| Sl. No. | Item Description |
| 1 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 9.0 Mtr long PCC pole of 200 Kg Working Load |
| 2 | Supply and fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 3 | B & S type hardware 45 KN |
| 4 | B & S disc insulator 45 KN |
| 5 | Supply and fixing of 'V' type cross arms with top hamper and clamps as per latest Discom specifications made of MS angle on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 6 | Supply and fixing of top hamper on the existing pole as per latest Discom specifications complete including nut bolts with two coats of Red oxide and two coats of Aluminium paint etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 7 | 11 kV (.7m long) (65 x 65 x6mm angle)Vertical type |
| 8 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 9 | Supply and fixing of PG / T clamps on overhead lines/jumpers, made of aluminium alloy 4600 of IS 617-1994 (with latest amendment if any) with steel nut and bolts conforming to IS 1363-1992 & IS 1367/1979-80 (with latest amendments if any) all ferrous metal parts intended for outdoor use except those made of stainless steel shall be protected by hotdip galvanising in accordance with IS 2633-1986 complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 10 | PG Clamp for Dog Conductor Type - A |
| 11 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as reqd. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 12 | Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 13 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 14 | LT cross arm 600 mm long with clamp |
| 15 | LT cross arm 1200 mm long with clamp |
| 16 | Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 17 | 100 mm x 70 mm |
| 18 | Supply and fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 19 | 75mm x 90mm |
| 20 | Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 21 | 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 22 | 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog) |
| 23 | Supplying and laying of Hot dip galvanized steel stay wire of 550-900 N/mm Quality confirming to IS-2141/2000 in all respect Including chemical composition (Heavily coated Hard quality) of dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 24 | Supply and fixing of 11 / 33. KV Stay insulator as per IS:5300/1969 and as per Discom's standard specifications etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 25 | 110 x 75 x 22mm 11 KV Stay Insulator |
| 26 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 27 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 28 | Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double pole as per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 29 | Supply and fixing of strut made out of ‘B’ Class GI pipe 80mm. having base plate of size 300mmX300mmX6mm. (10.0 Mtr. long) by fixing on the pole at top by clamping within position with M.S. flat 50mmX6mm. Clamps and M.S. nuts & bolts and grouting in ground as required (0.4 Mtr)GI pipe Strut 10Mtr. |
| 30 | Supply and fixing of guard bracket 2.2 mtr. long made from (75x40) ISMC 7.14Kg. Per Mtr. M.S. channel including necessary clamp and botls etc. as per technical specification & drawing of DISCOM. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 31 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM. |
| 32 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 33 | 3 core 300.0 Sq.mm |
| 34 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 35 | 3 core 185.0 Sq.mm |
| 36 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 37 | Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 38 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 39 | Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 40 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 41 | 11 KV End Termination Kit Indoor type |
| 42 | 3 core 120/150/185 Sq.mm |
| 43 | 11 KV End Termination Kit Outdoor type |
| 44 | 3 core 120/150/185 Sq.mm |
| 45 | 11 KV Straight Through Joint Kit |
| 46 | 3 core 120/150/185 Sq.mm |
| 47 | 33 KV End Termination Kit Outdoor type |
| 48 | 3 core 240/300/400 Sq.mm |
| 49 | 33 KV Straight Through Joint Kit |
| 50 | 3 core 185/240/300 Sq.mm |
| 51 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 52 | 10.0 Sq. mm |
| 53 | 2 core |
| 54 | 6.0 Sq. mm |
| 55 | 4 core |
| 56 | 10.0 Sq. mm |
| 57 | 4 core |
| 58 | 25.0 Sq. mm |
| 59 | 3.5 core |
| 60 | 35.0 Sq. mm |
| 61 | 3.5 core |
| 62 | 70.0 Sq. mm |
| 63 | 3.5 core |
| 64 | 185.0 Sq. mm |
| 65 | 3.5 core |
| 66 | 300.0 Sq. mm |
| 67 | 3.5 core |
| 68 | Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 69 | Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 70 | Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 71 | Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 72 | S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 73 | 3/3.5/4 x 70.0 sq.mm-150 sq.mm |
| 74 | 3/3.5/4 x 185.0 sq.mm-300 sq.mm |
| 75 | Supplying and drawing of XLPE insulated LT Aerial bunched Aluminium conductor cable confirming to IS 14255/1995 and IS 398 (Pt-4)/ 1994 and as per Discom Specs. on existing cross arms through I hook with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 76 | 3 X 25 sq. mm. + 1X25 sq. mm. (insulated) |
