| 1 | WORKS DETAILS |
| 2 | ESTABLISHMENT OF NEW 33/11 KV SERAKULAM SS. |
| 3 | SUPPLY OF POWER TRANSFORMERS, BREAKERS, CONTROL ROOM EQUIPMENTS GALVANISHED STEEL STRUCTURES AND OTHER ACCESSORIES AT NEW 33/11 KV SERAKULAM SS. |
| 4 | 8MVA, 33/11KV, 3phase, 50C/S, Dyn11 Outdoor Power Transformers having 8.35% impedance with on-load tap changing gear (+5% to -15% in steps of 1.25%), including transformer oil for first filling, RTCC panel and complete accessories and confirming to relevant IS & as per e-tender specification, Freight, packing, forwarding upto substation site including unloading on the plinth, transport & Storage insurance at site for the Power Transformer and accessories. |
| 5 | 33 KV (GC) VCB (out door) 1250A, 26.3kA per 3 Sec., 3 pole Gang operated Solid Dielectric Insulated with Permanent Magnetic Actuator operating Mechanism with inbuilt VCB Bushing embedded Dry Type Epoxy Resin Cast CT (600-300/1-1A) with structure and complete Accessories |
| 6 | 11KV (LV) VCB (out door) 12 KV, 1250A, 26.3kA per 3 Sec., 3 pole Gang operated Solid Dielectric Insulated with Permanent Magnetic Actuator operating Mechanism with inbuilt VCB Bushing embedded Dry Type Epoxy Resin Cast CT (1200-600/1-1A) with structure and complete Accessories |
| 7 | 11KV (Feeder) VCB (out door) 12 KV, 1250A, 26.3kA per 3 Sec., 3 pole Gang operated Solid Dielectric Insulated with Permanent Magnetic Actuator operating Mechanism with inbuilt VCB Bushing embedded Dry Type Epoxy Resin Cast CT (400-200/1-1A) with structure and complete Accessories |
| 8 | 33KV Potential Transformer with TC (Single phase unit) |
| 9 | 11KV Potential transformer with TC (Three phase unit) |
| 10 | AC Panel for 33KV SS |
| 11 | 110 V DC annunciation panel Type B |
| 12 | 110V DC indoor C&R Panel for GC Breaker |
| 13 | 110V DC indoor C&R Panel for LV Breaker |
| 14 | 110 V DC indoor C&R Panel for Twin feeder |
| 15 | Control Cables, Junction Box and Accessories |
| 16 | 14C x 2.5 Sq.mm Copper cable armoured |
| 17 | 8C x 4 Sq.mm Copper cable armoured |
| 18 | 4C x 4 Sq.mm Copper cable armoured |
| 19 | 4C x 2.5 Sq.mm Copper cable armoured |
| 20 | 2C x 2.5 Sq.mm Copper cable armoured |
| 21 | 4C x 25Sq.mm LT UG Aluminiums Power cable armoured |
| 22 | Supply and glanding of ISI mark cable gland of 19/22 mm of reputed make including removing of insulation of cables and providing suitable holes as required and as directed by the field Engineer. |
| 23 | Supply and glanding of ISI mark cable gland of 25 mm of reputed make including removing of insulation of cables and providing suitable holes as required and as directed by the field Engineer. |
| 24 | Supply and glanding of ISI mark cable gland of 28 mm of reputed make including removing of insulation of cables and providing suitable holes as required and as directed by the field Engineer. |
| 25 | Supply and termination of cable core end dressed neatly including the cost of cable socket (lug) ferrules, sleeves, tags, ties, stropes, etc., as directed by the field Engineer. |
| 26 | Supply of CT/PT junction box made out of 14Swg (2mm) M.S.Sheet wherever required as directed by the field Engineer. The box shall be vermin proof shall have sturdy hinges, provision for mounting terminal blocks and locking arrangements including cost of all materials. 400W x 300H X 150D |
| 27 | Supply of AC Junction Box of size 535x310x127mm of 18SWG MS sheet including HRC fuse unit-18 Nos. Should be fitted with base, consumables etc. (The box shall be vermin proof, shall have sturdy hinges and locking arrangements) |
| 28 | Supply of mounting channel suitable for CBTM 5 terminal block in panel /box as required and as directed by the field Engineer. |
| 29 | Supply and fixing of disconnected type terminal block suitable for CT Circuits in panels/ box as required & as directed by the field Engineer |
| 30 | Supply and fixing of ISI mark 16 Amps - Fuse holder with HRC Fuse of reputed make in panels/ boxes for AC/DC/PT circuits wherever required as directed by the field Engineer. |
| 31 | Supply and fixing of ISI mark 63 Amps - Fuse holder with HRC Fuse of reputed make in panels/ boxes for AC/DC/PT circuits wherever required as directed by the field Engineer. |
