Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | `Supplying, Installing, testing and Commissioning of Electrically driven horizontal split casing pump and motor sets complete with Impeller made of SS CF8M, Shaft made of Stainless Steel 410 grade, Efficiency- 85% minimum alongwith Base frame, coupling and Coupling Guard of each pump, foundation bolt, suction/discharge flange and Electrical Induction Motors 1500 RPM Horizontal foot mounted LT (415V) motor with specifications of TEFC (Total enclosed Fan cooled), space heater, BTD (Bearing Temp. Detector) and RTD (Resistance Temp. Detector) complete in all respect and all civil work related to installation of pump and motor (foundation etc) along with pressure Gauges on suction and discharge as per site requirement integrating with existing structure. complete in all respect to the entire satisfaction of Engineer-in-charge for following Duty points. Make of Pump : WPIL, Kirloskar, Grundfos,Darling,KSb,CRI,WILO MandP,Crompton GreavesMate of Motor : Kirloskar, Siemens, ABB ,Crompton Greaves,BHEL,Bharat Bijlee, Toshiba- Mistubishi, Marathon `1332 m3/Hr @ 45 Mtr Head, minimum 300 HP |
| 2 | `Supplying, Laying, Stringing out, Jointing, Cutting, making connection with existing line at both ends and testing of spirally welded M.S. pipe to be made of 12mm thick MS Sheet from SAIL/Jindal/TATA/Welspun only and specials made up of M.S. plate of minimum 12mm thickness as per IS:3589 , PU coating outside and food grade epoxy inside coating as per relevant specification and IS code and laying the same including excavation, welding, cutting of the pipe etc. all material and labour as per requirement complete in all respect as per direction and satisfaction of Engineer-in-Charge...`500mm i/d MS Pipe of 12mm Thick (Food Grade Epoxy inside) |
| 3 | `Providing, Fixing, Testing, Commissioning of Clamp-on Ultrasonic Flow Meter totaliser with flow transmitter/RTU conforming to IS 2147/ IP 65 with multi stand Copper conductor cable, 1.5 sqmm with PVC screened complete in all respect as per direction and entire satisfaction of Engineer-in-Charge. Make : George Fischer,Siemens, Tallis, Krohne-Marshall,EndressandHauser, Bermad India `400mm i/d to 1500 mm i/d (1Nos Inlet and 1 Nos Outlet) |
| 4 | `Providing, fixing, testing and commissioning of vacuum pump of minimum 5 HP discharge capacity 550 LPM conforming to BIS specifications complete in all respect but for application as vacuum pumps for priming purpose)Item similar to H.S.R 20.115.4 ` |
| 5 | `Supplying, Installing, Commissioning and Testing of Dewatering pumps (5 HP) conforming to BIS specifications suitable to Sp. gravity 1.1 with separate 100 mm i/d GI Piping (Heavy C Class) for discharge of and amp: panel board etc complete in all respect. Make : Crompton, Kirloskar etc.` |
| 6 | `Providing and fixing of D.I. Sluice valves of PN-1.6 rating with Actuator confirming to IS:14846-DIN- 3352 / BS-5163 bldg-IS-1865 G-400/1500/7 (with latest revision) specifications sluice valves 300mm and above to be provided with back thrust bearing and spur gear arrangment for easy operation, along with contingent material required for their fixing with pipes and specials laid in trenches complete in all respect to the entire satisfaction of the Engineer-in-Charge. 500 MM I/D actuator operated sluice valve resilient seated.Make: VAG, IVC NASHIK` |
| 7 | `Providing and Fixing of MS and Flanged specials etc.(painted black) as required as per IS specifications complete in all respects as per directions of Engineer in Charge. All Specials to factory made as per requirement at site.` |
| 8 | Providing, Fixing, Testing, Commissioning of Gauges, compound and Pressure gauges 200 mm dia Guage upto 10 kg pressure. With GI valve, nipple etc. complete in all respect as per direction and entire satisfaction of Engineer-in-Charge.Make: Bells Control, Frobes Marshal, H.Guru, Manometer India Ltd. |
| 9 | Providing , Installation, testing and commissioning of MS mechanical dismentling joint 500 mm PN 1.6 as per IS 9523 complete in all respect to the satisfaction of Engineer in Charge. 500 MM I/D |
| 10 | Supply, installation, testing and commissioning of Main LT Panel as per IS61439/ IEC61439 consisting of 3 Nos incomer ACB 1250Amp, 4 Nos outgoing ACB (800Amp) with motor protection relay , 1 Nos Bus-Coupler 1250 Amp, and MCCB and TPN as neccessary as per the complete satisfaction of Engineer-in-charge for all lighting, dewatering, vaccum pumps and all other miscellaneous load LT-Motors Bus-Bars of enough capacity to handle above load , with provision for cables from top and bottom ,digital ammeter and voltmeter for each ACB, RYB indicator, ON/OFF indicator, complete in all respect including connection/integration with existing panel/system with required accessories/bus-bars complete with all material and labour to the entire satisfaction of Engineer in charge. ( 3 no incomer- 2 for transformer , 1 for D.G)(4 NO outgoing- 3 for motors and 1 no for extra load and lightning etc.Make: Schneider Electric, BCH Electric Limited, Waaree Energies. |
| 11 | Supply, installation, testing and commissioning of SET of 11KV- 630 Amp VCB Panel complete with protection relays, 1 IC/3 OG VCB PANEL to feed transformers connection/integration with existing panel/system with required accessories/bus-bars complete with all material and labour to the entire satisfaction of Engineer in charge(1 IC for main and 3 outgoing for 2 transformer and 1 no for extra or standby in future).Make: Siemens, Schneider Electric, ABB, CG power. |
