| 1 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size. R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required. Cooling Only |
| 2 | 3.8 TR BEE 5 Star Rating |
| 3 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 4 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 5 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 6 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 7 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 8 | Supplying and Laying of XLPE insulated and PVC round sheathed multicore industrial flexible cable for voltage grade upto 1100V of following size In HUME/ DWC Pipe/ Metal Pipe/ RCC Pipe etc. as required. |
| 9 | 4X10 Sq. mm. |
| 10 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 11 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 12 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 13 | 4 way (4 + 12), Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Single pole |
| 16 | Triple pole |
| 17 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 18 | Supplying and Laying of XLPE insulated and PVC sheathed aluminium conductor armoured Power Cable of 1.1 KV grade of following size on wall surface as required. |
| 19 | 3.5X35 Sq. mm. |
| 20 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. Please Enable Macros to View BoQ information |