Name of Work:- Providing and Fixing of Electrical Driving unit (Actuator) by operating 800 mm dia Sluice valve installed at Rohini Sec-23 BPS
Sl. No.
Item Description
1
Procurement of Actuator Integral Starter Conventional Type setting of Torque Levels, Position Limits contacts etc without removal of cover and main power supply. Double Sealing, Ambient Temperature 0°C to +70 °C Position measurement, Mechanical limit Switch of Model No. L120-20-BA0-IS-Dual Potentiometer for Exiting size of 800mm dia SluiceGate. Make: - Limitorque/Rotork/Cair.
2
Procurement of Gear Box suitable for existing Sluice Gate of size 800mm Make:- Limitorque/Rotork/ Cair.
3
Procurement of adoption plate/Kit/Flange suitable for 800mm dia Sluice Gate.
4
Procurement of Electrical Panel Including all required article for Operating equipment with Measuring Transmission System.
5
Procurement of Flexible Copper Power Cable of size 10sq mm X4 core Make:- Havells/ Kalinga/Grandly
6
Procurement of Copper Flexible Cable of size 19 Core 1.5 sq mm Make:- Grandly/Havells/Kalinga .
7
Laying of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required Upto 35 sq. mm Meter.(DSR 7.1.1. 2022)
8
Dismantle of upper part/Wheel/Gear box of Sluice Gate of size 800mm cutting/opening rusted nut,bolt by gas cutter or by manual Skilled Staff the work includes arrangement of holding the gate.
9
Arrangement for lifting the actuator to Top of the valve by crane Try pod with chain pulley Block/Heavy Manual Labor.
10
Fixing of Actuator on the existing Sluice Gate of size 800mm with the help of above adoption plate/kit/Flange with proper alignment, the Work includes Supply & fixing the key grinding, welding, cutting, polishing etc.
11
Minor repairing/Cleaning of SS Spindle for smooth installation of actuator for sluice gate of 800mm dia.
12
Making the setting of Actuator Electrical Connection with Actuator and electrical Panel by using the Ferule, Packing etc.
13
Machining and threating in the stem nut.
14
All required Safety Equipment’s / Articles as per NHRC Guidelines
15
Testing and Commissioning of Complete above work on-load and No-load including testing of level indication. Please Enable Macros to View BoQ information