| 12 | Supply, installation, testing and commissioning of APFC Panel 300 KVAr with Heavy Duty Capacitors and detuned reactors, 12 step complete to the satisfaction of Engineer-in-Charge.Make: E-Abel, Brilltech Engineers Pvt Ltd, SMA Power control Pvt Ltd, BCH Electric, Isotech. |
| 13 | Providing, installation , testing and commissioning of PLC SCADA system complete in all respect to the satisfaction of engineer in charge at Boosting station Gawal Pahari. Make: SIEMENS, Schneider Electric, ABB.. |
| 14 | Supply installation testing and commissioning of 120 watt LED light with IP 66 rating in die cast aluminium alloy housing, SMPS based phase to phase protection, overload protection, surge voltage protection upto 10KV with external SPD and other safety and test as per IS 15885 to be fixed on electric pole including cost of 32 mm dia 1.5 meter long bracket, M.S clamps, nut bolts and other petty material for complete commissioning in all respect to the satisfaction of engineer in charge. Make :- Bajaj, Havells, Philips, Crompton etc... |
| 15 | Providing and Fixing of 50 Watt 4 ft LED Tubelight complete in all respect to the satisfaction of engineer in charge. Make :- Bajaj, Havells, Philips, Crompton etc. |
| 16 | Operation and Maintenance of 20 MLD capacity boosting station at Gawal Pahari, Gurugram (For 36 months including Gawal Pahari area upto tail end excluding maintenance of pumping mechinery installed at booster) |
| 17 | Providing, testing, installation and commissioning of soft starter suitable for minimum 225 KW LT induction motor with all protection relays and MCCB complete in all respect as per latest standards and specifications complete to the entire satisfaction of engineer in charge. Make: Siemens, ABB, Schneider.1 No. Panel with soft starter for each pump set of 1332 m3/Hr @ 45m and 415 V 3P Induction Motor . |
| 18 | [10.1.1.1]Providing and laying of base course of floors consisting of 100 mm thick cement 1:8:16 and 100 mm sand or stone filling. 1.1. Re-compacting excavated soil in plinth under floors, including watering, ramming, consolidating and dressing complete. [Through Rate] |
| 19 | [10.1]Providing and laying of base course of floors consisting of 100 mm thick cement 1:8:16 and 100 mm sand or stone filling. [Through Rate] |
| 20 | [10.37.1]Providing and fixing of Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 1. 25 mm thick [Through Rate] |
| 21 | [10.49.1]Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : 1. Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. [Through Rate] |
| 22 | [10.61]Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including pointing the joints with white cement and matching pigments etc., complete. [Through Rate] |
| 23 | [10.62]Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. [Through Rate] |
| 24 | [10.63.2]Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. 2. Size of Tile 600x600 mm [Through Rate] |
| 25 | [10.67.2]Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours and shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement and matching pigments etc. complete. 2. Size of Tile 600x600 mm [Through Rate] |
| 26 | [10.68]Providing and fixing glazed screen printed border tile 75mm wide having thickness 5mm, of approved quality and make, in all shades, design and prints, in dado, over 12mm thick bed of cement mortar 1:3 (1 Cement : 3 Coarse sand) and jointing with grey cement slurry @ 3.3 kg/sqm including pointing with white cement mixed with pigment of matching shade, all complete as approved by Engineer - in - Charge [Through Rate] |
| 27 | [11.26.1]Pointing on tile brick work with cement mortar 1:3 (1 cement : 3 fine sand): 1. Flush/ Ruled/ Struck or weathered pointing [Through Rate] |
| 28 | [11.4.2]10 mm thick cement plaster 2. 1:3 (1 cement: 3 fine sand) [Through Rate] |
| 29 | [11.5.3]12 mm cement plaster of mix : 3. 1:4 (1 cement: 4 fine sand) [Through Rate] |
| 30 | [11.60]Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. [Through Rate] |
| 31 | [11.63]Distempering with dry distemper of approved brand and manufacture (two or more coats) of required shade on new work, over and including water thinnable priming coat to give an even shade. [Through Rate] |
| 32 | [11.71.1]Wall painting on a cement plaster surface with acrylic emulsion paint of approved brand and manufacture to give an even shade : 1. Two or more coats on new work [Through Rate] |
| 33 | [11.78]Painting two coats excluding priming coat with synthetic enamel paint in all shades on new wood work or metallic or plastered or concrete surfaces to give an even shade. [Through Rate] |
| 34 | [11.82.1]Painting the wooden / metal surface with synthetic enamel paint of approved brand and manufacture to give an even shade : 1. Two or more coats on new work [Through Rate] |
| 35 | [12.103.1]Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. 1. Single rubber stopper [Through Rate] |
| 36 | [12.25.1.1]Providing and fixing 25 mm thick shutters for cup board etc. : 1.1. Panelled or panelled & glazed shutters : Second class teak wood including ISI marked anodised aluminium butt hinges with necessary screws [Through Rate] |
| 37 | [12.37.1]Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 1. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws [Through Rate] |
| 38 | [12.50.1]Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. 1. Fixed to steel windows by welding [Through Rate] |
| 39 | [12.7.2.1]Providing and fixing panelled or panelled and glazed shutters for doors, windows and clerestory windows, including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer-in-charge. (Note:- Butt hinges and necessary screws shall be paid separately) 2.1. Kiln seasoned and chemically treated Hollock wood 35 mm thick shutters [Through Rate] |
| 40 | [12.79.2]Providing and fixing bright finished brass door latch with necessary screws etc. complete : 2. 250x16x5 mm [Through Rate] |
| 41 | [12.9.7.1]Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick : 7.1. Float glass panes 4 mm thick glass pane (weight not less than 10kg/sqm). [Through Rate] |
| 42 | [12.98.1]Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 1. 300x16 mm [Through Rate] |
| 43 | [12.99.1]Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 1. 300x10 mm [Through Rate] |
| 44 | [13.21.1]Supply and fixing Windows frames (Chowkhats) including mullions consisting frame fabricated from sheet roll formed out of 1.2mm thick galvanized sheet as per IS:277 (Base steel as per IS 513) with zinc of 120 gm/sqm and Powder coated with pure Polyester powder up to 50 microns (as per approved colour), 3 Nos. 100mm butt - hinges 2mm thick, 6 Nos. 1.2mm thick CRCA electroplated stiffner, 6 Nos. M.S hold fast with split and tail welded to stiffner plate 200mm long, receiver for aldrop, weld less corner assembly with brackets and screws, M.S tie rod 50mm x 25mm to be fixed at bottom finished with powder coated total thickness of coating 0.6mm of approved shade, fixed in position including the cost of cement concrete for 1:2:4 for fixing lugs complete in all respects as per drawing, design, specification and entire satisfaction of Engineer-in-charge. 1. Door Frame of size 80mm x 50mm with 37mm wide single rebate for 35mm door shutter [Through Rate] |
| 45 | [13.22.1]Supply and fixing Windows frames (Chowkhats) including mullions consisting frame fabricated from sheet roll formed out of 0.58mm thick galvanized sheet (Base steel as per IS 513) with zinc of 120 gm/sqm steel sheet pre coated (as per approved colour) with Polyester paint of 12-16 microns thickness under coat of EPOXY primer and back coat with ALKYD backer of 5-7 microns, total sheet thickness with coating 0.58mm of approved shade, weld less corner assembly with brackets and screws, fixed in position by means of PVC and metal hold fastener with PVC cap complete in all respects as per drawing, design, specification and entire satisfaction of Engineer-in-charge. 1. Windows Outer frame of size 72mm x 55mm and central mullion 72mm x 50mm with Double rebate [Through Rate] |
| 46 | [13.23.1]Supply and fixing Windows frames (Chowkhats) including mullions consisting frame fabricated from sheet roll formed out of 0.58mm thick galvanized sheet (Base steel as per IS 513) with zinc of 120 gm/sqm steel sheet pre coated (as per approved colour) with Polyester paint of 12-16 microns thickness under coat of EPOXY primer and back coat with ALKYD backer of 5-7 microns, total sheet thickness with coating 0.58mm of approved shade, weld less corner assembly with brackets and screws, fixed in position by means of PVC and metal hold fastener with PVC cap complete in all respects as per drawing, design, specification and entire satisfaction of Engineer-in-charge 1. Glazed Windows shutter section 47mm x 20mm (Without Glass) [Through Rate] |
| 47 | [13.24.1]Providing and fixing glazing in door, window, ventilator shutters and partitions etc. complete as per the architectural drawings and the directions of engineer-in-charge. (Cost of Gasket / beading shall be paid as per respective item) 1. Float glass panes of 5.5mm thickness [Through Rate] |
| 48 | [13.27]Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. [Through Rate] |
| 49 | [13.42.1]Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. 1. M.S. tube [Through Rate] |
| 50 | [13.43]Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete. [Through Rate] |
| 51 | [13.44]Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. [Through Rate] |
| 52 | [20.11.10]Providing and fixing cast iron double flanged swing check type reflux (non return) valves PN-1.6 marked with IS:5312 including nuts and bolts marked with IS:1363, rubber sheet marked with IS:638 etc., carriage loading, unloading, stacking, handling, re-handling etc. Complete in all respect to the satisfaction of Engineer-in-charge 10. 500 mm i/d [Through Rate] |
| 53 | [20.114.1]Supplying erection, testing of fullyautomatic electric control panel board forT/Wells in Pump Chamber consisting ofMS sheet of thickness 14 gauge dulypainted box type floor mounted made ofangle Frame containing 1 no. fullyautomatic air brake starter suitable forMotor of the following capacity, Minswitch of suitable range with HRC fuse, 1no. volt meter (0 to 500 volts), 1 No.Amp. Meter of 0 to 100 amp. 3 sets ofindicating lamp capacitor of suitablecapacity and 1 no. single phase preventerswith the timer switch including wiring inpanel board and suitable electric energymeter wiring in Electric Control PanelBoard complete in all respect as perspecification given in Schedule No. II,Including MCB, suitable, Capacitor,Wooden Box etc as per siterequirement complete in all respect. 1. 10 HP Motor [Through Rate] |
| 54 | [20.15.3]Providing and fixing C.I. Kinetic air valves conforming to and marked with IS: 14845 including carriage, loading, unloading stacking, handling, re-handling etc., drilling, tapping, screwing in valves connections complete in all respects to the satisfaction of Engineer-in- Charge. 3. 150 mm i/d [Through Rate] |
| 55 | [20.53.10]Providing and fixing rubber sheet 3mm thick of best quality for jointing flanged pipes, specials etc. including making of holes etc. complete in all respects to the satisfaction of Engineer-in- Charge. 10. for pipe size 500mm i/d [Through Rate] |
| 56 | [20.53.6]Providing and fixing rubber sheet 3mm thick of best quality for jointing flanged pipes, specials etc. including making of holes etc. complete in all respects to the satisfaction of Engineer-in- Charge. 6. for pipe size 300mm i/d [Through Rate] |
| 57 | [20.68.2]Providing, lowering, laying in trenches, aligning, fixing in position and jointing at all level/depths Ductile Iron (DI) standard specials plain /flanged/ socketed confirming to IS9523-2000 with rubber ring (EPDM/SBR) joints such as tees, bends, tapers, caps etc. with in trenches in DI pipe line complete including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. 2. Above 300mm dia and up to 600mm dia [Through Rate] |
| 58 | [20.70.7]Supplying and fixing of bell mouth as per specifications of IS Code 1538 of 1993 including cost of jointing materials, excavation laying jointing refilling , making adequate supports of masonry/ concrete for delivery and suction pipe from bell mouth in the under structures complete in all respect to satisfaction of Engineer-in-charge. 7. 400 mm i/d [Through Rate] |
| 59 | [20.71.1]Supply, erection, testing of Ceiling fans IS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge 1. 48\\" (1200mm) [Through Rate] |
| 60 | [20.72]Supplying, errection, testing of Exhaust fan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structure confirming to latest IS specifications complete in all respect to satisfaction of Engineer-in-charge. [Through Rate] |
| 61 | [20.73.4]Supply and fixing of Gantry with chainpulley block (tested for 1.5 times the ratedcapacity) with travelling trolley ofappropriate lifting capacity as per IS code3177:1999 with up to date amendments forhandling of pumping sets capable ofmoving along the girders including cost ofsuitable sized RCC pillars to be provided inpump house complete in all respects as perdirections of Engineer-in-charge 4. 2.5 tonne capacity [Through Rate] |
| 62 | [20.76.17]Design, Supply and erection of transformer of standard make Required 25 KVA 11/0.433 KVA rating outdoor type 11 KVA V.C.B, panel, G.O. switch, H. Pole , H.T metering panel, APFC panel, battery charges, 11 KVA substation, entire cable network from G.O. switch to H.T metering equipment and from H.T metering to Transformer. From transformer to main to L.T, panel earthling, safety equipment, fenced enclosure for transformer, and any other contingent thereto complete in all respect as per approved make and directions of Engineer-in-charge as per respective capacity. 17. 1000 KVA [Through Rate] |
| 63 | [20.84]Providing and fixing of insulated rubber matting suitable for 11 KV installation 1 M x 2 M x 12 mm thick (IS code 15652-40091) as per specification complete and as per directions of Engineer-in-charge [Through Rate] |
| 64 | [20.86]Supply, erection, testing and commissioning of G.O. Switch two poles, with blade, pin 6 insulators operating handle with GI pipe 25 mm class B complete in all respects. [Through Rate] |
| 65 | [20.88]Supply, erection, testing and commissioning of CT meter of standard make with cubical meter box as per HVPNL specifications including 3 phase electrical meter 100/5 of standard make approved by HVPNL including CT/PT of suitable rating complete in all respect as per directions of Engineer-in-charge [Through Rate] |
| 66 | [20.89.14]`Designing, Supply and erection of DG set of capacity given below with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through a set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standard panel, making second incoming cable connection from transformer, outgoing cable connection from changeover / STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge.The rating should be at 1500 RPM.a) Diesel Engineb) Alternatorc) Battery 24 V.d) Base Plate.e) suitable sq mm suitable core copper cable upto 40 metres.f) Tools, standard panelg) Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT`s)h) Metering set 60/5A/110V (Amp. Meter, Volt Meter)i) Overload protection for DC-1 No.j) Battery Charger 24V DC k)Copper bus bar of suitable sizel) KWH meter 96 sqmm sizem) Starting fuse button and key switch9on/off)n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, Dc control and other required accessories complete in all respects to the satisfaction of Engineer-in-charge` 14. 500 KVA [Through Rate] |
| 67 | [21.105.14]Supplying, erection, testing andcommissioning of submersible motorpumping set non clog for seweragehaving head 12.00 m as per the indicatedrequirements of discharge in LPM andpower capacity in BHP as perIS marked including all accessories (likeSS Pipes, SS Chain (Shackle Chain) ,SS Foundation Bolt, complete base frame,Monorail, Chain Guide Line, AutoCompiling, Duct Foot Bend (D/F Bend)etc. complete in all respect 14. Discharge Capacity (LPM) - 700 Power Capacity (BHP) - 5 [Through Rate] |
| 68 | [21.84.1]Constructing brick masonry inspection Chamber sizes as given below up to 0.60 metre average depth in cement mortar 1:5 lime concrete with 40 per cent lime mortar 2:3 in foundation cement concrete 1:2:4 benching 12mm thick cement plaster 1:2 with a floating coat of 1 mm thick of neat cement R.C.C. 1:2:4 slab 100 mm thick/cement concrete topping, 50mm thick with 455mmx455mm / 455mm x610mm inside light duty C.I. inspection chamber cover and frame weight as per I.S.I. specification painted with 3 coats of black bitumastic superior paint complete as per standard design. 1. Size 450 mm X450 mm inside (with 455 mm x 455 mm cover and frame light duty single seal weighing 20 kg with C.C. topping [Through Rate] |
| 69 | [22.1.7]Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: 7. White vitreous chinaware Flat back wash basin size 450x 300 mm with single 15mm C.P. brass pillar tap [Through Rate] |
| 70 | [22.103.2]Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 2. 20 mm nominal bore [Through Rate] |
| 71 | [22.105.1]Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. 1. 15 mm nominal bore [Through Rate] |
| 72 | [22.14.1.2]Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. 1.2. Semi rigid pipe 40 mm dia [Through Rate] |
| 73 | [22.15]Providing and fixing CP Brass 32mm size Bottle Trap of approved quality and make and as per the direction of Engineer-in-charge. [Through Rate] |
| 74 | [22.171.1]Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8m long complete as per standard design. 1. With common burnt clay non-modular bricks of class designation 7.5 [Through Rate] |
| 75 | [22.181]Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. [Through Rate] |
| 76 | [22.19]Providing and fixing 100 mm sand cast Iron grating for gully trap. [Through Rate] |
| 77 | [22.22.1]Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: 1. White vitreous chinaware Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests [Through Rate] |
| 78 | [22.24.1]Providing and fixing white vitreous chinaware pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous chinaware flushing cistern and C.P. flush bend with fittings and C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : 1. W.C. pan with ISI marked white solid plastic seat and lid [Through Rate] |
| 79 | [22.26.1]Providing and fixing white vitreous chinaware flat back half stall urinal of size 580x380x350 mm with white PVC flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required : 1. Single half stall urinal with 5 litre P.V.C. automatic flushing cistern [Through Rate] |
| 80 | [22.35]Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan. [Through Rate] |
| 81 | [22.51.1.1]Providing and fixing soil, waste and vent pipes : 1.1. 100 mm dia Sand cast iron S&S pipe as per IS: 1729 [Through Rate] |
| 82 | [22.86.2]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply, including all CPVC plain and brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. 2. 20 mm nominal outer dia Pipes [Through Rate] |
| 83 | [22.87.3]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 3. 25 mm nominal outer dia Pipes [Through Rate] |
| 84 | [22.88.3]Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall 3. 25 mm dia nominal bore [Through Rate] |
| 85 | [22.88.5]Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall 5. 40 mm dia nominal bore [Through Rate] |
| 86 | [22.89.1]Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall : 1. 15 mm dia nominal bore [Through Rate] |
| 87 | [22.89.2]Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall : 2. 20 mm dia nominal bore [Through Rate] |
| 88 | [22.9.1]Providing and fixing kitchen sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P. brass waste complete, including painting the fittings and brackets, cutting and making good the walls wherever required: 1. White glazed fire clay kitchen sink of size 600x450x 250 mm [Through Rate] |
| 89 | [22.98.1]Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 1. 25 mm nominal bore [Through Rate] |
| 90 | [22.98.4]Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 4. 40 mm nominal bore [Through Rate] |
| 91 | [23.22.1.9]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.9. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 6 amp to 100 amp , 25 KA [Through Rate] |
| 92 | [23.22.2.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.1. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 125 A FP [Through Rate] |
| 93 | [23.22.4.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.7. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DB Horizontal type Double Door 8 way ( 8 incoming 3phase*8 outgoing) [Through Rate] |
| 94 | [23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole [Through Rate] |
| 95 | [23.22.5.6]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.6. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs TRIPLE POLE [Through Rate] |
| 96 | [23.23.7.3]MISCELLANEOUS 7.3. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 375 X 50 X 2 mm metre [Through Rate] |
| 97 | [23.23.7.4]MISCELLANEOUS 7.4. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 600 X 50 X 2 mm [Through Rate] |
| 98 | [23.26.1]SAFETY ITEMS 1. Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages. [Through Rate] |
| 99 | [23.26.4]SAFETY ITEMS 4. Supply & Erection of mild steel bucket stand suitable for 6 Nos. fire buckets,(but without bucket) including the cost of welding and painting of complete stand will one coat of red oxide and 2 coats of approved paint of red colour with all labour and material required to complete the job in all respect up to the entire Satisfaction engineer in charge of the work (size 6x4 made of GI pipe 32mm dia). [Through Rate] |
| 100 | [23.3.1.1]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 1.1. Wiring for Light/Fan/call bell point in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. Group A [Through Rate] |
| 101 | [23.3.4.1]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 4.1. Wiring in PVC conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin socket and 1 no 5/6 Amp switch required MS Box etc complete as required Group A [Through Rate] |
| 102 | [23.3.6.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.2. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 2.50 Sqmm(1.1.80mm) [Through Rate] |
| 103 | [23.3.6.5]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.5. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 10 Sqmm(1/3.50 mm) [Through Rate] |
| 104 | [23.4.1.1]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 1.1. Wiring for Light/Fan/call bell point with modular type switch/socket and GI box, Modular type face plate etc in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. Group A [Through Rate] |
| 105 | [23.4.4.1]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 4.1. Wiring in PVC conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin Modular type socket and 1 no 5/6 Amp Modular type switch required GI Box ,modular face plate etc complete as required Group A [Through Rate] |
| 106 | [23.4.5.1]COPPER WIRING WITH MODULAR SWITCHES IN PVC CONDUIT (SURFACE/RECESS) 5.1. Wiring in PVC conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin Modular socket and 1 no 15/16 Amp Modular switch required GI Box , modular face plate etc complete as required Group A [Through Rate] |
| 107 | [23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate] |
| 108 | [23.8.1.13]FITTING AND ACCESSORIES 1.13. Providing and fixing Piano type accessories of approved make in existing box and Bakelite sheet including fixing and making necessary connections, complete in all respect. Socket size rotary step type Electronic regulator for A.C. ceiling fan [Through Rate] |
| 109 | [23.8.3.1]FITTING AND ACCESSORIES 3.1. Supply and erection of suitable MS/GI Box covered with 5 mm thick Bakelite sheet as below 75 mm x 75 mm x 60 mm deep M.S. box [Through Rate] |
| 110 | [23.8.3.2]FITTING AND ACCESSORIES 3.2. Supply and erection of suitable MS/GI Box covered with 5 mm thick Bakelite sheet as below 100 mm x 100 mm x 60 mm deep M.S. box [Through Rate] |
| 111 | [23.8.4]FITTING AND ACCESSORIES 4. Supply and erection of 10.5 cm dia M.S.Fan box including 8 mm dia 30 cm long M.S. Road made into suitable suspension hook and erected in R.C.C. slab for the erection of fan complete with all labour and material required to complete the job. [Through Rate] |
| 112 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate] |
| 113 | [24.1.10]EARTHING AND LIGHTENING ARRESTOR 10. Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate] |
| 114 | [24.1.16]EARTHING AND LIGHTENING ARRESTOR 16. Supply and erection of 25mm dia 1.5 metre long lightning GI. tube rod tapered into a point at the top with 16cm x 16cm x 3mm thick G.I. base plate and necessary nuts and bolts with washers. [Through Rate] |
| 115 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate] |
| 116 | [24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required. [Through Rate] |
| 117 | [24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. [Through Rate] |
| 118 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate] |
| 119 | [24.13.24]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 24. 16 Sq mm 4 core (Arm.) [Through Rate] |
| 120 | [24.14.40]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 40. 35 Sq mm 4 core (Arm.) [Through Rate] |
| 121 | [24.14.46]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 46. 50 Sq mm 3.5core (Arm.) [Through Rate] |
| 122 | [24.14.54]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 54. 70 Sq mm 3.5 core (Arm.) [Through Rate] |
| 123 | [24.14.62]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 62. 95 Sq mm 3.5 core (Arm.) [Through Rate] |
| 124 | [24.14.70]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 70. 120 Sq mm 3.5 core (Arm.) [Through Rate] |
| 125 | [24.14.76]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 76. 150 Sq mm 3.5 core (Arm.) [Through Rate] |
| 126 | [24.14.82]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 82. 185 Sq mm 3.5 core (Arm.) [Through Rate] |
| 127 | [24.14.94]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE ONSURFACE/ EXISTING CABLE TRAY COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 94. 300 Sq mm 3.5 core (Arm.) [Through Rate] |
| 128 | [24.16.5]HT CABLES (Aluminium Conductor, Armoured and Unarmoured) Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 5. Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 120 Sq mm 3 core [Through Rate] |
| 129 | [24.2.3.1]LT CABLE 3.1. Laying of underground cable 0.75 metre below ground level covered without sand and bricks including excavation and refilling of trenches.:- 2.5 Sq mm to 10 Sq mm 2 to 4 Core [Through Rate] |
| 130 | [24.2.6.2]LT CABLE 6.2. Supply and erection of copper lugs including crimping etc. entire satisfaction of Engineer-in- Charge of the work. 2.5 sqmm [Through Rate] |
| 131 | [24.2.8.4]LT CABLE 8.4. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 16 sqmm [Through Rate] |
| 132 | [24.4.15.3]STREET LIGHT 15.3. B.S.E.N. 10025 High Masts \\"Supply, installation, testing and commissioning of 20 mtr. long High Mast manufactured from B.S.E.N. 10025 or equivalent grade material in, 2 (two) section hot dip, galvanized inside and outside in single dip, suitable for wind velocity as per IS 875 Part-3 suitable for 9/12 nos. luminaire loading fully motorized (power tool) with starter & cable complete along with standard accessories supplied by the manufacturer with 3 nos. steel wire rope double drum system and twin dome aviation light with LED without foundation but including cost of set of foundation nut and bolts, installation at site complete in all respect upto entire satisfaction of Engineer -in-ChargeThickness of Top and Bottom Section = 3 mm & 4mm (minimum)Top Dia = 150 mm and Bottom Dia = 460mmThickness of Galvanization - Top = 65 micron (minimum) and Bottom = 85 micron (minimum)\\" [Through Rate] |