| 77 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 78 | 3.5 x 25.0 sq.mm |
| 79 | 3.5 x 35.0 sq.mm |
| 80 | 3.5 x 70.0 sq.mm |
| 81 | 3.5 x 185.0 sq.mm |
| 82 | 3.5 x 300.0 sq.mm |
| 83 | 4 x 10.0 sq.mm |
| 84 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 85 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 86 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 87 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 88 | 10 SWG G.I. ( Hot Dipped ) Wire |
| 89 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annex ure \\"A\\" attached with this BSR . |
| 90 | 100 mm dia. |
| 91 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 92 | 50 mm |
| 93 | 110 mm |
| 94 | 160 mm |
| 95 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 96 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .Electrolytic grade Aluminium bus bar 6010 grade |
| 97 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 98 | 9.0 mm thick |
| 99 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 100 | 3 pole MCCB With Thermal Magnetic release |
| 101 | 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 102 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 103 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 104 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 105 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 106 | Supply, installation & commissioning of 1lKV, 20KA, 4way ring main unit having one breaker and 2 nos. ON- load operative circuit must have the following feature. Manually operated 6004' circuit VCB earthing switch with fully making capacity. Both side extendable type. Auto reflex operating handle' Shunt trip coil (230 V AC) for external trip.self Powered ON/OFF earth indication .Live cable indication LEDs energized capacity divider Cable box suitable for cable termination of 1 nos 3*300sqmm XLPE cable Right angle boos eqvt. To '11'300 of MECP make push on type Scineider/ABB/C&S/C.G./Areva. (b)RMU 3+1.(SSSV Type) |
| 107 | S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 . including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect .The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including testing from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 160KVA |
| 108 | 100 KVA |
| 109 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 110 | 200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer |
| 111 | 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 112 | 100 Amp. Distribution Kiosk suitable for Underground cable of Size 500mm x 550 mm x 700 mm |
| 113 | Supplying and drawing of XLPE insulated LT Aerial bunched Aluminium conductor cable confirming to IS 14255/1995 and IS 398 (Pt-4)/ 1994 and as per Discom Specs. on existing cross arms through I hook with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 114 | 1 X 25 sq. mm. + 1X25 sq. mm. (insulated) |
| 115 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 116 | 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 117 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 118 | Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: |
| 119 | Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 120 | 32 mm Dia. |
| 121 | Dismantling/removal of line and Sub-Station material collecting from site and depositing the same with store of RSEB/UIT in safe conditions and refilling the pit in compaction, leveling etc. The AAC/ACSR/Copper Conductor and GI wire stay wire etc. shall be wound in the shape of coils. (The damaged caused to the material during dismantling/transportation shall be recovered from the Contractor.GI Wire 6 Swg/8Swg. |
| 122 | LT Cable upto 4corex35sqmm. |
| 123 | LT Cable above 35sqmm. |
| 124 | Stay set (all sizes) including stay wire etc. |
| 125 | LT Cross Arm. |
| 126 | LT Pin Insulators with H.W. |
| 127 | PCC Pole 9 Mtr. |
| 128 | GI pipe upto (80mm) Strut. |
| 129 | ACSR Rabbit/Weasel/Squerrel. |
| 130 | ACSR Recoon/Dog. |
| 131 | 11KV XLPE Cable upto 185mm2. |
| 132 | Horn Gap Fuse Set. |
| 133 | 11KV Double break Isolator. |
| 134 | Steel. |
| 135 | M.S. Cross Arm (100x50x6) |
| 136 | 11KV Cross Arm with clamps (65x65x6) |
| 137 | Guarding Bracket with clamps. |
| 138 | Lattice Tower. |
| 139 | 11KV Top Hamper. |
| 140 | 11KV Disc Insulator. |
| 141 | 11KV Pin Insulator with Pin. |
| 142 | Pillar Box. |
| 143 | 11/0.4 KV Distribution transformer upto 100KVA capacity |
| 144 | 11/0.4 KV Distribution transformer above 100KVA upto 315KVA Capacity |
| 145 | 11/0.4 KV Distribution transformer 500/630KVA capacity |
| 146 | LA Set. |
| 147 | 11KV Danger Plate. |
| 148 | D.P. Structure set for 11/0.4KV Sub Station. |
| 149 | 11KV Isolator Structure. |
| 150 | 11KV D.O. Fuse Structure. |
| 151 | Shackle Insulator. |
| 152 | Only fixing /Refixing Item |
| 153 | Only laying P.V.C /XLPE insulated & P.V.C. sheathed cable of 1.1 k.v. grade with aluminum conductor of IS 1554 P-1/7098 P-I of Group I of approved make in ground as per IS : 1255 including excavation of 30 cm x 75 cm size trench, 25 Cm thick under layer of sand, 11nd class bricks covering, refilling earth compaction of earth making necessary connection testing etc. as required of size |
| 154 | LT Cable 3.5corex50sqmm. |
| 155 | LT Cable 3.5corex70sqmm. |
| 156 | LT Cable 3.5x185sqmm. |
