floor mounted to allow cable entry from bottom, dust and vermin proof complete with interconnections, Bus bar wiring doors and covers fully gasketed. The panel board should be derusted and painted powder coating (7tank process) and oven process. Panel board made up of 16 SWG CRCA sheets and mounted on suitable size MS angle frame and installed on the floor firmly using cement concrete or anchor fastened not bolts with following accessories: a.Main incomer MCCB, 3pole 200 Amps 25 KA - 3Nos. b. Main R.Y.B. indication lamps LED - 1No. c. Voltmeter 0 - 500V- 1 No. d. Voltmeter selector switch - 1 No. e. Ammeter range 0-200 amps CT operated - 1 No.f. Ammeter selector switch - 1 No. g. CTs for ammeter Ratio 200/5A - 3 Nos. h. Fully automatic Star/Delta starter for 40 HP motor - 2Nos. i. MCCB for starter 150 Amps 3pole - 2 Nos. j. ON/OFF push botton cum indicator - 4 Nos. k. Trip indication - 2 Nos. l. Single phase preventor - 2 Nos. m. Over load relay 30-50 amps - 2 Nos. n. Power capacitor 10 KVAR 415V- 2 Nos. Each |
| 3 | Removal of existing panel board and two pump and two motor including disconnection of powersupply. Removal of existing suction and discharge pipe and demolition of foundation concrete. |
| 4 | Armoured PVC/XLPE 1100 V cable 3 1/2 core 50 sq.mm aluminium. |
| 5 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with CI /RCC cover having locking/Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x 1.0 x 3.0 mtrs(min) and disposal of excavated soil. c)Watering GI pipe 20mm Class B with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs (min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe.g) watering arrangement(plumbing will be paid seperately ).;(a) In soily strata. |
| 6 | Extra for using salt and charcoal for GI or copper plate earth electrode as required( 96 Kgs of Charcoal and 5 Kgs of Salt) |
| 7 | Supplying and laying 8 SWG copper wire at 0.5 mbelow ground level for conductor earth electrodeincluding soldering etc. as required. |
| 8 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(2) 3 1/2 x 35 Sq.mm. |
| 9 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(4) 3 1/2 x 70 Sq.mm. |
| 10 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq. mm direct in ground including excavation in the form of a trench as perCable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run(the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15cm crown on the top complete as required.;(a In soily strata. |
| 11 | Supplying stacking at site and conveying hoistinglaying in position to correct line and level and linking joints of MS specials. fabricated from MS plate including cutting bending welding procurement of plates gas cutting to required size rolling tack welding assembling in suitable length to form special welding on automatic machine and forming V edge on both ends of special as required hydraulic pressure test at factory to the required test pressure conforming to IS : 3589-1991 including freight etc. complete;With 10 mm -12 mm thick plate;Tees bends reducers. |
| 12 | Supplying stacking at site and conveying hoisting laying in position to correct line and level and linking joints of MS specials. fabricated from MS plate including cutting bending welding procurement of plates gas cutting to required size rolling tack welding assembling in suitable length to form special welding on automatic machine and forming V edge on both ends of special as required hydraulic pressure test at factory to the required test pressure conforming to IS : 3589-1991 including freight etc. complete;With 25 mm thick Plate;Flanges. |
| 13 | Supplying at store or site of work including freight transit insurance carting loading unloading stacking etc. Ductile Iron double flanged manually operated Sluice valve generally confirming to IS 14846-2000 non rising spindle type (soft seated) resilient seated with Body Bonnet of Ductile Iron of grade GGG40 or SG 400/12 400/15 500/7 or equivalent grade as per IS 3896 part 2-1985 and subsequent revisions Wedge fully rubber lined with food grade EPDM( WRAS approved) and seals of NBR spindle stem SS/AISI 410 and having glandless operation. The valve should be vacuum tight 100% leak proof with face to face dimensions as per IS14846-2000 or BS 5163- 89 or DIN 3202-F4. The valves shuld be coated with electrostatic Powder/Epoxy Coating on both inside and outsideminimum 250 microns thickness of blue color RAL5017/5005 suitable for drinking waterand shall have pocket less body passage. The flangesshall be Drilled as per IS:1538 with latest amendments. The valve shall be supplied with Hand Wheel for operation (by-pass and gear arrangements for sizes above 400mm dia) and relevant Test & Guarantee certificates. TYPE P.N. 1.6 (Class A);Nominal Diameter in mm;80. |
| 14 | Supplying at store or site of work including railway freight carting loading unloading stacking etc. C.I. Reflux valve conforming to IS:5312 part-I. Valve double flanged ends without bypass arrangements and drilled to IS:1538 part IV & VI bearing ISI Certificate mark TYPE P.N. 1.6 (Class B);Dia in mm;80 Please Enable Macros to View BoQ information |