| 1 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 2 | 14.6:Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 3 | 90.3.17.3:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.50 mm dia GI pipe |
| 4 | 6.2:Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube,having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 5 | 90.16.3.10:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm copper strip |
| 6 | 5.10:Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 7 | OD385971/2025-2026:Earthing with maintenance-free chemical earthing electrode of 50 mm dia copper bonded/GI, 3m long, complete with backfill compound, testing as required. including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. as required |
| 8 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 9 | OD386753/2025-2026:Supply, Installation, Testing and Commissioning of SPD for 3 phase MSB- Prewired, sparkgap-based type 1 + type 2 combined lightning current and surge arrester consisting of a base part and plug-in protection module SPD according to EN 61643-11 / ... IEC 61643-11 type 1 + type 2 / class I + class II Energy coordination with terminal equipment ( 10 m) type 1 + type 2 + type 3 Nominal voltage (a.c.) (UN) 230 / 400 V (50 / 60 Hz) V Max. continuous operating voltage (a.c.)[L-N]/[N-PE] (UC) 255 V (50 / 60 Hz) Lightning impulse current (10/350 µs)[L1+L2+L3+N-PE] (Itotal) 100 kA Specific energy [L1+L2+L3+N-PE] (W/R) 2.50 MJ/ohms Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) 25 / 100 kA |
| 10 | OD385713/2025-2026:Engaging wire man |
| 11 | OD385719/2025-2026:Engaging beldar/coolie |