| 157 | Only fixing of following Lt supporting accessories with nut bolt & clamps made out as per standard Discom's specification |
| 158 | LT Cross Arm. 600 mm |
| 159 | LT Cross Arm. 1200 mm |
| 160 | Only erection of P.C.C. / R.C.C. pole as per REC Manual no 15/1979 conforming to is : 2905/1966 as per requirement of sec 3in alignment, including excavation of pit and back filling with stone aggregate/ boulders and soil in 0.45m consolidating each deposit layer of 0.45 m by ramming and watering etc complete in all respect. 9.0 Mtr. Long (200Kg) as per Discom specification. |
| 161 | Only fixing of strut made out of ‘B’ Class GI pipe 80mm. having base plate of size 300mmX300mmX6mm. (10.0 Mtr. long) by fixing on the pole at top by clamping within position with M.S. flat 50mmX6mm. Clamps and M.S. nuts & bolts and grouting in ground as required (0.4 Mtr)GI pipe Strut 10Mtr. |
| 162 | Only drawing overhead steel core Aluminum conductor (ACSR) ISI marked (IS 398 part II- 96) on existing cross arms through insulator with necessary T&P required including bidding and twisting etc. complete in all respect as required as per Discom specification |
| 163 | 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) |
| 164 | ACSR Recoon/Dog. |
| 165 | Only laying XLPE insulated IS: 7098/II/85 of Group I and approved make H.T. cable for working voltage 11 KV. Earthed direct in ground including excavating of 30 cm x 100 cm size trench 25 cm layer of river sand IInd class brick covering refilling earth compaction of earth making necessary connection testing etc. as required of size. |
| 166 | 11 KV XLPE Cable Upto 185 SQMM |
| 167 | 11 KV XLPE Cable 300SQMM |
| 168 | Only fixing 100 Amp, 11KV horn gap fuse set IS 9385 on Existing DP structure with 6nos 24 KV/22KV post insulator (IS:5350 part III), hot dipped hard ware fuse wire of require size etc. complete in all respect as per specification give by Discom. (Type tested by ERDA/CPRI) |
| 169 | Only fixing of 11KV, 400Amp. 3 Pole central pot rotating double break type isolator (IS: 9921 part I to V) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electoytic copper tubular moving contact with silver/nickel plated at end points, 9 nos. pot insulator of 12KV (IS:2554 & IS:5350 part III), hot dipped galvanizing hard ware, nut bolts, etc. complete in all respect as per specification of Discom. (Type tested by ERDA/CPRI). |
| 170 | Only fixing of Cross arms made out from 100 x 50 x 5 mm MS channel complete in all respect as required including nuts and bolts and clamp as per Discom specification etc. as required. 1.3 mtr, long |
| 171 | 2x1.3 mtr long |
| 172 | Only fixing 11KV Disc Insulator (IS:731/1971) with minimum creepage distance of 300mm. on existing bracket including all accessories like hot dipped GI spindle and nuts etc (as per specification of Discom) B&S type hardware 45KN. |
| 173 | B&S disc Insulator 45KN. |
| 174 | Only fixing 11Kv pin insulator (IS 731/1971) with minimum creep age distance of 300 mm on existing bracket including all accessories like hot dipped GI spindle and nuts etc(as per specification Discom) |
| 175 | Only fixing of piller box made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including knife switch of 400 amp. rating , HRC fuses with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS angle frame of 50 x 50 x 6 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for four outgoing. |
| 176 | only fixing of Star rated aluminium wound distribution Transformer of following rating 11/0.433KV Delta-star Connected, Vector Group Dyn 11, as per BEE star level -2 & BIS approved with losses as defined as per IS 1180 PART 1 2014. including standard accessories like conservator , silica gel breather, radiator, fins, HT cable box & LT cable boxes, off - LTC(+5% to -10% @ 2.5%) winding temperature gauge, first fill of oil, epoxy based paint, including carrying of pre-commission testing & Charging of Transformer.(Transformer should be CTL tested , w/o any extra cost) group 1 |
| 177 | 100KVA |
| 178 | 160KVA |
| 179 | 250KVA |
| 180 | 315KVA |
| 181 | Only fixing double pole structure for 11/0.4 KV substation as per Discom specification complete in all respect as required including nuts and bolts etc. (excluding the cost of poles) made of MS channel 4 nos 100X50X6mm. ans 4nos 75X40X6mm. and MS flat 50X6mm. as per Discome specification. |
| 182 | Only fixing of 11 KV, 400/630A, 20KA/3 sec, out door, Extensible type ring main unit (RMU) in suitable RCC foundatin with 2no Load break switch & 1no. VCB/SF6 circuit breaker with over load, earth fauit short circuit relay, copper bus bar,earthing switch , mechanical on / off / earth indication , voltage presence indicator , ring core protection CT2.5 VA ,10P10 as per transformer rating , shunt trip coil , anti reflex operating handle , right angle boots etc as required |
| 183 | Only drawing of XLPE insulated LT bunched Aluminium conductor cable confirming to IS 14255/1955 and IS 398(Pt-4)/1994 on existing cross arms through I hook with all necessary T&P required including binding and twisting etc. Complete in all respect as required as per Discom specification. |
| 184 | 1x16 sqmm (insulated) |
| 185 | 3x25sqmm +1x25sqmm (insulated) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail