| 1 | Installing one DTR Meter with box (normal size 40x25x100cm) on existing poles including fixing of 3 CTs on bus bar, laying and termination of control cable using proper lugs, fixing of meters, capacitors, control fuses and giving the complete connections including conveyance of materials. |
| 2 | Transporting poles by hired vehicle to a distance upto 5km and carrying upto 4 numbers of poles excluding loading& unloading charges. |
| 3 | Fitting and erecting one HT Double Pole Structure using PSC pole in position including fitting 2 channel cross arms, digging and back fillingpit in ordinary soil, drawing sufficient length of GI earthing leads through all cross arms to the ground for earthing (excluding provision of earthing). |
| 4 | Additional rate for providing one discset,PGclampetc.complete,onany type of HT pole for making cut point. |
| 5 | Fitting 5 channel cross arms, AB switch, DO fuse, LA(Ord), HT < connections upto OH lines, etc. on existing DP structure, Fixing distribution box/provision for one set (3No.) of LT fuses, , drawing sufficientlengthofGIearthingleadstothegroundforearthing,excluding provision of earthing & mounting of Transformer on poles. |
| 6 | Fitting one Additional Vcros sar m ine xisting single pole including conveyance of materials. |
| 7 | Drilling hole of various sizes on existing Channel/Cross Arm. |
| 8 | Labour charges for loading HTPSC pole from the stacking place and unloading the same at work site (transportation by any vehicle). |
| 9 | Fitting and providing one HT Stay for 11kV pole, including digging and back filling pit in ordinary soil. |
| 10 | Providing Transformer fencing to a height of 1.8 m above ground level using MS Angle frames of size ISA 50x50x6mm for outer frame, 2 runs of 40 x 6 MS flat for horizondal brasing and grills with MS rods 8 mm Dia @ 10cm c/c for verticals, providing gate with locking arrangements, providing danger board & name board, embeding the legs in cement concrete1:2:4,footingofsize30cmx30cmx50cm,paintingwithsynthetic enamel paint two coats over one coat of iron primer etc complete, incl cost of transportation |
| 11 | Cleaning and levelling of transformer yard/RMU, spreading 40 mm broken stone in yard for a thickness of 10 cm above bed of 10 cm thick 6 mm broken stone, after constructing a curb wall of height 20cm above ground and 10cm below level including cost of all materials and charges for conveying, spreading, consolidating etc. |
| 12 | Erectingone100kVATransformertoexistingDPandgivingconnections, including loading from TMR/SRS/other stacking place & unloading at site but excluding cost for transporting transformer. |
| 13 | Transporting Transformers by hired vehicle to a distance upto 5km and carrying upto 2 numbers of 63/100/160/250kVA Transformers / Ring Main Units excluding loading& unloading charges. |
| 14 | Insertion of one HT PSC pole in existing OH line including digging & backfilling pit in ordinary soil, fitting cross arm, insulators, binding etc., drawing sufficient length of GI earth leads to the ground for earthing (excluding provision of earthing). |
| 15 | ProvidingoneCoilEarthusingNo.8GI-earthwire(50mmdia,115turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling. |
| 16 | Providing one Earth using GI earth pipe of size 38.1mm dia, 2.5m length including digging separate pit (0.45x0.45x2.5m) at a minimum distance of 1.5m away from the pole/structure and maintaining standard distance between different earth pipes in ordinary soil & backfilling. |
| 17 | Fitting and erecting on eHT PSC Single Pole inposition,includingfitting crossarm,diggingandbackfillingpitinordinarysoil(asperstandards),drawing sufficient length of GI earthing leads from F clamp through Vcross arm to the ground for earthing (excluding provision of earthing |
| 18 | Fitting one Additional 75x40mm, 1.8mChanne lcrossarm in existing single pole including conveyance of materials. |
| 19 | Fitting one set AB switch on existing DP, giving connection and drawing sufficientlengthofGIearthingleadstothegroundforearthing,excluding provision of earthing. |
| 20 | Fitting one Additional 2.4m/3m Channe lcrossarm(100x50x6mm),in existing 11kV DP including conveyance of materials. |
| 21 | Fitting and providing one HT Fly stay for 11kV pole using HT PSC pole includingdiggingandbackfillingpitsinordinarysoil,drawingsufficient lengthofGIearthleadstothegroundforearthing(excludingprovisionof earthing). |
| 22 | Stringing of one km 11kV line with ACSR Raccoon (3 conductors) after fitting insulators and giving jumper connections including cutting and removing tree branches wherever necessary excluding cut point works. |
| 23 | Fitting an d providing one Strut using HTPSC pol e including diggingand back filling pit in ordinary soil. |
| 24 | Quoted Amount of BOQ1 in figures |
| 25 | GST Rate in percentage Please Enable Macros to View BoQ information |