| 1 | Punjabi Bagh Underpass lightingSupplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 2 | 150 Watt |
| 3 | Supplying & Fixing of Outdoor Weatherproof Junction Box,(Size : 28cmX 21cm X 11cm) White Colour Fiber Reinforced Plastic including terminal for connection of incoming/outgoing cable and 6A SPMCB and mounting on Street light pole at suitable height with the help of clamp |
| 4 | Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade |
| 5 | 3 x 10 Sqmm |
| 6 | 4 x 25 Sqmm |
| 7 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface/ Pole to Pole etc as required. |
| 8 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 9 | Fabricating Supplying, Installation, Testing and Commissioning of floor mounted, Double door Feeder Pillar having 300amp, 4 strip aluminiuml busbar with heat shrikable coloured sleeves and DMC/SMC busbar supports etc made out of 2mm thick CRCA Sheet, mounting on angle iron frame work with angle iron of size 50 mm X 50 mm X 6 mm (NS) 90 cm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 (1 cement 2 sand :4 stone aggregate 20 mm), dust and vermin proof, duly compact with Al. bus bar suitable as per incomer, duly powder coated paint of approved colour and shade providing earth stud at both end, louvers and mesh on both side of panel board for ventilation purpose i/c connection and interconnection, earthing complete etc. as reqd. having following accessories. (Size of each panel is 0.4 Sqmtr)a) 63 Amp. 1 6 KA MCCB 3 pole- 1 Nos. (With 100 Amp. frame size)b) Voltmeter 0-500 volt 96 sqmm flush type with selector switch.c) Ammeter 0-100 Amp 96 sqmm flush type with selector switch & 100/5 Amp ratio CTs. d) LED type indicating lamp RYB Phase-- 3 Nos. e Power contactor 3 pole , 30 A, 415 volt (MNX-40/similar make).f) Astro timer- 01 No. g) Danger notic plate. |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 11 | 4 X 25 sg. mm (28mm) |
| 12 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 13 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required |
| 14 | Peeragarhi UnderdeckSupplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 15 | 150 Watt |
| 16 | Supplying & Fixing of Outdoor Weatherproof Junction Box,(Size : 28cmX 21cm X 11cm) White Colour Fiber Reinforced Plastic including terminal for connection of incoming/outgoing cable and 6A SPMCB and mounting on Street light pole at suitable height with the help of clamp |
| 17 | Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade |
| 18 | 3 x 10 Sqmm |
| 19 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface/ Pole to Pole etc as required. |
| 20 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 21 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 22 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required |
| 23 | Bhera Enclave UnderpassSupplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 24 | 150 Watt |
| 25 | Supplying & Fixing of Outdoor Weatherproof Junction Box,(Size : 28cmX 21cm X 11cm) White Colour Fiber Reinforced Plastic including terminal for connection of incoming/outgoing cable and 6A SPMCB and mounting on Street light pole at suitable height with the help of clamp |
| 26 | Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade |
| 27 | 3 x 10 Sqmm |
| 28 | 4 x 25 Sqmm |
| 29 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface/ Pole to Pole etc as required. |
| 30 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 31 | Fabricating Supplying, Installation, Testing and Commissioning of floor mounted, Double door Feeder Pillar having 300amp, 4 strip aluminiuml busbar with heat shrikable coloured sleeves and DMC/SMC busbar supports etc made out of 2mm thick CRCA Sheet, mounting on angle iron frame work with angle iron of size 50 mm X 50 mm X 6 mm (NS) 90 cm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 (1 cement 2 sand :4 stone aggregate 20 mm), dust and vermin proof, duly compact with Al. bus bar suitable as per incomer, duly powder coated paint of approved colour and shade providing earth stud at both end, louvers and mesh on both side of panel board for ventilation purpose i/c connection and interconnection, earthing complete etc. as reqd. having following accessories. (Size of each panel is 0.4 Sqmtr)a) 63 Amp. 1 6 KA MCCB 3 pole- 1 Nos. (With 100 Amp. frame size)b) Voltmeter 0-500 volt 96 sqmm flush type with selector switch.c) Ammeter 0-100 Amp 96 sqmm flush type with selector switch & 100/5 Amp ratio CTs. d) LED type indicating lamp RYB Phase-- 3 Nos. e Power contactor 3 pole , 30 A, 415 volt (MNX-40/similar make).f) Astro timer- 01 No. g) Danger notic plate. |
| 32 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 33 | 4 X 25 sg. mm (28mm) |
| 34 | Fabricating, Supplying & Fixing wire mesh protection frame work made out of 40 mm x 6 mm thick angle & \\"T\\" strengthened with intermediate members of MS flat iron of size 30 mm x 5 mm thick welded at a distance of 30 cm horizontally & vertically and duly welded with wire mesh of size 75 mm x 25 mm made with 6 SWG wire mash of size 75 mm x 25 mm made with 6 SWG wire on all sides and top i/c providing and fixing of double door gate with double locking arrangement ( Two Nos. sliding bolts and One No go down lock) having 0.5 mtr. long legs of 40 mm x 40 mm x 6 mm thick angle iron, duly grouted in cement concrete foundation ration 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate), up to suitable depth painting with one coat of red oxide & Two coats of synthetic enamel paint of approval colour and shade etc. complete as reqd. |
| 35 | Punjabi Bagh Club Road Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade |
| 36 | 4 x 25 Sqmm |
| 37 | 3 x 6 Sqmm |
| 38 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 39 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required |
| 40 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.. |
| 41 | Supplying and fixing of 40 Amp terminal block suitable for 25sq.mm conductor -4 nos. & shorting links – 5nos. on DIN channel i/c pdg. and fixing DIN channel of suitable length – 2 nos. on the existing laminated sheet.a) Supplying and fixing 6 Amp, SPMCB, ‘C’ Characteristics Curve - 2 No. Earth stud-2Nos. welded at suitable height two nos. washers, springs washers & nuts.b) Cable support clamp suitable for 4 Nos of 4x25 sqmm cable.c) The nuts and bolts shall be welded.. |
| 42 | Supplying & Fixing of following size Aluminium thimble with proper connection and PVS Tape etc as required. |
| 43 | 16/25 Sqmm |
| 44 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 45 | Upto 35 sq. mm |
| 46 | Dismantiling of existing damaged following items including credit back to agency as an where basic |
| 47 | Assorted size cable |
| 48 | Assorted Watt Street/Flood LED fittings |
| 49 | Damaged panels Please Enable Macros to View BoQ information |