| 32 | Supply of M.S Chequerred plate of 6 mm thickness |
| 33 | Bus Bars, Strung bus, conductors and Connectors |
| 34 | Zebra ACSR conductor |
| 35 | 2.0\\" / 50 mm Aluminium Bus bar (Thickness:5 mm) |
| 36 | Supply of eye bolt of 18 - 20 mm dia GI rod of required length suitable for 33KV, 22KV and 11KV strung bus including cost of GI rod and 2Nos GI nuts & washer as directed by the field Engineer. |
| 37 | Tension fitting Clamp 4 Bolted for Zebra |
| 38 | T Clamp for 2\\" Bus to Single Zebra |
| 39 | T Clamp for Zebra to Zebra |
| 40 | Switchend clamp for Single Zebra |
| 41 | Switchend clamp for 2\\" Busbar |
| 42 | Reducer clamp for 2\\" Bus to Zebra |
| 43 | PG Clamp for Zebra |
| 44 | Free end clamp for 2\\"Busbar |
| 45 | Corana Bell for 50mm Bus Bar |
| 46 | Switch end clamp for Mink |
| 47 | Seating Block for 2\\" Bus bar(for giving Elect Conn) |
| 48 | 22 kV PT Insulators |
| 49 | 11KV PT Insulator |
| 50 | 11KV, 120KN Disc insulators (Antifog) |
| 51 | LIGHTNING ARESTERS |
| 52 | 33KV Lightning Arrester Station type |
| 53 | 11KV Lightning Arrester Station Type |
| 54 | 11KV Lightning Arrester Dist. Type |
| 55 | Station Transformer & its Accessories |
| 56 | 11 KV/433 V 100 KVA Station Transformer |
| 57 | 11 KV HG Fuse set with PT |
| 58 | 11 KV AB switch centre rotating along with PT Insulator without Support Structure. |
| 59 | 11 KV Station Transformer structure using R.S.Joist 200x100 RSJ.channels, angles etc. |
| 60 | Supply of ISI mark 200 Amps porcelain fuse unit along with the hylam board of 25 mm thick (size 600 X 500mm) in panels, boxes for AC Circuits wherever required as directed by the field Engineer |
| 61 | Fabrication, supply and fixing A.C.distribution box of size 750x750x250 mm out of 14SWG (2mm) M.S.Sheet including primer paint coat, Supply, Fabrication and Erection of Fixing Flat using 65x10MSF, supply & fixing of 3 nos 200A and 6 nos 100A Porcelain fuse units, Supply and Painting of Two coat of Enamel Paint including cost of materials, consumables, fright, etc., as directed by the field Engineer. The box shall be vermin proof shall have sturdy hinges, provision for mounting MCB and MCCB, detachable gland plate and locking arrangements. |
| 62 | DOUBLE BREAK CENTRE ROTATING ABSWITCH AND ACCESSORIES |
| 63 | 33KV Centre rotating AB switch along with PT Insulator without Support Structure |
| 64 | 11KV AB switch centre rotating along with PT Insulator without Support Structure. |
| 65 | Supply of reputed make long shackle 6 lever Navtal lock with triplicate keys for AB switches and for any other purpose including the cost of ring and key token as directed by the field Engineer |
| 66 | Supply of flexible copper tape 25x3 sqmm /12mm rope for interlinking panel earthing and for any other purpose, on any sizes, including the cost of copper lugs at both ends as directed by the field Engineer |
| 67 | Supply and erection of `B` Class GI pipe for extension of tandum /down pipe for AB Switches and for any other work as required and as directed by field Engineer 40mm dia. |
| 68 | SUPPLY OF VARIOUS TYPES OF FABRICATED MILD STEEL STRUCTURES CONFIRMING TO IS 2062 GR A AT SITE AS PER THE STD.DESIGN/ DRAWING, INCLUDING FREIGHT & HANDLING, LOADING, UNLOADING, LABOUR, MACHINERY AND CONSUMABLES AND AS DIRECTED BY THE FIELD ENGINEER AT THE SS SITE. |
| 69 | 33 KV Four Pole structure (Incomer 4.5 meter pole to pole) |
| 70 | 33 KV Strung Bus structure |
| 71 | 33 KV Power Transformer Gantry structure |
| 72 | 33 KV AB switch structure |
| 73 | 33 KV Pie support Structure |
| 74 | 33 KV LAS Structure under Strung Bus |
| 75 | 11 KV Feeder Bay structures (4m Pole centre to Pole centre) with (3 Bays + 1 LV) |
| 76 | Non-specified structures, Extension, Alterations, and Deductions as per station requirement. |
| 77 | Heavy section using RSJ 250 x 125 mm |
| 78 | Heavy section using RSJ 200 x 100 mm |
| 79 | Light section (other than heavy section) |
| 80 | Supply and Erection of 5m Grouting type lamp post of B class MS pipe (3 inch dia for 3mtrs & 2.5inch dia for 2mtrs) including single/double fitting (Straight or 'V' type) fixing arrangements, 1 inch dia B class pipe arms, yard light box fixing flat and one coat of redoxide and one coat of aluminium paint. |
| 81 | Supply and Erection of reputed make street light fitting with 1x(70-75)W or 2x(35-40)W, 240V CGL/ PHILIPS make LED Light. |
| 82 | Supply and Erection of yard light fuse unit mounting box of size 200x200x150mm (BxHxD) out of 18 SWG (1.22mm) M.S Sheet including primer paint as per Drawing including the Supply, Fabrication and Erection of Box fixing Flat using 50x8MSF, Two coat of enamel paints, provided with 16/20A rewirable Porcelain Fuse carrier unit, 16 A Bakelite connenectors including its cost materials, consumables, freight, etc and as directed by the fiels Engineer on site requirements. (The box shall be vermin proof, shall be provided with sturdy hinges, with provision for cable entry and locking arrangements). |
| 83 | EARTHING - EARTH MAT & LIGHTNING SPIKES |
| 84 | Supply of M.S round rod of 40 mm dia for earth electrodes ( Each earth electrodes should contain double rods each with 6 meter length) |
| 85 | Supply of Earth Spikes by using 40 mm M.S.Rod (300 mm) & GI Earth pipe (40 mm Dia, 3m length) , M,S Angle (50x6x450mm), Bolt, Nut with washer etc as per drawing. |
| 86 | Supply of M.S FLAT 65X10 mm for Earth Mat |
| 87 | Supply of M.S FLAT 50X8 mm for Earth Mat |
| 88 | Supply of Rubber mat of size 2000X1000X10mm as per relavent ISI Code. |
| 89 | Supply and providing of 600mm mean dia, 300mm height 36mm thick cement coller for identification of earth electrode location including 1primer and 2 coats of colour wash as directed by field Engineer |
| 90 | Battery and Charger |
| 91 | 110V, 120AH Battery set with stand |
| 92 | 110V, DC 24 A, Battery charger |
| 93 | FIRE FIGHTING, SAFETY & SCIENTIFIC EQUIPMENTS |
| 94 | Supply of Mechanical Foam Portable type 9 litres capacity fire extinguishers with initial charge complete with chromium plated GM cap, high pressure nylon braided discharge hose with specially designed foam designed nozzle and in general all accessories strictly confirming to the latest issue of ISI Certification mark |
| 95 | Supply of Dry Chemical Powder type trolley mounted Cylindrical shape 25KG capacity fire extinguisher with initial charge & complete with rubber or braided hose, dry powder level indicator and all accessories confirming to the latest issue of ISI Certification mark |
| 96 | Supply of Dry Chemical Powder type Cylindrical shape 9/10 KG capacity fire extinguisher with initial charge & complete with rubber or braided hose, dry powder with level indicator and all accessories confirming to the latest issue of ISI Certification mark |
| 97 | Supply of Portable Dry Chemical Powder type cylindrical shape 5/6 KG capacity fire extinguisher wilth initial charge & complete with rubber or braided hose, dry powder with level indicator and all accessories confirming to the latest issue of ISI certification mark. |
| 98 | Supply of Fire/Water bucket of 10 lit capacity made out of 26Swg (0.46 mm) M.S.Sheet painted with white & red enamal paint in side & out side respectively bottom of bucket shall be ` U ` shapped out side of the bucket shall be written as Fire in English /Tamil in white enamal paint including cost of all materials. |
| 99 | Supply and Fabrication of Yard Fire Stand frame with top canopy cover confirming to IS 2062 GrA |
| 100 | Supply and Fabrication of Battery Room Fire Stand confirming to IS 2062 GrA |
| 101 | Provision for sand drums with conical top cover for each Power Transformer |
| 102 | Supply of Danger board |
| 103 | Supply of rubber Gauntlets as per IS Standard as directed by the field Engineer. |
| 104 | Supply of rubber Gloves as per IS Standard as directed by the field Engineer. |
| 105 | Supply of Telescopic earth rod with copper wire 10 feet (SS type) as per IS Standard as directed by the field Engineer. |
| 106 | Supply of Discharge rod 10 feet (SS type) as per IS Standard as directed by the field Engineer. |
| 107 | Supply of Aluminium extension type ladder 24 feet Length with support and trolley as per IS Standard as directed by the field Engineer. |
| 108 | Supply of Double End and Rings Spanner set & Allen Key |
| 109 | Supply of Rain coat |
| 110 | Supply of ISI brand Belt Rope |
| 111 | Supply of Reputed make Emergency Light(Rechargable & Portable) |
| 112 | High Beam Torch Light |
| 113 | Supply of First Aid Kit |
| 114 | Plastic Name Board ( Feeder Name, LC board, Back charged etc.,) |
| 115 | GPS Synchronised Wall clock |
| 116 | Entrance Floor Mat |
| 117 | Welcome Mat |
| 118 | Earthing layout board ( wooden / plastic / Aluminium) having the size of 1200mm x 600 mm and board covered with 3mm thick achorlic transparent sheet. |
| 119 | Supply of 1000V/2000 MOhm Hand operated Meggar |
| 120 | Digital multi meter of reputed make (Fluke) |
| 121 | Supply of Power clamp Meter 400A AC/DC with Accessories |
| 122 | SUPPLY OF PAINT, EQUIPMENT BOARD, LC BOARD ETC |
| 123 | Supply of Enamel Paint including cost of paint, brush and consumables etc., |
| 124 | Supply and erection of Vinyl Sticker cutting/ Printing on Vinyl Sticker/ Foam board to be used for main equipment, slogan, name board & any other purpose of required sizes as directed by the field Engineer. |
| 125 | Supply of Fabricated main equipment board 2500 X 1500 mm out of 14 SWG M.S Sheet, alongwith painted MS Channels(100 x 50 MM) and MS Flat(65x65x6) (50x50x6) (50x6) and mounting the Board on to a Structure with all reuqired hardware. |
| 126 | Supply & fixing of LC/Key board out of 75x 25mm Alu. frame embedded with 12mm pre-laminated wood particle board using screw on rear side, 2Nos plain glass sliding shutter of 5mm thick fixed with metal roller on Alu.channel with locking arrangements, glass piece handle shutters, wall clamp, key hooks as directed by the field Engineer including cost of all materials & all consumables. |
| 127 | Supply of M8, M9, M10, M12 & M16 full thread GI bolt, nuts & GI washer of various size with IS Grade for erection of insulator or any other purpose wherever required and as directed by the field Engineer. |
| 128 | LABOUR CHARGES FOR ERECTION TESTING AND COMMISIONING OF POWER TRANSFORMERS, BREAKERS, CONTROL ROOM EQUIPMENTS AND ERECTION OF M.S STRUCTURES AT NEW 33/11 KV SERAKULAM SS. |
| 129 | Erection, Testing & Commissioning Charges for 8 MVA Power Transformer |
| 130 | Labour for erection of 33/11 KV, 3 pole Gang operated Soild Dielectric Insulated with Permanent Magnetic Actuator operating Mechanism with inbuilt 33/11KV VCB Bushing embedded Dry Type Epoxy Resin Cast 33/11 KV CT with structure and complete Accessories and providing template |
| 131 | Labour for erection of 33/22/11KV , PT, (one S.Ph or 3Ph. Unit) with provision of hardwares,etc. Using manual labour |
| 132 | Labour Charge for assembling of panel (Single Feeder) , including supply & fabrication of MS flat 65x10mm for mounting arrangement and earthing of panel including hardwares.(Simplex indoor/outdoor) |
| 133 | Labour Charge for assembling of panel (Twin Feeder), including supply & fabrication of MS flat 65x10mm for mounting arrangement and earthing of panel including hardwares.(Simplex indoor/outdoor) |
| 134 | ERECTION OF CONTROL CABLES, JUNCTION BOX AND ACCESSORIES |
| 135 | Labour for erection of cable in duct/ trench/ clamping on structures - neat laying in the ducts with identification Aluminium tags in all duct corners for easy identification of cables including fabrication of clamps and fixing at uniform intervals as directed by the field Engineer - Up to 8 core |
| 136 | Labour for erection of cable in duct/ trench/ clamping on structures - neat laying in the ducts with identification Aluminium tags in all duct corners for easy identification of cables including fabrication of clamps and fixing at uniform intervals as directed by the field Engineer. Above 8 core |
| 137 | Labour for erection of cable end glands |
| 138 | Labour for erection of cable core end termination |
| 139 | Labour for excavating and refilling of earth /trench for earthmat, cable, etc., of any size/depth narrow excavation as directed by the field Engineer in normal clay / hard graval soil |
| 140 | Labour for erection of CT/PT junction box ,AC distribution box, yard light box,change over switch including fabrication of clamping arrangements with provision of hardwares,etc., |
| 141 | Supply and fixing of 32 AMPS - 3 phase, 4 poleMCB of Havells/Schneider/ MDS/ Reputed make with ISI mark wherever required as directed by the field engineer. |
| 142 | Supply and fixing of 16 AMPS - 1 phase, 1 pole MCB of Havells/Schneider/ MDS/ Reputed make with ISI mark wherever required as directed by the field engineer. |
| 143 | ERECTION OF BUS BAR, STRUNG BUS AND LAS |
| 144 | Labour for erection of single / double pole stack up right, under hang or suspension.33KV or 22KV or 11KV insulators. |
| 145 | Labour for providing Droppers and jumpers |
| 146 | Labour for the erection of Busbar with 50mm Aluminium bus including suitable Modifications of End Clamps, providing holes wherever necessary as directed by the field Engineer. |
| 147 | Labour for the Erection of Strung bus and all related hardwares, fittings, clamps including Meggering, hoisting of insulators and consumables and as directed by the field Engineer. (1 span=3 runs) |
| 148 | Labour for erection of LAS including erection of base if required Station type single/ Double pole stack 33 or 22 or 11KV with provision of hardwares,etc., |
| 149 | ERECTION OF STATION TRANSFORMER & ACCESSORIES |
| 150 | Labour for erection of 33/22/11KV/433V distribution transformer with using crane with provision of hardwares,etc., |
| 151 | Labour for erection of HG fuse 3pole set 33 KV or 22 KV or 11KV |
| 152 | 11 KV Station Transformer structure |
| 153 | Labour for erection of AB Switches, including erection of insulators and alignment works with provision of hardwares,etc., without earth hand operated 11 KV Station Transformer |
| 154 | ERECTION OF AB SWITCHES & ACCESSORIES |
| 155 | Labour for erection of 33 KV isolator / AB Switches, including erection of insulators and alignment works with provision of hardwares,etc., without earth hand operated. |
| 156 | Labour for erection of 11 KV isolator / AB Switches, including erection of insulators and alignment works with provision of hardwares,etc., without earth hand operated. |
| 157 | ERECTION OF 33KV & 11 KV STRUCTURES |
| 158 | 33 KV Four Pole structure (Incomer) |
| 159 | 33 KV Strung Bus structure |
| 160 | 33 KV Power Transformer Gantry structure |
| 161 | 33 KV AB switch structure |
| 162 | 33 KV Pie support Structure |
| 163 | 33 KV LAS Structure under Bus Bar |
| 164 | 11 KV Feeder Bay structures (4m Pole centre to Pole centre) with 3 Bays + 1 LV |
| 165 | Non-specified structures, Extension, Alterations, and Deductions as per station requirement. |
| 166 | Heavy section using RSJ 250x125mm/ 200x100mm |
| 167 | Light section (other than heavy section) |
| 168 | LABOUR CHARGES FOR EARTH BORE, ERECTION OF EARTH MAT & SPIKE |
| 169 | Providing Earth bore 140/150 mm dia using power rig or 100/125 mm dia using hand bore set including the labour, lead, lift etc., sedimentary strata of clay & sand stone shale pebbles boulders etc., for earth Pits with supply and providing of Bentonite powder (Sodium Bentonite) 5Kg /Mtr depth of the bore mixed with low resistivity earths as directed by the field Engineer (Earth to be supplied by the contractor) |
| 170 | Labour, machinery, consumables for fabrication, erection of earthmat, earth connection, earth electrode, earthspike (including sharpening of earth spike) as directed by the field Engineer. |
| 171 | ERECTION OF 110V 120 AH BATTERY & CHARGER |
| 172 | Erection, Testing & Commissioning of 110V, 24 A Battery charger with stand for operable height including Labour Charge for assembling of battery charger, including supply & fabrication of MS flat 65x10mm for mounting arrangement and earthing of panel including hardwares. |
| 173 | Labour for Erection of Battery set including two coats of painting of Acid proof paint on wooden stand (including any modification if required) and neatly stacking the Battery cells and fixing of connecting plates including any modifications/ alterations required as directed by field Engineer - 110 V, 120 AH |
| 174 | Labour, Consumables for the Initial filling and First Charging of the Battery to the required AH input and thereafter atleast 3 cycles of Charge / Discharge of the Battery set till the battery is charged to its full Capacity as directed by the field Engineer. 110V, 120 AH. |
| 175 | Supply and fixing of 63 Amps, AC single/ 3 phase 4 pole 415V ISI mark changeover switch of reputed make iron glad metal switch as required and directed by the field Engineer. |
| 176 | Supply & Fixing of 63 A HRC Fuse Holder with HRC DC Fuse and Wooden board (Positive and Negative) |
| 177 | Commissioning of 33/11 KV SS Electrical Equipments (Except Power Transformer, Battery & Battery Charger ) including testing and relay setting in coordination with TNPDCL & TANTRANSCO officials |
| 178 | MISCELLANEOUS - (PAINTING OF EQUIPMENT BOARD, LC KEY BOARD, ETC.) |
| 179 | Yard Fire Stand frame with top canopy cover |
| 180 | Battery Room Fire Stand |
| 181 | Labour charges for writing details/drawing layout in any finished surface/board including cost of enamel paints and other consumables as directed by the field Engineer. |
| 182 | Supply of paint of reputed make and Labour for first primer coat of Painting using Red oxide paint including consumables, after proper surface preparation using appropriate machinery to remove rust/scales etc as directed by the field Engineer. |
| 183 | Supply of paint of reputed make and Labour, consumables for first primer coat using red oxide Paint and first finish coat of Painting using Aluminium Paint including consumables, after proper surface preparation using appropriate machinery to remove rust/scales etc as directed by the field Engineer. |
| 184 | Labour, consumables for the Second Finish coat using Aluminium Paint of all steel sections as directed by the field Engineer. |
| 185 | LABOUR CHARGES FOR ERECTION OF SUPPORT STRUCTURES FOR BREAKERS AND YARD LIGHTS |
| 186 | Earthwork excavating and depositing on bank with initial lead of 10m & initial lift of 2m in hard stiff clay stiff black cotton hard red earth, shales, murram, gravel stoney earth, earth mixed with small size boulders. |
| 187 | Earthwork excavating and depositing on bank with initial lead of 10m & initial lift of 2m in soft disintegrated rock laterite soft rock or kankar not requiring blasting, etc., complete. |
| 188 | Earthwork excavation in medium rock and dense medium rock not requiring blasting. |
| 189 | Supplying and filling of M sand in foundation and basement with well watering and consolidation as per specn. including cost of all materials labour, lead, lift, etc., complete. |
| 190 | PCC 1:3:6 mix using 20mm HBS machine crushed metal for foundation including with out form work cost of all labour, materials, lead, lift, curing, etc., complete. |
| 191 | PCC 1:2:4 using 12-20mm HBS metal for structure concrete with form work including cost all materials lead, lifts, labour curing etc complete |
| 192 | PCC 1:2:4 using 12-20mm HBS metal for plinth concrete with out form work including cost all materials lead, lifts, labour curing etc. |
| 193 | RCC 1:1.5:3 using 12 - 20mm (machine crushed) metal for raft foundation without formwork including cost of all materials, labour lead, litf, etc., complete. |
| 194 | Plastering with CM. 1:3 mix 12mm thick including cost of materials, labour, lead, lift, watering, curing, etc., complete. |
| 195 | Colour washing two coats with Exterior Plastic Emulsion paint over one coat of Plastic Emulsion primer for outside wall including cost of all materials, labour, lead, lift, etc., complete. |
| 196 | Assembling of various plinth templates for providing concrete including transporting from one plinth to another, alingning fixing to corrrect level and dismatling the templete after concreting including cost of labour, cost of template, lead, lift, etc., complete. |
| 197 | Supplying and fabricating and placing in position of MS / RTS steel reinforcement for RCC works including labour for cutting, bending, tying and fixing in position as per specification including cost of all materials, lead, lift, labour, cost of binding wire, etc., complete. Please Enable Macros to View BoQ information |