| 133 | [24.4.8.7]STREET LIGHT 8.7. Supply and erection of Hot Dip Galvanized octagonal pole of 3mm thickness, with base plate including cost of nut and bolts , earthing studs, Integral Cable termination arrangement 5 mm thick Bakelite base plate on suitable welded MS/GI bracket 32 A four way connector 2 no 10 A SP MCB , end cover and all accessories as supplied by the manufacture including Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @80 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 9 Metre Long pole with top dia 100 mm and bottom 200 mm with base plate of size 350 x 350 x 20 mm. [Through Rate] |
| 134 | [24.5.1.2]MISCELLANEOUS ITEMS 1.2. Supply and jointing three core submersible flat cables of approved make with bare bunched copper conductor insulated and sheathed with PVC for submersible pump motors /fountain lights etc with voltage grade 1100 volts marked with IS:694, 1990 including cost of jointing, materials as well as carriage, loading, unloading etc. complete in all respect up to the entire satisfaction of Engineer- in-Charge. Submersible Copper Cable 3 Core 2.5 sqmm [Through Rate] |
| 135 | [24.5.2.3]MISCELLANEOUS ITEMS 2.3. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia [Through Rate] |
| 136 | [24.7.8]RCC FOUNDATIONS FOR DG SET 8. 750 KVA DG Set [Through Rate] |
| 137 | [24.9.3]RCC FOUNDATIONS FOR HIGH MAST OCTAGONAL POLES 3. Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @ 75 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for high mast octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 20m high mast pole [Through Rate] |
| 138 | [26.10]Maintenance of fine grass lawn for one year including fertilizer application, DAP @ 20gm/sqm, urea 40gm/sqm, watering, weeding, top dressing with good earth and manure mixture 2:1 @ 0.01cum per sqm, maintaining fine level, regular mowing and removal of rubbish with all lifts and leads. [Through Rate] |
| 139 | [26.13.1]Digging holes in all kinds of soil, and refilling the same, with the excavated earth, mixed with well decayed farmyard manure (cost of well decayed farm yard manure to be paid separately) 1. Hole 1.2 metre dia and 1.2 metre deep [Through Rate] |
| 140 | [26.15.1]Maintenance of tree including fertilization, application of insecticide, watering, weeding, training, pruning, 1. Maintenance of tree for one year for the 1st three years of age including weeding, hoeing , plant protection , watering from Deptt. source , application of 10 ml chlorpyriphos four times, 0.0289 cum FYM each,50 gm urea and 50 g DAP twice ,replacement of casualty ,disposal of debris and other activities.etc. [Through Rate] |
| 141 | [26.274]Providing and Displaying Adenium Obesum well developed with fresh and healthy 4 to 5 branch 60 to 75 cm ht. in 40 cm size Earthen Pot/ Plastic Pot as per direction of the officer-in-charge. [Through Rate] |
| 142 | [26.277]Providing and Displaying Bamboo Buddha Valley with fresh and healthy 5 to 6 suckers 1.80 m to 2.10m ht umbrella type plant well developed in 50 cm Cement Pot as per direction of the officer-in-charge. [Through Rate] |
| 143 | [26.281]Providing and Displaying Cycus cirsnallis well developed with fresh and healthy 35 to 40 lush green leaves in 40 cm Cement Pot as per direction of the officer-in-charge. [Through Rate] |
| 144 | [26.304]Providing and Displaying Mascarena palm well developed with fresh and healthy foliage leaves 180 to 210 cm ht in 40 cm Cement Pot as per direction of the officer-in-charge. [Through Rate] |
| 145 | [26.34]Planting permanent hedges including digging of trenches, 60 cm wide and 45 cm deep, refilling the excavated earth, mixed with farm-yard manure, supplied at the rate of 1.62 cum per 18 sqm, DAP 0.6kg, Chlorpyriphos 20%EC@ 0.20 litre per 18 sqm and supplying and planting hedge at 30 cm apart in two rows @ 202 no. well trimmed bushy ,multi-branched ,30 cm to 45 cm in height plants to be supplied in 15 cm x 15 cm poly bags per 18 sqm . [Through Rate] |
| 146 | [26.348]Providing and stacking of Azadirachta indica ( Neem ) of height 120-130cm in big Polybag of size 25 cm as per direction of the officer-in-charge. [Through Rate] |
| 147 | [26.35]Maintaining the hedges for one year including watering, hoeing weeding trimming and shaping ,replacement of casualty as and when noticed, application of Farm yard manure @ 0.0127 m layer over surface, application of insecticide chlorpyriphos @ 2ml per sqm twice , urea @40gm and DAP @10 gm per sqm once in a year. [Through Rate] |
| 148 | [26.379]Providing and stacking of Ficus religiosa (Peepal) of height 150-165 cm. in big poly bags of size 30 cm as per direction of the officer-in-charge. [Through Rate] |
| 149 | [26.396]Providing and stacking of Mangifera indica (Mango-grafted ) of height 60-75 cm. in big poly bag of size 25 cm as per direction of the officer-in-charge. [Through Rate] |
| 150 | [26.4.2]SITE CLEARANCE 2. Surface dressing of ground including removing rank vegetation and inequalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m in all kind of soils . [Through Rate] |
| 151 | [26.406]Providing and stacking of Phoenix sylvestris Roxb. (Wild date palm/khajur) of height 150-165 cm. in 30-35 cm size HDPE Bag as per direction of the officer-in-charge. [Through Rate] |
| 152 | [26.41.3]Supplying and display seasonal flowers of F1 hybrid quality in earthen pots at site of work, as specified by Engineer-in-charge including cost of pot. 3. Supply and planting F1 hybrid seasonal plants in well bloomed flowering stage in 30 cm size of pots [Through Rate] |
| 153 | [26.418]Providing and stacking of Polyalthia longifolia (Ashok) of height 180-195 cm. in gunny bag of size 30 cm as per direction of the officer-in-charge. [Through Rate] |
| 154 | [26.426]Providing and stacking of Eugenia jambolana (Jamun) of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. [Through Rate] |
| 155 | [26.43]Maintenance of seasonal plants, Dahlia and Chrysanthemum in pots for one month including replacement of seasonal pot on breakage . [Through Rate] |
| 156 | [26.9.8]Turfing lawns with fine grassing ( selection no.1/ Bermuda and Mexican/Neelgiri grass )including ploughing, dressing including breaking of clods, removal of rubbish, dressing and supplying of selection no. 1 / Bermuda doob grass and Mexican/Neelgiri grass roots, including supplying and spreading of farmyard manure at the rate of 0.60 cum per 100 sqm, maintenance till weed free turf is formed 8. Providing and fixing Neelgiri/ Mexican grass turf with earth 50mm to 60 mm thickness and ramming with required wooden tools, rolling with light roller to make the surface smooth and even. [Through Rate] |
| 157 | [4.12.1]Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, as directed by Engineer-in-charge. 1. All kinds of soil [Through Rate] |
| 158 | [6.1.6]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 6. 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) [Through Rate] |
| 159 | [6.10]Providing and applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil. [Through Rate] |
| 160 | [6.13]Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling and dressing and finishing the top smooth. [Through Rate] |
| 161 | [6.14.1]Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size) [Through Rate] |
| 162 | [6.15.1]Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor four level, excluding cost of centering, shuttering, finishing and reinforcement : 1. 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) [Through Rate] |
| 163 | [6.16]Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor four level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). [Through Rate] |
| 164 | [6.30.1]Centering and shuttering including strutting, propping etc. and removal of form for 1. Foundations, footings, bases of columns, etc. for mass concrete [Through Rate] |
| 165 | [6.30.3]Centering and shuttering including strutting, propping etc. and removal of form for 3. Suspended floors, roofs, landings, balconies and access platform [Through Rate] |
| 166 | [6.30.5]Centering and shuttering including strutting, propping etc. and removal of form for 5. Lintels, beams, plinth beams, girders, bressumers and cantilevers [Through Rate] |
| 167 | [6.30.6]Centering and shuttering including strutting, propping etc. and removal of form for 6. Columns, Pillars, Piers, Abutments, Posts and Struts [Through Rate] |
| 168 | [6.33.6]Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note: Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding & placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement. 6. Thermo-Mechanically Treated bars of grade Fe-500D or more [Through Rate] |
| 169 | [6.9.2]Providing and laying damp-proof course with cement concrete 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20mm nominal size) 2. 40 mm thick [Through Rate] |
| 170 | [7.21.2]Brick work with common burnt clay non-modular bricks of class designation 10.5 in foundation and plinth in: 2. Cement mortar 1:6 (1 cement : 6 coarse sand) [Through Rate] |
| 171 | [7.22.1]Brick work with common burnt clay non-modular bricks of class designation 10.5 in superstructure above plinth level up to floor IV level in all shapes and sizes in : 1. Cement mortar 1:4 (1 cement : 4 coarse sand) [Through Rate] |
| 172 | [9.10.1]Painting top of roofs with bitumen of approved quality @ 17kg per 10 sqm impregnated with a coat of coarse sand at 60 cudm per 10 sqm, including cleaning the slab surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil complete : 1. With residual type petroleum bitumen of grade VG -10 [Through Rate] |
| 173 | [9.12.1]10cm thick (average) mud phaska of damped brick earth on roofs laid to slope consolidated and plastered with 25 mm thick mud mortar with bhusa @ 35 kg per cum of earth and gobri leaping with mix 1:1 (1 clay : 1 cow-dung) and covered with machine moulded tile bricks, grouted with cement mortar 1:3 ( 1 cement : 3 fine sand) mixed with 2% of integral water proofing compound by weight of cement and finished neat. 1. With machine moulded common burnt clay non-modular brick tiles of class designation 12.5, conforming to IS 2690 [Through Rate] |
| 174 | [9.18]Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. [Through Rate] |
| 175 | [9.57.2]Providing and fixing on wall face Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 2. 110 mm diameter [Through Rate] |
| 176 | [9.58.1.2]Providing and fixing on wall face Unplasticised - PVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. 1.2. Coupler 110 mm [Through Rate] |
| 177 | [9.58.5.2]Providing and fixing on wall face Unplasticised - PVC moulded fittings/ accessories for Unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. 5.2. Bend 87.5° 110 mm bend [Through Rate] |
| 178 | [9.59.2]Providing and fixing Unplasticised -PVC pipe clips of approved design to Unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 2. 110 mm [Through Rate] |
| 179 | [9.60]Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. [Through Rate] Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail