Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Design, Project Management Consultancy (PMC) Services and Construction of Mass Manufacturing Facility for EM SBU at BEL – Palasamudram(AP). |
| 2 | Amount after unconditional rebate |
| 3 | Total Of BOQ 3 and Boq 4 |
| 4 | Schedule 1 - Part- I - DSR 2023 including correction slip & Landscaping (DSR 2020) |
| 5 | Schedule 2 - Part- II - CIVIL WORK - AP SR and KPWD SR |
| 6 | Schedule - 3 - Part- III- Civil Work-Market rate |
| 7 | Schedule 4 - ELECTRICAL-ELV and HVAC |
| 8 | Schedule - 5 - ELECTRICAL-Fire Fighting Works, Lifts and Electrical Internal |
| 9 | Schedule - 6 - EXTERNAL ELECTRICAL WORKS |
| 10 | EARTH WORK |
| 11 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge - All kind of soil |
| 12 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. - Ordinary rock |
| 13 | Hard Rock ( Blasting Prohibited) |
| 14 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m |
| 15 | Pipes, cables etc, not exceeding 80 mm dia |
| 16 | Pipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia |
| 17 | Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm |
| 18 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 19 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials |
| 20 | Supplying and filling in plinth with sand under floors, including watering,ramming, consolidating and dressing complete. |
| 21 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 22 | Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material |
| 23 | Beyond 30 cm girth upto and including 60 cm girth |
| 24 | Beyond 60 cm girth upto and including 120 cm girth |
| 25 | Beyond 120 cm girth upto and including 240 cm girth |
| 26 | Above 240 cm girth |
| 27 | PCC WORK |
| 28 | 1:4:8 (1 Cement : 4 coarse sand (zone-III)derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources ). |
| 29 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills,fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing:1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 30 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 31 | Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75 mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 32 | Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand(zone-III) derived from natural sources: 4 graded stone aggregate 20mm nominal size) |
| 33 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification. |
| 34 | Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil |
| 35 | RCC WORK |
| 36 | Centering and shuttering including strutting, propping etc. and removal of form for: |
| 37 | Foundations, footings, bases of columns, etc. for mass concrete |
| 38 | Walls (any thickness) including attached pilasters,butteresses, plinth and string courses etc |
| 39 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 40 | Edges of slab and Breaks in floors & walls -Under 20cm wide |
| 41 | Weather shade, Chajjas, corbels etc., including edges |
| 42 | Suspended floors, roofs, landings, balconies and access platform |
| 43 | Lintel, Beams, plinth beams, girders, bressumers and cantilevers |
| 44 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc.,-Suspended floors, roofs, landing, beams and balconies(Plan area to be measured) including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). |
| 45 | Providing, hoisting and fixing above plinth level up to floor five level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but , excluding cost of reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derivedfrom natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 46 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.-Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 47 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level-Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 48 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections |
| 49 | Extra for laying reinforced cement concrete in or under water and/ or liquid mud, including cost of pumping or bailing out water and removing slush etc., complete.Note For Item No. 5.31:- The quantity will be calculated by multiplying the depth measured from the subsoil water level up to the centre of gravity of the R.C.C. under subsoil water with the quantity of R.C.C. in cubic metre executed under subsoil water. The depth of centre of gravity shall be reckoned correct to 0.1 m (0.05 m or more shall be taken as 0.1 m and less than 0.05 m ignored). No extra payment shall be made for placing reinforcement or centering & shutteringunder sub - soil water conditions. |
| 50 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement-All works upto plinth level |
| 51 | Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 52 | Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 53 | All works above plinth level upto V level-Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 54 | All works above plinth level upto V level-Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 55 | Masonry works |
| 56 | Providing and laying Autoclaved Aerated concrete (AAC) blocks masonry 150mm to 300 mm thick with Grade- I AAC blocks of density 551 to 650 kg/cum conforming to IS 2185 (part 3) in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately). |
| 57 | Brick work with common burnt clay F.P.S (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 58 | Cladding Works |
| 59 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.-Granite stone slab colour black, Cherry/Ruby red |
| 60 | Area of slab upto 0.50 sqm |
| 61 | Area of slab over 0.50 sqm |
| 62 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.-Granite work |
| 63 | Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete. |
| 64 | Extra for providing opening of required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 65 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 66 | Providing and fixing cramps of required size & shape in RCC/ CC / Brick masonry backing with cement mortar 1:2 ( 1 cement : 2 coarse sand), including drilling necessary hole in stones and embedding the cramp in the hole (fastener to be paid separately). Stainless steel cramps |
| 67 | Wood & PVC Works |
| 68 | Providing and fixing factory made ISI marked un-insulated metal fire rated doorset assembly for all non egress application areas like shafts etc. consisting galvanized iron steel frame and single leaf shutter including necessary hardware accessories conforming to FD 120 UD classification of IS 3614:2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS: 277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS 17518 (Part -1): 2022 Frame: The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS: 4351. The smoke seal material shall be of EPDM tested in accordance with ASTM E-84 of minimum size 10x4 mm, fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all four sides to masonry wall opening with CSK/Hex headed fasteners of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 4 number at each on vertical sides (up to 2100 mm height) and 2 numbers each on top and bottom sides.Door shutter:The double skin single leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffeners as per IS: 16074 including Resin bonded honey comb paper core infill material of density 5 kg/cum. The door shutter shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935: 2002 or butt hinges as per IS 12817 both, of minimum size 100x75x3 mm @ minimum 4 numbers up to 2100 mm / 2400 mm height or as per test evidence, which ever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. |
| 69 | Hardware Accessories :Fire doorset assembly shall-be provided with one number fire rated SS 304 shaft mortise dead lock, one number 50-80 mm Back Set with minimum 20 mm Square forend with allen key including SS304 dead strike plate conforming to IS: 16015:2022/EN 12209, one number recessed flush pull handle (SS304) of minimum size 40 mm x 120 mm, as approved by Engineer-in-Charge.Finishing:Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS: 13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge.Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. |
| 70 | Single leaf un-insulated metal fire rated door and frame of FD 120 UD with 120 minutes integrity only as per lS 3614:2021 -For non egress application like area shafts etc |
| 71 | Providing and fixing factory made ISI marked un-insulated metal fire rated doorset assembly, for all egress applications areas ike utility rooms and service areas etc, consisting of galvanized iron steel frame and single leaf shutter including necessary hardware accessories conforming to FD 120 UD classification of IS: 3614 2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick Gi Sheet with minimum 120 GSM Zinc coating as per IS 277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS 17518 (Part -1): 2022FrameThe frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS: 4351. The smoke seal material shall be of EPDM tested in accordance with ASTM E-84 of minimum 10 x 4 mm, fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fasteners of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical side and 2 numbers on top side.Door Shutter: The double skinned single leaf door shutters shall be consisting of minimum 46 mm thick and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded honey comb paper core infill material of density 5 kg/cum. Door leaf shall be provided with vision panel, having maximum area of 0.12 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The door shutter shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hinges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws.All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. |
| 72 | Accessories Hardware :Fire doorset shall be provided with one number fire rated SS 304 grade mortise dead lock, 50-80 mm backset with minimum 20 mm square forend with allen key including Escutcheon of stainless steel (SS304) with 65/70 mm cylinder both side key conforming to EN: 12209 / IS 16015:2022, one pair of D type pull handle of stainless steel (SS304) of minimum 22 mm dia centre to centre distance of 300 mm back to back fixing with spindle, one number 120 minutes fire rated surface mounted heavy duty door closer of size EN 3-5 with standard arm of desired finish conforming to IS: 3564/EN1154Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS: 13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge.Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. |
| 73 | Single leaf un-insulated metal fire rated doorset of FD 120 UD classification with 120 minutes integrity and as per IS 3614:2021- for non egress applications like utility room and service area etc. |
| 74 | Providing and fixing factory made ISI marked partially insulated metal fire rated doorset assembly, for staircase / exit pathway and refuge areas applications, consisting of galvanized iron steel frame and double leaf shutter including necessary hardware accessories, conforming to FD 120 PI classification of IS 3614:2021 with fire rating of 120 minutes integrity and 30 minutes insulation. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS: 277. The entire fire rated doorset assembly shall be tested in latched condition as per IS 17518 (Part -1) 2022Frame:The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joint (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS 4351. The smoke seal material shall be of EPDM tested in accordane with ASTM E-84 of minimum size 10 x 4mm, fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed to the three sides to masonary wall opening with CSK/Hex headed fastner of minimum 8 mm dia size and minimum 80mm long hot dip galvanized with 8mm dia Polyamide sleeves @ 5 number at each on vertical sides and 3 number on top side Door shutter:The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool / ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. |
| 75 | The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935: 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hinges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware :Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564 / EN 1154, and one number surface mounted door coordinator for sequencing of closing.Finishing:Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge.Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. |
| 76 | Double leaf partially Insulated metal fire rated doorset of FD 120 Pl classification with 120 minutes integrity and 30 minutes insulation as per IS 3614:2021 for Staircase/ Exit pathway / Refuge area etc. |
| 77 | Steel Works |
| 78 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete |
| 79 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete |
| 80 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces |
| 81 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete-Hot finished welded type tubes |
| 82 | Providing and fixing circular / Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron / M.S. sheet box by means of 3.3 mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing |
| 83 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as requir-In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all completeed. |
| 84 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 85 | Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge. |
| 86 | 10 X 80 mm |
| 87 | 10 X 120 mm |
| 88 | 10 X 80 mm |
| 89 | 10 X 120 mm |
| 90 | Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 91 | Flooring |
| 92 | Providing and fixing 2nd class teak wood plain lining tongued and grooved, including wooden plugs complete with necessary screws and priming coat on unexposed surface--12mm thick |
| 93 | Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade : (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) :Red sand stone - exposed face fine dressed with rough backing.-40mm thick |
| 94 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6mm thck board backing:shade with 6 mm thick hard board backing : Rectangular shape 1500x450 mm |
| 95 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25mm thick |
| 96 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete |
| 97 | 38 mm thick wood block flooring of first class teak wood laid over 25 mm thick leveling layer of cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 10 mm nominal size) to be paid separately, coated with a thin layer of hot bitumen penetration 80/25 (blown type) @ 2.45 kg per sqm, including fixing blocks in position after dipping in hot bitumen (blown type) up to half depth, planed, levelled smooth and finished complete. |
| 98 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement:4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed Vitrified Tile polished finish of size- 600X600 mm |
| 99 | Providing and laying vitrified tiles in different sizes (thickness to be spcified by manufacturer) with water absorption less than 0.08% and conforming to IS 15622 of approved make, in all colors & shade, in skirting, riser of steps, over 12mm thick bed of cement mortar 1:3 (1 cement: 3 course sand), jointing with grey cement slurry @3.3 kg/sqm including grouting the joint with white cement & matching pigments etc. complete-Size of Tile 600 x 600 mm |
| 100 | Glazed Vitrified tiles Matt/Antiskid finish of size-Size of Tile 600 x 600 mm |
| 101 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.-Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent |
| 102 | 62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 103 | Cement Plaster skirting upto 30cm height, with cement mortar 1:3 ( 1 cement : 3 coarse sand), finised with a flaoting coat of neat cement)-18mm thick |
| 104 | Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of: (a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100mm x 100mm x 3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully threaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug. (b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge. (c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with lightweight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product.-450 mm Finished Floor Height (FFH) |
| 105 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25mm thick |
| 106 | Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement:4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed Vitrified tiles Matt/Antiskid finish of size |
| 107 | Chequered Precast cement concrete tiles 22mm thick in footpath & courtyard, jointed with neat cmenet slurry-Light shade pigment using white cement mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 course sand) |
| 108 | Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 109 | Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. |
| 110 | Roofing Works |
| 111 | Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner. |
| 112 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarsesand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 113 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with sealring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.-110 mm dia |
| 114 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. |
| 115 | Coupler-110mm dia |
| 116 | Single pushfit Coupler- 110mm dia |
| 117 | Single tee with door-110x110x110mm |
| 118 | Single tee with door-110x110x110mm |
| 119 | Bend 87.5°-110mm bend |
| 120 | Shoe (Plain)-110mm shoe |
| 121 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 122 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :12.5 mm thick tapered edge Glass Reinforced gypsum (GRG) Board conforming to IS: 2095- (Part 3) :1996 (Board with BIS certification marks) |
| 123 | Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’. Bottom exposed with 24 mm of all T-sections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.Note :- Only calcium silicate false ceiling area will be measured from wallto wall. No deduction shall be made for exposed frames/opening (cut outs)having area less than 0.30 sqm.The calcium silicate ceiling tile shall haveNRC value of 0.50 (Minimum), light reflection > 85%, non- combustible asper B.S. 476 part IV, 100% humidity resistance and also having thermalconductivity <0.043 w/mK. |
| 124 | Finishing Works |
| 125 | 12 mm cement plaster of mix : 1:6 (1 cement:6 coarse sand) |
| 126 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand) |
| 127 | Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. |
| 128 | 6mm cement palster of mix:1:3 (1 cement : 3 fine sand) |
| 129 | Providing and applying white cement based putty of average thickness 1mm , of approved brand and manufacturer , over the plastered wall surface to prepare the surface even and smooth complete. |
| 130 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new work |
| 131 | Polishing on wood work with ready mixed wax polish of approved brand and manufacture :new work |
| 132 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm |
| 133 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour.two coats |
| 134 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre |
| 135 | Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. |
| 136 | Aluminium Works |
| 137 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 138 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimumthickness of powder coating 50 micron) |
| 139 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade I Type II, in panelling fixed in aluminium doors, windows shutters and prtition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge.Pre-laminated particle board with decorative laminated on both sides |
| 140 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paidin basic item):With float glass panes of 8 mm thickness (weight not less than 20 kg/sqm) |
| 141 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness |
| 142 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete.Upto 5mm depth and 5mm width |
| 143 | Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete |
| 144 | Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineer-in-charge complete. 510x19mm |
| 145 | Providing and fixing aluminium casemnet window fasterner of required length for aluminium windows with necessary screws etc. completePowder coated minimum thickness 50 micron aluminium |
| 146 | Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete |
| 147 | Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-chargePowder coated minimum thickness 50 micron aluminium |
| 148 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). |
| 149 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 150 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper |
| 151 | Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levellingto required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in- charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately).Cement concrete manufactured in automatic batching plant (RMC plant) including transportation to site in transit mixer |
| 152 | Construction of dry lean cement concrete sub base over a prepared subgrade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineer-in- charge. |
| 153 | Extra for providing and mixing hardening compound of approved quality as per manufacturer’s specification in cement concrete. |
| 154 | Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as perdirection of the Engineer-in-ChargeProviding and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. |
| 155 | Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30 ) |
| 156 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as perdirection of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 157 | Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge. |
| 158 | Providing and laying factory made chamfered edge Cement Concretepaver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge60 mm thick C.C. paver block of M-35 grade with approved color design and pattern |
| 159 | Water Proofing |
| 160 | Grading roof for water proofing treatment withgraded stone aggregate 20 mm nominal size) |
| 161 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50 mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. |
| 162 | For vertical surface two coats @ 0.70 kg per sqm per coat |
| 163 | For horizontal surface one coat @1.10 kg per sqm. |
| 164 | Providing and applying of swellable type water stop tape, 19 mm x 25 mm thick in linear metre (expansive nature) for construction joints treatment of RCC structure such as raft slab, retaining walls, water storage tank and at the junctions of raft slab with the retaining walls etc.. After cleaning the surface, one coat of required primer for swellable water stop tape shall be applied throughout the length of the joint @3.78 litre per 240 running metre. Over the primed surface swellable type water stop tape shall be placed. The work shall be carried out all complete as per specification and the direction of the Engineer-In-Charge. The product performance shall carry guarantee for 10 years against any leakage. |
| 165 | Glazing works |
| 166 | Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings, the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).The weight of aluminium extruded section shall be taken for purpose of payment. |
| 167 | Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: |
| 168 | a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: |
| 169 | b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. |
| 170 | c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. |
| 171 | d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. |
| 172 | e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, roviding suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid,installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and unctional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and rotection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance haracteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. |
| 173 | Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this subhead. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places. |
| 174 | Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. |
| 175 | The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and Importance of the work.Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 |
| 176 | 1.Performance Laboratory Test for Air Leakage Test (-50pa to – 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr. |
| 177 | 2.Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331- 09 testing method for a range up to 2000 ml. |
| 178 | 3.Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml” |
| 179 | 4.Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME- 330-10 testing method for a range upto 50 mm” |
| 180 | 5.Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test” Tests to be conducted on site. |
| 181 | 6.Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml |
| 182 | 6.Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml |
| 183 | Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4-point cremone locking sets with stainless steel plates, handles, buffers etc. all complete as per the architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-charge. |
| 184 | Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor |
| 185 | Payment for fixing of IGU Panels in the curtain glazing is including in cost of item No. 25.2) |
| 186 | For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.“ |
| 187 | (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. |
| 188 | Providing, fabricating and supplying shadow box of required size and shape, for fixing in the spandrel portion of the structural glazing, in linear as well as curvilinear portions of the building by providing semi -rigid, inorganic, non-combustible fibre glass wool insulation 50 mm thick, conforming to IS: 8183 and BS: 3958 Part 5. The insulation layer shall have facing (factory bonded on surface # 1 of the fibre glass insulation layer), of black non-woven fibre glass tissue of nominal thickness 0.5 mm and nominal mass not less than 60 gm /sqm, made of randomly oriented glass fibres distributed in a binder by a wet-lay process including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick cement board including SS rivets, nuts, bolts, washers etc complete. |
| 189 | Sanitary Installations |
| 190 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 191 | Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete. |
| 192 | Providing and fixing Stainless Steel AISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : |
| 193 | Kitchen sink with drain board-510x1040 mm bowl depth 250 mm |
| 194 | Kitchen sink without drain board-610x460 mm bowl depth 200 mm |
| 195 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.-15mm nominal bore |
| 196 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931-15mm nominal bore |
| 197 | Providing and fixing toilet paper holder :C.P. brass |
| 198 | Providing and fixing CP Brass 32 mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 199 | Providing & fixing chrome plated brass battery based infrared sensor operated pillar cock, having foam flow technology.-15 mm nominal bore |
| 200 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. |
| 201 | Providing and fixing uplasticised PVC connection pipe with brass unions :45 cm length- 15mm nominal bore |
| 202 | Water Supply |
| 203 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 204 | 15 mm nominal outer dia Pipes |
| 205 | 20 mm nominal outer dia Pipes |
| 206 | 25 mm nominal outer dia Pipes |
| 207 | 32 mm nominal outer dia Pipes |
| 208 | 40 mm nominal outer dia Pipes |
| 209 | 50 mm nominal outer dia Pipes |
| 210 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings and fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 211 | 15 mm nominal outer dia Pipes |
| 212 | 20 mm nominal outer dia Pipes |
| 213 | 25 mm nominal outer dia Pipes |
| 214 | 32 mm nominal outer dia Pipes |
| 215 | Providing and fixing Stainless Steel pipe and fitting of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards complete with press type fitting (fitting shall be paid for separately) including fixing of the pipe with clamps at 1.00 m spacing including cutting and making good the walls including testing of joints complete as per direction of Engineer-in-charge. (The pipe length inserted in the fitting shall not be measured for payment)-internal work- exposed on wall |
| 216 | 15 mm nominal outer dia Pipes |
| 217 | 20 mm nominal outer dia Pipes |
| 218 | 25 mm nominal outer dia Pipes |
| 219 | 32 mm nominal outer dia Pipes |
| 220 | Providing and fixing Stainless Steel pipe and fitting of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards complete with press type fitting (fitting shall be paid for separately) including fixing of the pipe with clamps at 1.00m spacing and also including cutting of chases and making good the walls including testing of joints complete as per direction of Engineer -in-charge. (The pipe length inserted in the fitting shall not be measured for payment)Internal work-Concealed pipe |
| 221 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 222 | For 22 mm outer dia pipe |
| 223 | For 28 mm outer dia pipe |
| 224 | For 35 mm outer dia pipe |
| 225 | For 42 mm outer dia pipe |
| 226 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards with V-profile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. |
| 227 | For 28 mm x 22 mm outer dia pipe |
| 228 | For 35 mm x 28 mm outer dia pipe |
| 229 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 230 | For 22 mm outer dia pipe |
| 231 | For 28 mm outer dia pipe |
| 232 | For 35 mm outer dia pipe |
| 233 | For 42 mm outer dia pipe |
| 234 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 235 | For 28 mm outer dia pipe |
| 236 | For 35 mm outer dia pipe |
| 237 | For 42 mm outer dia pipe |
| 238 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 239 | For 28 mm x 22 mm outer dia pipe |
| 240 | For 35 mm x 28 mm outer dia pipe |
| 241 | For 42 mm x 35 mm outer dia pipe |
| 242 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standard with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 243 | For 22 mm outer dia X 3/4” nominal dia threaded |
| 244 | For 28 mm outer dia X 1” nominal dia threaded |
| 245 | For 35 mm outer dia X 1-1/4” nominal dia threaded |
| 246 | For 42 mm outer dia X 1-1/2”nominal dia threaded |
| 247 | Providing and fixing required Stainless Steel Fitting of press fit design of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standard with V-profile and with O-ring sealing gasket of EPDM material of required dia as per direction of Engineer-in-charge. |
| 248 | For 22 mm outer dia X 3/4” nominal dia threaded |
| 249 | For 28 mm outer dia X 1” nominal dia threaded |
| 250 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 251 | 20 mm nominal bore |
| 252 | 25 mm nominal bore |
| 253 | 32 mm nominal bore |
| 254 | 40 mm nominal bore |
| 255 | 50 mm nominal bore |
| 256 | 65 mm nominal bore |
| 257 | 80 mm nominal bore |
| 258 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 259 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge |
| 260 | 65 mm nominal outer dia Pipes |
| 261 | 80 mm nominal outer dia Pipes |
| 262 | 100 mm nominal outer dia Pipes |
| 263 | 150 mm nominal outer dia Pipes |
| 264 | SOIL, WASTE, VENT & RAIN WATER PIPES |
| 265 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. |
| 266 | 75 mm diameter |
| 267 | 110 mm diameter |
| 268 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. |
| 269 | Coupler |
| 270 | 75 mm |
| 271 | 110 mm |
| 272 | Single pushfit Coupler |
| 273 | 75 mm |
| 274 | 110 mm |
| 275 | Single tee without door |
| 276 | 75x75x75 mm |
| 277 | 110x110x110 mm |
| 278 | Bend 87.5° |
| 279 | 75 mm bend |
| 280 | 110 mm bend |
| 281 | Shoe (Plain) |
| 282 | 75 mm Shoe |
| 283 | 110 mm Shoe |
| 284 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 285 | 75 mm |
| 286 | 110 mm |
| 287 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 288 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 289 | Providing and fixing M.S. holder bat clamp of approved design to sand cast iron/ cast iron (spun) pipes comprising of M.S. flat brackets made of 50x5 mm flat of specified shape, projecting 75 mm outside the wall surface and fixed on wall with 4nos, 6 mm dia expansion hold fasteners, including drilling necessary holes in brick wall/ CC/ RCC surface and the cost of bolts etc. The pipes shall be fixed to the already fixed brackets with the help of 30 mm x1.6 mm galvanised M.S. flats of specified shape and of total length 420 mm and shall be fixed with M.S. nuts, bolts, & washers of size 25x6 mm, one bolts on each side of the pipe. |
| 290 | Total bracket length 580 mm of approved shape and design(For Single 100mm dia pipe) |
| 291 | Total bracket length 810 mm of approved shape and design(For Two 100mm dia pipe) |
| 292 | Total bracket length 1040 mm of approved shape and design(For Three 100mm dia pipe) |
| 293 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x 300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: |
| 294 | 100x100 mm size P type-With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 295 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 296 | 1:5:10 (1 cement : 5 coarse sand (zone-ill) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 297 | External Plumbing-Sewerage System |
| 298 | Excavating trenches by mechinical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :All kinds of soil-Pipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia |
| 299 | Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m : |
| 300 | Ordinary rock :Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 301 | Hard rock (blasting prohibited):Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 302 | Extra for excavating trenches for pipes, cables, etc. in ordinary/hard rock exceeding 1.5 m in depth but not exceeding 3 m. (Rate is over corresponding basic item for depth upto 1.5 metre) |
| 303 | Ordinary rock :Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 304 | Hard rock (blasting prohibited):Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 305 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge.-All kinds of soil |
| 306 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. |
| 307 | Ordinary rock |
| 308 | Hard rock (blasting prohibited) |
| 309 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials.- ordinary or hard rock |
| 310 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 311 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 312 | Extra for plastering on circular work not exceeding 6 m in radius: In one coat |
| 313 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth lev1:5:10 (1 cement : 5 coarse sand (zone-ill) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources)el : |
| 314 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 315 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 316 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : |
| 317 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 318 | Extra for depth for manholes :Size 90x80 cm-With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 319 | Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand), inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : |
| 320 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 321 | Extra depth for circular type manhole 0.91m internal dia (at bottom) beyond 0.91 m to 1.67 mWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 322 | Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : |
| 323 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 324 | Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 325 | Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :2.30 m deep with SFRC Cover and frame (heavy duty HD- 20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : |
| 326 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 327 | Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m : |
| 328 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 329 | Water Supply System |
| 330 | Excavating trenches by mechinical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :All kinds of soil |
| 331 | Pipes, cables etc, not exceeding 80 mm dia. |
| 332 | Pipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia |
| 333 | Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m :Ordinary rock : |
| 334 | Pipes, cables etc. not exceeding 80 mm dia |
| 335 | Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 336 | Hard rock (blasting prohibited)Pipes, cables etc. not exceeding 80 mm dia |
| 337 | Hard rock (blasting prohibited)Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 338 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. |
| 339 | 40 mm dia nominal bore |
| 340 | 50 mm dia nominal bore |
| 341 | 65 mm dia nominal bore |
| 342 | 80 mm dia nominal bore |
| 343 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 344 | 40 mm diameter pipe |
| 345 | 50 mm diameter pipe |
| 346 | 65 mm diameter pipe |
| 347 | 80 mm diameter pipe |
| 348 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work : |
| 349 | 40 mm diameter pipe |
| 350 | 50 mm diameter pipe |
| 351 | 65 mm diameter pipe |
| 352 | 80 mm diameter pipe |
| 353 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 354 | 20 mm nominal bore |
| 355 | 25 mm nominal bore |
| 356 | 32 mm nominal bore |
| 357 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in reinforced cement concrete slab 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), including necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 358 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), including necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 359 | Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), including necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 360 | TUBE well |
| 361 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level.Rocky strata including Boulders-300mm dia |
| 362 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge-200 mm nominal size dia |
| 363 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge-200 mm nominal size dia |
| 364 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 365 | Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineerin- charge. |
| 366 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by “V” notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 367 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: |
| 368 | 200 mm dia |
| 369 | 200 mm clamp |
| 370 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I)-200 mm dia |
| 371 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :80mm nominal bore |
| 372 | Providing and fixing gun metal non- return valve of approved quality (screwed end) :80mm nominal bore-vertical |
| 373 | External Drainage System |
| 374 | Excavating trenches by mechinical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :All kinds of soil-Pipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia |
| 375 | Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m :Ordinary rock :Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 376 | Hard rock (blasting prohibited):Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 377 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge-all kinds of soil |
| 378 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. |
| 379 | Ordinary rock |
| 380 | Hard rock (blasting prohibited) |
| 381 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 382 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:5:10 (1 cement : 5 coarse sand (zone-ill) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 383 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 384 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 385 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 386 | 1:3:6 (1 Cement : 3 coarse sand (zone-ill) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 387 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement-All works upto plinth level |
| 388 | Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 389 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 390 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 391 | Foundations, footings, bases of columns, etc. for mass concrete |
| 392 | Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 393 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 394 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : |
| 395 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 396 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 397 | Rain Water Harvesting System |
| 398 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level-Rocky strata including Boulders-300 mm dia |
| 399 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge-200 mm nominal size dia |
| 400 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge-200 mm nominal size dia |
| 401 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 402 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineerin-charge. |
| 403 | Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge. |
| 404 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineerin-charge. |
| 405 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I)-200 mm dia |
| 406 | Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape and approved quality-H D-20-Circular shape 560mm internal diameter |
| 407 | SANITARY INSTALLATIONS |
| 408 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required: using White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 409 | Supply & Fixing of 2 in 1 Bibcock cum Health Faucet with1m long tube and wall hook , Chrome Finish with 7 yearswarranty |
| 410 | Supply & fixingsoap dish: with 7years warranty:Chromeplated |
| 411 | Providing and fixing Liquid soap dispenser made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class b.Premium |
| 412 | Supply & Fixing of Towel ring with 7 years warranty:Chrome plated |
| 413 | Providing and fixing Stainless Steel Grab Bar 600 mm Long with all concealed fitting arrangements & all necessary accesories complete - Class a. Economy |
| 414 | WATER SUPPLY |
| 415 | a)S & F Gunmetal (GM) Ball valve with SS Ball and SSSpindle as per IS - Class - I, Indian make heavy type - 20mm NB Size and |
| 416 | a)S & F Gunmetal (GM) Ball valve with SS Ball and SSSpindle as per IS - Class - I, Indian make heavy type - 25mm NB Size |
| 417 | a)S & F Gunmetal (GM) Ball valve with SS Ball and SSSpindle as per IS - Class - I, Indian make heavy type - 40mm NB Size |
| 418 | a)S & F Gunmetal (GM) Ball valve with SS Ball and SSSpindle as per IS - Class - I, Indian make heavy type - 50mm NB Sizea)S & F Gunmetal (GM) Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 50mm NB Size |
| 419 | b) - do - labour charges only |
| 420 | Manufacture, Supply and delivery of CI Wafer Lug type Butterfly Valves conforming to IS 13095/1991 (Reaffirmed 1998) excluding transportation, CED and taxes etc., complete. Operation done with worm actuator ISI marked - 100 mm dia |
| 421 | SOIL, WASTE, VENT & RAIN WATER PIPES |
| 422 | Providing and fixing Unplasticised Polyvinyl Chloride (uPVC) pipes, for cold water supply including all uPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work |
| 423 | 80 mm nominal dia Pipes |
| 424 | 100 mm nominal dia Pipes |
| 425 | Providing PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. |
| 426 | PVC pipes 63mm dia., 6 kg/sqcm & class 3 |
| 427 | PVC pipes 75mm dia., 6 kg/sqcm & class 3 |
| 428 | Supplying of special moulded variety PVC couplers as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark and with its latest amendments to walk site etc. complete |
| 429 | Supply and delivery at site special moulded variety PVC elbows as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark with its latest amendments110mm dia PVC elbows |
| 430 | Supply and delivery at site special moulded variety PVC tee as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark with its latest amendments-110mm dia PVC tee |
| 431 | Supply and delivery at site special moulded variety PVC bend as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark with its latest amendments-110mm dia PVC bend |
| 432 | Supply and delivery at site special moulded variety PVC service saddles as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark with its latest amendments-110mm dia PVC service saddles |
| 433 | Supply and delivery at site special moulded variety PVC reducer as per IS 7834/ 1987 and fabricated as per IG124/ 1984 with ISI mark with its latest amendments |
| 434 | Providing, Laying and Fixing of GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings (excluding the cost of fittings) with cuts and threads wherever necessary, including testing for water tightness, with all lead and commissioning. (contractor will make his own arrangements for procuring water for testing) For:Heavy Duty GI Pipe etc. complete-Heavy Duty GI pipe of 100mm dia |
| 435 | Sewerage System |
| 436 | Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey. |
| 437 | RCC NP3 Class pipe of 250 mm dia |
| 438 | RCC NP3 Class pipe of 300 mm dia |
| 439 | Water Supply System |
| 440 | Providing, Laying and Fixing of GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings (excluding the cost of fittings) with cuts and threads wherever necessary, including testing for water tightness, with all lead and commissioning. (contractor will make his own arrangements for procuring water for testing) For:Heavy Duty GI Pipe etc. complete. |
| 441 | Providing, fixing, testing and commissioning uPVC Pipes complete (I:S 4985 class-V, 10 kg/sq.cm) with all uPVC fittings e.g. elbows, tees , reducers, unions, plugs, bends of all degree etc. and jointing with solvent cement joints complete as per direction of Engineer in Charge. |
| 442 | 20mm OD |
| 443 | 25mm OD |
| 444 | 32mm OD |
| 445 | 40mm OD |
| 446 | 50mm OD |
| 447 | 90mm OD |
| 448 | Civil Works |
| 449 | Designing, fabricating, testing, supplying & erecting the Pre-Engineered structure steel superstructure of Warehouse connected to PCB & Admin Building, as per tender drg and details given below. Warehouse connected to PCB & Admin Building - Warehouse of size 74.50 X 47.45 m as per Arch./tender Drawing & technical specification. |
| 450 | The job shall be executed with supply and erection of steel column, steel rafters, ties, bracing, purlins, sag rods, sag angles, nut bolts, washers,runners, high strength anchor bolts etc., insulated panels in roof and side cladding and gable end cladding as per technical specifications and GS profile sheets on both sides of insulated panels in roof, side clading & gable end cladding as per the technical specifications. The work also including supply,testing and fixing holding down bolts at beam/column location, base plates etc whever required and the other embedment, screw and EDP washers, Polycarbonate sheets 3mm thick of desired close fitting profile, barge board, ridges and hips etc., flashings , gutters , roof water take down pipes and other suitable accessories to provide a weatherproof and well detailed structure. |
| 451 | The work also involves providing and fixing suitable steel frame both hand and electrically operated rolling shutters including motor and starter. All the steel work including rolling shutters shall be mechanically cleaned and given 2 hour fire rated paint of approved Colour. Necessary openings and provisions for fixing electrical conduits, suspension of false ceiling, firefighting, lighting fixtures, and other related services shall be included in the scope of PEB works. The entire work shall be as per specification & scope as detailed in this tender. The contractor shall submit detailed design & drawings for complete warehouse including designs of RCC in foundation as per loads coming in columns/pedestals for approval of engineer-in-charge. Any modification suggested by Engineer-in -charge shall be carried out for which no separate payment will be made. The rate shall include cost of structure, insulated sheeting, clading, poly carbonate sheeting, turbo fan/ventilators, hand and electrically operated Heavy Duty rolling shutters with motor and starter as per size, numbers & specifications shown in the drawing. The rate shall include cost of motor of adequate capacity, reduction gear & starter in both direction (up & down) complete in all respect for functioning of rolling shutter. It shall also have provision of mechanical device for manual operation. The above information should be read in conjunction with the details furnished in the table below: |
| 452 | Building type - Pre-Engineered Warehouse Roof slope - 1 in 10 (Tentative)Size of warehouse - 74.50 m x 47.45 m from external wall face to faceClear Eaves height - 12.0 M from finished floor levelRidge height- 14.50 M floor finish floor levelBay Spacing -As per tender drawings - As per tender drawingsSteel Columns-Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge.Type of bracing on roof & wall- Type of bracing on roof & wall- Diagonal Rod / Angle Bracing (as per design)Diagonal Bracing (FEW/BEW - Rigid end frame is considered at both end wall with half width loading- non-expandable Block wall height - ACC block wall up to 3m height above plinth beam all around the building. (to be paid separately) Roof sheeting - The single skin seamless roofing profile system consists of 0.55 mm TCT AZ150 Hi-Rib Bare Galvalume 550 MPA steel substrate, clear acrylic coating on both sides with 50mm thick rock wool of 48Kg/m3 insulation density fixed with 75X75X2mm thick GI wiremesh for roof insulation. Wall - The double skin wall cladding system consists of 50mm thick, 40+2 Kg/m3 density PUF insulated panels sandwiched between two sheets of 0.50 mm TCT Hi-Rib SMP coated AZ150 Galvalume 550 MPA steel. Side cladding and gable End Cladding should be overlapped on masonry wall by 450 mm with End Flashing. Canopy - Two canopies of size 6mX5m & 16.5m X and cantilever projection of required size at each opening.The Roof sheeting for canopy will be seamless Straight roofing profile system out of 0.5 mm TCT Hi-rib SMP coated AZ150 Galvalume 550Mpa steel.Daylight panels (nos. and %) -(5 % of Roof Area)-3 mm thick polycarbonate sheet is considered.Turbo vent - 64 nos.- 610mm throat dia of turbo vent is considered.Eave Gutter/ Down take pipes - Standard 0.5mm thick Galvalume Gutter & Down take pipes up to catch basin |
| 453 | Purlin & Girts - Purlins & girts shall be cold formed “Z” section manufactured from GI coils with base galvanization of 275 gm/Sqm (total on both sides) and yield strength of 350Mpa. Minimum thickness of the sheet to be used for “Z” section shall not be less than 2.0mm.Sidewall girts and end wall girts are mounted on the exterior face of the main column.Fasteners - Mechanically galvanized Hex-washer head self-drilling fasteners with integral EPDM seals.Accessories: - Flashing, trims, eave gutters, roof flashing, gable end flashing, End wall flashing, Box Gutter, downspouts screws etc.Civil / Electrical works -As per BOQ & drawingsElectrically operated Rolling shutter - Heavy duty rolling shutters as per specification.Heavy duty rubber stopper - Providing 2 nos. heavy duty rubber stopper of size 300X200X100mm including fixing arrangement in front of each rolling shutter along platform side.DESIGN LOADS - Live Load For Roof : 0.75kN/SQMDead Load For Roof : IS 875-1987 ( Part-1)Additional Collateral Load=0.15 KN/sqmWind speed/pressure : IS:875-1987Seismic Zone/Factor : IS:1893-2016Deflection in Rafter (Vertical) : As per latest IS 800:2007 Deflection to Column (Horizontal) : As per latest IS 800:2007 Deflection to Purlin : As per latest IS 800:2007 Considerations of loading for cable trays, solar, firefighting & electrical & other MEP services etc. as per tender drawings.Building to be designed for one additional floor as future expansion.Applicable Codes: - Primary Member Design - IS:800-2007 (Limit State Design) Without Chapter-12Secondary Member Design - IS:801-1975Loads & Load Combination - IS:875-1987Earthquake Load- IS:1893-2016 (Part-1)-Only Static AnalysisWind Load As Per IS:875-2015 (Part-3) With Terrain Category-2Slender Sections Are Considered For Web & Semi-Compact Sections Are Considered For Flanges.Structural Steel Specification - a) Primary SteelAll primary steel members shall be solid web builtup section in manufactured out of 350 Mpasteel plates. All portals shall be supplied in fully finished and ready to use condition for fieldassembly.b) Cold formed sectionThese shall be Z/C shaped cold formed section out 275 GSM Galvanised steel stripesconforming to ASTM 570.c) Rod bracing, flange bracing, misc. steel components such as clips etc. shall be out of 350Mpa steel conforming to IS 2062.d) Structural HardwareAll primary steel connections shall be established using high tensile Gr. 8.8 fasteners. Steelsecondary connections bolt shall be done by Galvanised Gr. 4.6 fasteners. |
| 454 | Designing, fabricating, testing, supplying & erecting the Pre-Engineered structure steel superstructure of Warehouse connected to Production Building, as per tender drg and details given below. Warehouse connected to Production Building-Warehouse of size 78.50mX53.50m as per Arch./tender Drawing & technical specification. |
| 455 | The job shall be executed with supply and erection of steel column, steel rafters, ties, bracing, purlins, sag rods, sag angles, nut bolts, washers,runners, high strength anchor bolts etc., insulated panels in roof and side cladding and gable end cladding as per technical specifications and GS profile sheets on both sides of insulated panels in roof, side clading & gable end cladding as per the technical specifications. The work also including supply,testing and fixing holding down bolts at beam/column location, base plates etc whever required and the other embedment, screw and EDP washers, Polycarbonate sheets 3mm thick of desired close fitting profile, barge board, ridges and hips etc., flashings , gutters , roof water take down pipes and other suitable accessories to provide a weatherproof and well detailed structure. |
| 456 | The work also involves providing and fixing suitable steel frame both hand and electrically operated rolling shutters including motor and starter. All the steel work including rolling shutters shall be mechanically cleaned and given 2 hour fire rated paint of approved Colour. Necessary openings and provisions for fixing electrical conduits, suspension of false ceiling, firefighting, lighting fixtures, and other related services shall be included in the scope of PEB works. The entire work shall be as per specification & scope as detailed in this tender. The contractor shall submit detailed design & drawings for complete warehouse including designs of RCC in foundation as per loads coming in columns/pedestals for approval of engineer-in-charge. Any modification suggested by Engineer-in -charge shall be carried out for which no separate payment will be made. The rate shall include cost of structure, insulated sheeting, clading, poly carbonate sheeting, turbo fan/ventilators, hand and electrically operated Heavy Duty rolling shutters with motor and starter as per size, numbers & specifications shown in the drawing. The rate shall include cost of motor of adequate capacity, reduction gear & starter in both direction (up & down) complete in all respect for functioning of rolling shutter. It shall also have provision of mechanical device for manual operation. The above information should be read in conjunction with the details furnished in the table below: |
| 457 | Building type - Pre-Engineered Warehouse Roof slope - 1 in 10 (Tentative)Size of warehouse - 78.50 m x 53.50 m from external wall face to faceClear Eaves height - 12.0 M from finished floor levelRidge height- 14.50 M floor finish floor levelBay Spacing -As per tender drawings Steel Columns - Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge.Type of bracing on roof & wall- Diagonal Rod / Angle Bracing (as per design) Diagonal Bracing (FEW/BEW - Rigid end frame is considered at both end wall with half width loading- non-expandable Block wall height - ACC block wall up to 3m height above plinth beam all around the building. (to be paid separately) Roof sheeting - The single skin seamless roofing profile system consists of 0.55 mm TCT AZ150 Hi-Rib Bare Galvalume 550 MPA steel substrate, clear acrylic coating on both sides with 50mm thick rock wool of 48Kg/m3 insulation density fixed with 75X75X2mm thick GI wiremesh for roof insulation. Wall - The double skin wall cladding system consists of 50mm thick, 40+2 Kg/m3 density PUF insulated panels sandwiched between two sheets of 0.50 mm TCT Hi-Rib SMP coated AZ150 Galvalume 550 MPA steel. Side cladding and gable End Cladding should be overlapped on masonry wall by 450 mm with End Flashing.Canopy - Two canopies of size 6mX5m & 16.5m X and cantilever projection of required size at each opening. The Roof sheeting for canopy will be seamless Straight roofing profile system out of 0.5 mm TCT Hi-rib SMP coated AZ150 Galvalume 550Mpa steel. Daylight panels (nos. and %) -(5 % of Roof Area)-3 mm thick polycarbonate sheet is considered. Turbo vent - 74 nos.- 610mm throat dia of turbo vent is considered. Eave Gutter/ Down take pipes - Standard 0.5mm thick Galvalume Gutter & Down take pipes up to catch basin |
| 458 | Purlin & Girts - Purlins & girts shall be cold formed “Z” section manufactured from GI coils with base galvanization of 275 gm/Sqm (total on both sides) and yield strength of 350Mpa. Minimum thickness of the sheet to be used for “Z” section shall not be less than 2.0mm.Sidewall girts and end wall girts are mounted on the exterior face of the main column.Fasteners - Mechanically galvanized Hex-washer head self-drilling fasteners with integral EPDM seals.Accessories: - Flashing, trims, eave gutters, roof flashing, gable end flashing, End wall flashing, Box Gutter, downspouts screws etc.Civil / Electrical works -As per BOQ & drawingsElectrically operated Rolling shutter - Heavy duty rolling shutters as per specification.Heavy duty rubber stopper - Providing 2 nos. heavy duty rubber stopper of size 300X200X100mm including fixing arrangement in front of each rolling shutter along platform side.DESIGN LOADS - Live Load For Roof : 0.75kN/SQM, Dead Load For Roof : IS 875-1987 ( Part-1)Additional Collateral Load=0.15 KN/sqm, Wind speed/pressure : IS:875-1987Seismic Zone/Factor : IS:1893-2016, Deflection in Rafter (Vertical) : As per latest IS 800:2007 Deflection to Column (Horizontal) : As per latest IS 800:2007, Deflection to Purlin : As per latest IS 800:2007 Considerations of loading for cable trays, solar, firefighting & electrical & other MEP services etc. as per tender drawings. Building to be designed for one additional floor as future expansion.Applicable Codes: - Primary Member Design - IS:800-2007 (Limit State Design) Without Chapter-12Secondary Member Design - IS:801-1975, Loads & Load Combination - IS:875-1987, Earthquake Load- IS:1893-2016 (Part-1)-Only Static Analysis, Wind Load As Per IS:875-2015 (Part-3) With Terrain Category-2, Slender Sections Are Considered For Web & Semi-Compact Sections Are Considered For Flanges.Structural Steel Specification - a) Primary Steel, All primary steel members shall be solid web builtup section in manufactured out of 350 Mpa , steel plates. All portals shall be supplied in fully finished and ready to use condition for field assembly. b) Cold formed sectionThese shall be Z/C shaped cold formed section out 275 GSM Galvanised steel stripesconforming to ASTM 570.c) Rod bracing, flange bracing, misc. steel components such as clips etc. shall be out of 350Mpa steel conforming to IS 2062.d) Structural HardwareAll primary steel connections shall be established using high tensile Gr. 8.8 fasteners. Steelsecondary connections bolt shall be done by Galvanised Gr. 4.6 fasteners. |
| 459 | Designing, fabricating, testing, supplying & Erecting the pre-engineered steel superstructure of PCB & Admin Buildings, as per tender drg and note given below. PCB & Admin Office Area -96.50m X 74.50 m( G+1)A) Office & Common Area (G+1) with mezzanine floor having Height 4.8m floor to floor with with having cantilever projection at Porch level & at each opening as per Arch./tender Drawings.The job shall be executed with Providing, fabricating, supplying and erecting structural steel framework comprising of steel columns,steel beams, deck sheet,ties, bracing, rods, angles,runners, high strength anchor bolts etc including cutting, welding, drilling, fabrication, primer/paint application, base plates, holding down bolts, nuts, bolts, washers and all necessary embedments as per approved structural drawings and technical specifications. Work includes proper alignment, erection and securing of steel members in position with required machinery, tools and safety arrangements, complete with all labour, materials and consumables.Work also includes Composite Deck Slab consisting of minimum thickness of 0.8 mm profiled deck sheet over steel beams, shear connectors, reinforcement steel, concrete of specified grade, temporary supports/formwork/props for all heights, edge trims, cut-outs/openings, finishing and curing, forming a structurally sound floor system. All work shall be executed including supply of all accessories, consumables, labour, equipment, safety arrangements etc., complete in all respects as per drawings, specifications and direction of the Engineer-in-Charge. Note : RCC deck slab including reinforcement steel, concrete, curing, and finishing shall be executed as a part of normal RCC construction and shall be measured and paid separately. Similarly, all other civil works such as Block work, plastering, flooring, doors/windows, waterproofing, electrical & plumbing services and finishes etc will be paid in separate respective items.The rate of deck sheet is included in the item. |
| 460 | B) STM Double Height Area having Height 8.5 m at eaves level from and having of antilever projection above rolling shutter & each opening and 2.5 m projection/bull nose along one side of the wall as per Arch./tender Drawings The job shall be executed with supply and erection of steel column, steel rafters, steel truss, ties, bracing, purlins, sag rods, sag angles, nut bolts, washers,runners, high strength anchor bolts, bull nose etc., insulated panels in roof and side cladding and gable end cladding as per technical specifications and GS profile sheets on both sides of insulated panels in roof, side clading & gable end cladding as per the technical specifications. The work also including supply,testing and fixing holding down bolts at beam/column location, base plates etc whever required and the other embedment, screw and EDP washers,, barge board, ridges and hips etc., flashings , gutters , roof water take down pipes and other suitable accessories to provide a weatherproof and well detailed structure. The work also involves providing and fixing suitable steel frame both hand and electrically operated rolling shutters including motor and starter. All the steel work including rolling shutters shall be mechanically cleaned and given 2 hours of fire rated paint of synthetic enamel paint of approved Colour. Necessary openings and provisions for fixing electrical conduits, suspension of false ceiling,firefighting, lighting fixtures, and other related services shall be included in the scope of PEB works. The entire work shall be as per specification & scope as detailed in this tender. The contractor shall submit detailed design & drawings for complete Building including designs of RCC in foundation as per loads coming in columns/pedestals for approval of engineer-in-charge. Any modification suggested by Engineer-in -charge shall be carried out for which no separate payment will be made. The rate shall include cost of structure, insulated sheeting, clading, hand and electrically operated Heavy Duty rolling shutters with motor and starter as per size, numbers & specifications shown in the drawing. The rate shall include cost of motor of adequate capacity, reduction gear & starter in both direction (up & down) complete in all respect for functioning of rolling shutter. It shall also have provision of mechanical device for manual operation.The above information should be read in conjunction with the details furnished in the table below: |
| 461 | Building type - Pre-Engineered Building with mezzanine floorSize of Building - 96.50 m x 74.50m from external wall face to faceA) Office & common Area- Office & Common Area (G+1) with mezzanine floorFloor to Floor Height - 4.8 m Deck slab/sheet or Mezzanine Floor - 0.8mm thick deck sheet for mezzanine floor with RCC slab as per design.Canopy - 1 Nos of size 8.5m X5.0 m , & 7.0m X 5.0 m. and cantilever projection of required size at each opening.The Roof sheeting for canopy will be seamless Straight roofing profile system out of 0.5 mm TCT Hi-rib SMP coated AZ150 Galvalume 550Mpa steel.Steel Columns - Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge.Staircase - 03 Nos of staircaseLift - 02 Nos of passenger lift & 1 No of good LiftCivil / Electrical works - As per BOQ & drawings |
| 462 | B) STM Double Height AreaRoof slope - 1 in 10 (Tentative)Clear Eaves height - 8.50 M from finished floor levelRidge height - 13.60 M floor finish floor levelSteel Columns -Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge.Canopy - 2 Nos of 4.5m X 5.0m and cantilever projection of required size at each opening.The Roof sheeting for canopy will be seamless Straight roofing profile system out of 0.5 mm TCT Hi-rib SMP coated AZ150 Galvalume 550Mpa steel.Bay Spacing - As per tender drawingsType of bracing on roof & wall - Diagonal Rod / Angle Bracing (as per design)Diagonal Bracing (FEW/BEW - Rigid end frame is considered at both end wall with half width loading- Non-expandableBlock wall height - ACC block wall up to 3m height above the plinth beam as per tender drawings |
| 463 | Roof sheeting - Supply and fixing of double skin standing seam roofing system made of 0.60 mm BMT (0.65mm TCT) Zincalume steel. The roof system is comprising of the following layers :1. Top Layer - Supply of 0.60mm base metal thickness (0.65mm TCT) 400 standing seam profile shall have 400 mm effective coverwidth, three stiffener symmetrically spaced (100mm c/c) parallel to 65mm deep rib, fixed to every purlin by means of structural grade Aluminium clip with UPVC thermal pad at the bottom of clip to reduce or eliminate thermal bridging effect. The panel overlapping shall be mechanically field seamed using electric steamer tool achieve increased weather durability and greater resistance to wind uplift. The steel sheet shall have minimum yield strength of 300MPa, metallic coated with Zinc-Aluminium alloy (i.e. 55% Al, 43.4% Zinc, 1.6% Si - Zincalume), AZ150 (min 150 gm/ m2 total on both side), confirms to IS15961 / AS1397, pre-painted with Super Durable Polyester paint system includes inorganic infrared reflective pigment (High SRI- \\"Thermatech technology\\") of 20um exterior coat on top surface and 5pm reverse coat on back surface over 5pm primer coat on both surfaces of approved color shade by concern authority. The sheet conforms to general requirement of AS/NZS 2728 type 4 / IS 15965 class 3 durability and BIS registration having the license of Bethlehem International Engineering Corporation (BIEC). The sheet shall be Green pro certified and shall have brand marking of the manufacturer giving product details on the back of the sheet at every 1 meter c/c for confirming genuinity of the material. The Aluminium clip shall be fastened with 40pm zine coated or 25um zinc-tin alloy coated, Hex head, self-drilling screw as per AS 3566-2002 Class 3 fasteners as per the requirement considering the profile shape and design load.2. Second Layer - Insulation - Rockwool insulation of 100mm thickness, 60 kg/m' density.3. Third Layer - Vapour Control Layer - Single layer of double side aluminium foil having minimum thickness of 0.20 mm.4. Fourth Layer - Liner sheet - Supply & Fixing of Galvalume Colour coated 0.70mm thick Perforated profile sheet of 1000-1050 mm effective cover width and 28-35 mm height ribs with subtle square fluting in the five pan at 200-250 mm centre-to-centre. The feed material is manufactured out of nominal 0.70 mm Total Coated Thickness (TCT), Hi-strength steel with min. 240 MPa yield strength, metallic hot dip coated with Aluminium-Zinc alloy (55% Aluminium, 45% Zinc) as per AS 1397 - Zincalume AZ150 (Min. 150 gms/sq.mt total on both sides) Fixed to the purlins with self drilling at 500mm spacing. Perforation - 3mm dia hole, 25% in the flat valley area only alongwith Accoustic Tissue. |
| 464 | Wall - The double skin wall cladding system consists of 80mm thick, 40+2 Kg/m3 density PUF insulated panels sandwiched between two sheets of 0.50 mm TCT Hi-Rib SMP coated AZ150 Galvalume 550 MPA steel.Bull Nose Projection - As per tender drawings and same material as of roof sheetingEave Gutter/ Down take pipes - Standard 0.5mm thick Galvalume Gutter & Down take pipes up to catch basinGirts - Sidewall girts and end wall girts are mounted on the exterior face of the main column.Fasteners - Mechanically galvanized Hex-washer head self-drilling fasteners with integral EPDM seals.Accessories: - Flashing, trims, eave gutters & downspouts.Civil / Electrical works - As per BOQ & drawingsElectrically operated Rolling shutter - Heavy duty rolling shutters as per specification |
| 465 | DESIGN LOADS - Live Load For Roof : 1.50 kN/SQMDead Load For Roof : IS 875-1987 ( Part-1)Additional Collateral Load=0.15 KN/sqmWind speed/pressure : IS:875-1987Seismic Zone/Factor : IS:1893-2016Deflection in Rafter (Vertical) : As per latest IS 800:2007 Deflection to Column (Horizontal) : As per latest IS 800:2007 Deflection to Purlin : As per latest IS 800:2007 Considerations of loading for cable trays, solar, firefighting & electrical & other MEP services as per tender drawings.Building to be designed for a one additional floor as future expansion.Deck slab/sheet or Mezzanine Floor - Dead Load & Live Load as per latest IS 875 -1987 ( Part-1 & 2) .Applicable Codes:Primary Member Design - IS:800-2007 (Limit State Design) Without Chapter-12Secondary Member Design - IS:801-1975Loads & Load Combination - IS:875-1987Earthquake Load- IS:1893-2016 (Part-1)-Only Static AnalysisWind Load As Per IS:875-2015 (Part-3) With Terrain Category-2Slender Sections Are Considered For Web & Semi-Compact Sections Are Considered For Flanges.Structural Steel Specification - a) Primary SteelAll primary steel members shall be solid web builtup section in manufactured out of 350 Mpasteel plates. All portals shall be supplied in fully finished and ready to use condition for fieldassembly.b) Cold formed sectionThese shall be Z/C shaped cold formed section out 275 GSM Galvanised steel stripesconforming to ASTM 570.c) Rod bracing, flange bracing, misc. steel components such as clips etc. shall be out of 350Mpa steel conforming to IS 2062.d) Structural HardwareAll primary steel connections shall be established using high tensile Gr. 8.8 fasteners. Steelsecondary connections bolt shall be done by Galvanised Gr. 4.6 fasteners. |
| 466 | Designing, fabricating, testing, supplying & Erecting the pre-engineered steel superstructure of Production Buildings, as per tender drg and note given below. Production Building Office Area (G+1) -78.50 X 78.50 m ( with mezzanine floor having Height 4.8m floor to floor with having cantilever projection at Porch level & at each opening as per Arch./tender Drawings'The job shall be executed with Providing, fabricating, supplying and erecting structural steel framework comprising only steel columns and steel beams deck slab, including cutting, welding, drilling, fabrication, primer/paint application, base plates, holding down bolts, nuts, bolts, washers and all necessary embedments as per approved structural drawings and technical specifications. Work includes proper alignment, erection and securing of steel members in position with required machinery, tools and safety arrangements, complete with all labour, materials and consumables.Work further includes Composite Deck Slab consisting of 0.8 mm thick profiled deck sheet over steel beams, shear connectors, reinforcement steel, concrete of specified grade, temporary supports/formwork, edge trims, cut-outs/openings, finishing and curing, forming a structurally sound floor system. All work shall be executed including supply of all accessories, consumables, labour, equipment, safety arrangements etc., complete in all respects as per drawings, specifications and direction of the Engineer-in-Charge. |
| 467 | All the steel work shall be shall be mechanically cleaned and given 2 hours of fire rated paint of approved Colour as per technical specifications. Necessary openings and provisions for fixing electrical conduits, suspension of false ceiling, firefighting, lighting fixtures, and other related services shall be included in the scope of PEB works. The entire work shall be as per specification & scope as detailed in this tender. The contractor shall submit detailed design & drawings for complete building structure including designs of RCC in foundation as per loads coming in columns for approval of engineer-in-charge. Any modification suggested by Engineer-in -charge shall be carried out for which no separate payment will be made. The rate shall include cost of structure, sheeting as shown in the drawing and technical specification.The above information should be read in conjunction with the details furnished in the table below:Building type - Pre-Engineered Building with mezzanine floor Size of Building -78.50 m x 78.50 m from external wall face to face Floor to Floor Height - 4.8 m Steel Columns - Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge. Deck slab/sheet or Mezzanine Floor - 0.8mm thick deck sheet for mezzanine floor with RCC slab as per design. Canopy - 1 Nos of size 8.5m X5.0 m , & 7.0m X 5.0 m. and cantilever projection of required size at each opening. The Roof sheeting for canopy will be seamless Straight roofing profile system out of 0.5 mm TCT Hi-rib SMP coated AZ150 Galvalume 550Mpa steel.Block wall height - ACC block wall up to steel beam bottom as per tender drawings. Staircase - 05 Nos of staircaseLift - 03 Nos of passenger lift & 4 No of good LiftsCivil / Electrical works - As per BOQ & drawingsBay Spacing - As per tender drawings |
| 468 | DESIGN LOADS - Live Load For Roof : 1.50 kN/SQMDead Load For Roof : IS 875-1987 ( Part-1)Additional Collateral Load=0.15 KN/sqmWind speed/pressure : IS:875-1987Seismic Zone/Factor : IS:1893-2016Deflection in Rafter (Vertical) : As per latest IS 800:2007 Deflection to Column (Horizontal) : As per latest IS 800:2007 Deflection to Purlin : As per latest IS 800:2007 Considerations of loading for cable trays, solar, firefighting & electrical & other MEP services as per tender drawings.Building to be designed for a one additional floor as future expansion.Deck slab/sheet or Mezzanine Floor - Dead Load & Live Load as per latest IS 875 -1987 ( Part-1 &2)Applicable Codes: - Primary Member Design - IS:800-2007 (Limit State Design) Without Chapter-12Secondary Member Design - IS:801-1975Loads & Load Combination - IS:875-1987Earthquake Load- IS:1893-2016 (Part-1)-Only Static AnalysisWind Load As Per IS:875-2015 (Part-3) With Terrain Category-2Slender Sections Are Considered For Web & Semi-Compact Sections Are Considered For Flanges.Structural Steel Specification- a) Primary SteelAll primary steel members shall be solid web builtup section in manufactured out of 350 Mpasteel plates. All portals shall be supplied in fully finished and ready to use condition for fieldassembly.b) Cold formed sectionThese shall be Z/C shaped cold formed section out 275 GSM Galvanised steel stripesconforming to ASTM 570.c) Rod bracing, flange bracing, misc. steel components such as clips etc. shall be out of 350Mpa steel conforming to IS 2062.d) Structural HardwareAll primary steel connections shall be established using high tensile Gr. 8.8 fasteners. Steelsecondary connections bolt shall be done by Galvanised Gr. 4.6 fasteners. |
| 469 | Providing, constructing and completing in all respects the Civil Works for Conveyor Belt System, including design, detailing, and preparation of all civil and structural drawings required for the installation of the conveyor belt structure, comprising foundations, pedestals, trestles, transfer towers, galleries, loading/unloading platforms, equipment foundations, and other associated civil structures, as per approved design and drawingsConveyor Belt system (50m X 3.0 m) as per Arch./tender DrawingsThe job shall be executed with Providing, fabricating, supplying and erecting structural steel framework comprising only steel columns and steel beams deck slab, including cutting, welding, drilling, fabrication, primer/paint application, base plates, holding down bolts, nuts, bolts, washers and all necessary embedments as per approved structural drawings and technical specifications. Work includes proper alignment, erection and securing of steel members in position with required machinery, tools and safety arrangements, complete with all labour, materials and consumables.Work further includes Composite Deck Slab consisting of 0.8 mm thick profiled deck sheet over steel beams, shear connectors, reinforcement steel, concrete of specified grade, temporary supports/formwork, edge trims, cut-outs/openings, finishing and curing, forming a structurally sound floor system. All work shall be executed including supply of all accessories, consumables, labour, equipment, safety arrangements etc., complete in all respects as per drawings, specifications and direction of the Engineer-in-Charge. The above information should be read in conjunction with the details furnished in the table below:Building type - Pre-Engineered Building with mezzanine floorSize of Building - 50m X 3.0 m c/c of steel columnsFloor to Floor Height - Height as per tender drawings |
| 470 | Steel Columns - Structural steel columns shall be provided with fixed base connections to RCC columns or pedestals at floor finish level, using necessary anchor bolts/holding down bolts, base plates, nuts, washers, and fasteners, including alignment, leveling, grouting between RCC surface and steel base plate with non-shrink grout, all complete as per approved drawings, technical specifications, and as directed by the Engineer-in-Charge.Deck slab/sheet or Mezzanine Floor -As per design.Block wall heightCivil / Electrical works - ACC block wall up to steel beam bottom - As per BOQ & drawingsBay Spacing - As per tender drawings |
| 471 | DESIGN LOADS - Live Load & Dead Load : As per IS 875 ( part-2) and as per manufacturer/conveyor belt agency Dead Load For Roof : IS 875-1987 ( Part-1)Additional Collateral Load=0.15 KN/sqmWind speed/pressure : IS:875-1987Seismic Zone/Factor : IS:1893-2016Deflection in Rafter (Vertical) : As per latest IS 800:2007 Deflection to Column (Horizontal) : As per latest IS 800:2007 Deflection to Purlin : As per latest IS 800:2007 Deck slab/sheet or Mezzanine Floor - Dead Load & Live Load as per latest IS 875 -1987 ( Part-1 & 2) .Applicable Codes: - Primary Member Design - IS:800-2007 (Limit State Design) Without Chapter-12Secondary Member Design - IS:801-1975Loads & Load Combination - IS:875-1987Earthquake Load- IS:1893-2016 (Part-1)-Only Static AnalysisWind Load As Per IS:875-2015 (Part-3) With Terrain Category-2Slender Sections Are Considered For Web & Semi-Compact Sections Are Considered For Flanges.Structural Steel Specification - a) Primary SteelAll primary steel members shall be solid web builtup section in manufactured out of 350 Mpasteel plates. All portals shall be supplied in fully finished and ready to use condition for fieldassembly.b) Cold formed sectionThese shall be Z/C shaped cold formed section out 275 GSM Galvanised steel stripesconforming to ASTM 570.c) Rod bracing, flange bracing, misc. steel components such as clips etc. shall be out of 350Mpa steel conforming to IS 2062.d) Structural HardwareAll primary steel connections shall be |
| 472 | Providing and fixing mill finish powder coated aluminium System Profile 10 mm thick toughened glass partition having system profile size (25X45mm) with every glass joint use I-Profile frame for glass partition, All work complete as per directed by the Architect/Engineer in- Charge. |
| 473 | Providing & fixing of Classique Invincible or equivalent Toilet Cubicle of approved make of sizes as per drawing which includes 600 mm door size width made of heat, bacteria, water, chemical ,scratch, impact and anti bacterial resistant 12 mm thick solid compact laminate panels (tested by approved NABL laboratory). Finish of the compact laminate should be Suede/*Raw Silk or as approved by the engineer in charge, which includes door, pilasters & intermediate panels finished with approved texture/shade as per the details drawings & as per IS 2046 (Indian Standard ) and as per fire retardant BS-476/97 Standard.The item also includes providing and fixing in position necessary hardware made out of Stainless steel (Grade 304) as per manufacturer's specification & as approved by the Architect/ Engineer, like (1) Door Knop, (2) Gravity Hinges, (3) Thumb turn lockset indicators, (4) Coat hooks, (5) U Channels, (6) SS-Shoe Box Plate (7) MS- Base Plate, (8) Top rail with Corner connector (9) Rubber noise deafening tape (10) Screw & wall Plugs etc all complete to the satisfaction of engineer in charge. |
| 474 | The top fitting should consist of SS round top rail which will get fixed with pilasters,with SS panel tube holder, SS corner bend (connected with top rail) will be used on the corner of cubicle in absence of Blockwall, SS wall fixing is used on the wall which will hold the SS top rail. All screws will be of 304 Grade stainless steel with satin finish. All pilasters are supported by stainless steel bottom cladding.The base of stainless steel botoom cladding will be anchored to floor with a clearance height upto 150 mm. (Surface area of partitions including door shall be measured for payment. The quoted rate should be for the complete item and nothing extra is payable in this account. |
| 475 | Providing and fixing external wall cladding with Wood Plastic Composite (WPC) louvers of 25mm thick of approved make, shade, and profile, including necessary sub-structure, supports, and accessories, complete as per drawing and direction of the Engineer-in-Charge. The WPC louvers shall be composed of wood fibre and virgin polymer (HDPE/PVC/PP) compounded with UV stabilizers, anti-fungal, and anti-termite additives, having a minimum density of 650 kg/cum, water absorption not exceeding 2%, and fire-retardant property conforming to Class B or equivalent. Louvers shall be fixed over a 50x25 mm anodized MS sub-frame (1.5 mm thick), placed at maximum 600 mm c/c in both directions, and anchored using stainless steel (SS 304) brackets, screws, and anchor fasteners to ensure rigidity, alignment, and long-term stability, designed to withstand wind loads as per IS 875 (Part 3). The installation shall be weather-tight, allowing for thermal expansion and contraction, and shall include all necessary edge trims, flashings, gaskets, sealants, and corner profiles to ensure a neat and uniform finish. The shade, texture, and alignment shall be as approved by the Engineer-in-Charge. The rate shall include cost of all materials, labour, tools, plants, scaffolding, transportation, wastage, and all incidentals required to complete the work in all respects as per technical specifications and directions of the Engineer-in-Charge.(Note: M.S (mild steel) framework with priming coat and necessary SS fasteners and SSscrews shall be paid separately. |
| 476 | Providing and fixing factory made 18 mm thick single extruded WPC (Wood Polymer Composite) solid plain white colour board, fixing with WPC Jali for duct/shaft covering, partitions and facades comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium corbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives(maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with properties of being termite/borer proof, water/moisture proof and fire retardant and fixing on M.S (mild steel) frame made of 25 x 25 x 1.5 mm square hollow box section including applying a priming coat of approved steel primer, placed at grid made at 1.0 x 1.0 m or as per requirement at site with necessary stainless steel fasteners and SS screws etc., all complete as per direction of Engineer-In- Charge.(Note: M.S (mild steel) framework with priming coat and necessary SS fasteners and SS screws shall be paid separately.) |
| 477 | Providing and fixing factory made 18 mm thick single extruded WPC (Wood Polymer Composite) solid plain white colour board, fixing with WPC Jali for duct/shaft covering, partitions and facades comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium corbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives(maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with properties of being termite/borer proof, water/moisture proof and fire retardant and fixing on M.S (mild steel) frame made of 25 x 25 x 1.5 mm square hollow box section including applying a priming coat of approved steel primer, placed at grid made at 1.0 x 1.0 m or as per requirement at site with necessary stainless steel fasteners and SS screws etc., all complete as per direction of Engineer-In- Charge.(Note: M.S (mild steel) framework with priming coat and necessary SS fasteners and SS screws shall be paid separately.) |
| 478 | Supply and installation of 12 mm thick:B.W.P ply finished with 1 mm thick laminate on all visible sides backed with 50mm thick 1000 GSM polyester wool insulation. Construction of Frame work : Frame work consists of minimum 50mm GI stud with fully knurled surface of 0.55 mm thick, 50mm width and two equal flanges of 34mm is fixed on to the GI support made of required height, First the wall plate is fixed on to the wall using suitable fasteners at every 1200mm C/C in both the directions and an MS hallow box section of 40mmX40mm with 5mm thick is welded to the wall plate, this is used to give the support to the MS gride of 600mmX600mm which is placed at a distance of 480mm from the wall. Cavity Filling : The frame work shall be back lined by using polyester fiber having a density of 1000 GSM and 50mm thick held in position by using GI weld mesh Boarding : 12mm thick Laminated plywood (8mm plywood and 1mm laminate) of approved finish is then fixed to GI frame work by using suitable fasteners and ensure proper level of the panel surface.Finishing : Ensure plywood is in plumb level and finish by using laminate of approved shade and color |
| 479 | Providing and fixing door handles with bottom lock patch ( set) suitable for toughened glass doors, including all necessary fittings, fixtures, and accessories, complete as per manufacturer’s specifications and as directed by the Engineer-in-Charge. |
| 480 | Providing and fixing stainless steel (SS) mortice latch and lock with 8 levers and a pair of handles (best make of approved quality), suitable for toughened glass doors, including all necessary fittings, fixtures, accessories, required glass cut-outs, and making good the surface, complete as per manufacturer’s specifications and as directed by the Engineer-in-Charge |
| 481 | SPECIALISED HIGH PERFORMANCE ACRYLIC POLYMER MODIFIED ELASTOMERIC CEMENTITIOUS WATERPROOFING SYSTEM COATINGTO THE WET AREA / TOILET / BATH ROOM .a ) First Layer - Supply and Apply penetrative cum bonding primer as base primer cum sealer coat using equivalent modified with water and cement at the ratio 2:1:3 (MIXPRIME AC 100 : water : cement) by volume with a slow speed mixer machine. This compoundshall be applied with sufficient thickness to cover the holes/pores/cracks @ 1.000 Liter /SQMand the raw primer should be complain with ASTM 4541 and the Solidcontent 49% +2%b ) Second Layer – Supply and apply of 2 x2 mm welded with alkaline resistant coated/ non-woven 40 Gsm verging fiber mesh or equivalent for a minimum over lap of 100 mm embedded inthe primer coatc ) Third Layer - Supply and apply of first coat of two component (Powder + Liquid) system of high performance acrylic polymermodified elastomeric cementitious waterproofing system or equivalent @ 1.000 Kg / SQM ( mix the powder and liquid with the help of a slow speed mixer for a period of 2 to 3 minutes up to get a homogeneous mix- dilution or modification not recommended) should be complain with BS 1881 Part 5 1983 (ISAT476 Part 6), DIN 1048 Part 5 1991, BSEN12390-8 2000, ASTM D 412-92d ) Fourth Layer –Supply and apply of second coat of two component (Powder + Liquid) system of high performance acrylicpolymer modified elastomeric cementitiouswaterproofing system equivalent @ 1.000 Kg / SQM ( mix the powder and liquid with the help of a slow speed mixer for a period of 2 to 3 minutes up to get a homogeneous mix- dilution or modification not recommended) should be complain with BS 1881 Part 5 1983 (ISAT476 Part 6), DIN 1048 Part 5 1991, BSEN12390-8 2000, ASTM D 412-92. |
| 482 | UGT/OHT (Inside) Water proofing with Anti - microbial Coating:Waterproofing: Providing and Applying CFTRI approved two component flexible polymer modified acrylic cementitious waterproofing coating with a mix ratio of (5 Liquid :7 Powder) to the RCC surface of the UGT/ OHT tank applied @ 2.2kg/m2 in 2 coats to achieve 1.2mm DFT, having Elongation at break >120% as per ASTM D 412, Tensile strength >1N/ mm2 as per ASTM D 412, Adhesion strength: 0.80N/mm2 as per ASTM D 4541, crack bridging upto 2mm as per ASTM C 836. The finished cost to include surface preparation, making coving of 50 mm X 50mm at all right angles of wall Junction with Polymer Repair Mortar and lay 45 gsm glass fibre mesh over the angle fillet when the first coat in still wet, treatment of cracks completely as per specification. Followed by applying 15 mm thick dimensionally stable fibrous reinforced cementitious structural grade dual shrinkage Polymer Mortar on as protective plastering @ 29kg/m2. The material having Compressive strength of 38 MPa at 28 days as per EN 12190, Adhesive Bond Test, >1.5 Mpa as per EN 1542, followed by Water curing by sprinkling water for 3 times a day for 5- 7 days. Followed by applying two component, water-based food grade epoxy resin coating on inside surface of Potable water tank having anti- algae, antifungal, Non-toxic, hygiene cum damp-proof coating Certified by CFTRI as per 21 CFR 175 – 300 of US– FDA, having mixing Ratio (Base: Hardener: Water) – 1:1:1 to be applied @ 0.35 Kg/m2 in 2 coats. Ensure that this coating is applied over the protective plaster. The Waterproofing material shall have Specific Gravity: 1.2, Water vapor permeance: 244.48 g/m2/24 hrs, as per IS 7809/Pt 2/1977, Adhesion strength: 2 N/mm2 as per ASTM D 4541: 02. The finished cost to include surface preparation completely as per specification. |
| 483 | Retaining wall/ UG tank wall (outside) Waterproofing with SBS MembraneProviding and laying water proofing treatment to the Retaining wall, water retaining structures outside with fully bonded 1.6mm Thick SBS modified self- adhesive, cross laminated HDPE lining waterproofing membrane, conforming to IS 16471:2017 Type A, requirements of UG waterproofing structures, The SBS membrane shall have Mass per Unit Area > 1.8 Kg/m2 as per ASTM D 5147, Puncture resistance > 200 N as per ASTM E 154, Elongation > 180% as per ASTM D 412-06, Tensile Strength > 4 Mpa as per ASTM D 412- 06, Tear resistance > 20 N/mm as per ASTM D 4073, Hydrostatic pressure 50M as per DIN 1048. The lap with HDPE membrane shall be 100mm treated with TS tape. followed by the installation of 8-10mm THK polyethylene dimpled drain board having compressive strength > 400kN/m2 (as per ISO 25619-2). The finished cost includes surface preparation, making coving and a coat of solvent based bituminous primer @ 0.25l/m2 on entire surface before laying membrane completely as per specification |
| 484 | Underground structures waterproofing with HDPE membraneProviding and laying water proofing treatment to the Rafts, Below grade slab, Lift pits, water retaining structures with fully bonded 1.5 mm thick HDPE waterproofing pressure sensitive adhesive membrane over PCC before laying raft concrete having higher puncture resistance of 1000N as per ASTM E 154, confirming to BS 8102 & IS 16471:2017, requirements of UG waterproofing structures. Laying adjacent sheets by keeping overlap of 75mm, end overlaps to be treated using double sided tape. The membrane shall have Tensile strength >25 Mpa as per ASTM D 412, Elongation > 500% as per ASTM D 412, Hydrostatic head resistance >70m head of water as per ASTM D 5385, Low Temperature Flexibility: -25 deg C, Peel Adhesion to Concrete >880 N/m as per ASTM D 903 Modified, UV Exposure > 45 Days. The finished cost including surface preparation completely as per specification. |
| 485 | \\"Pre construction Anti termite is a process in which chemical toxic to subterrean termites is apply/ inject into soil during early stage of building Construction2. Treatement of soil Beneath the building and around the foundationsconduct and chemical use as per BIS - IS 6313 (Part -2) 2013 code specification & CIB RC registered termiticide which creates a continuouschemical barrier beneath the building which kills or repels terminates & impervious to tremite entry Imidacloprid 30.5% SC (IS 63131) dissolve 2.1 Ml/1 liter of water and apply emulsion/solution @ 7.5 Litres/Square meter (Sqm) of internal, external vertical surface of the colums , plinth beams (Back filling) walls and floor junction, external perimeters, along reatining wall @ 5.0 Liters/Sqm of the horizontalsurface of basement top surface of the basement filling below flooring bed (Plinth) & @ 2.0 Litres/ Line meter at expansion joints. The substructure of a depth of 500mm around coulmns & 300mm deep around plinth beams, basements & floor filling area including excavation channel along the wall & rodding etc. cost & Conveyance of all materials to the site, cost of labour for sparying, rodding etc. completefor furnished item of work as per theapproval of the Engineer-in-charge\\" |
| 486 | Providing and fixing machine cut, mirror/ eggshell polished ,granite stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. |
| 487 | Laying 400 micron PVC sheet over DLC surface in required line, level, curvature over and including 10 mm thick compacted bed of coarse sand etc. all complete as per the direction of Enginee rin- charge.(Overlaps at joints of PVC sheet should be 100mm wide). |
| 488 | Supplying, stacking,spreading and filling Contractor’s own Earth, moorum, or mixture having design CBR, as approved by the Engineer-in-charge as per MORTH Specification using heavy vibratory roller in embankment/sub-grade for construction of pavement in layers not exceeding 200mm compacted thickness as per clause 305 with all lead, lift, transportation, spreading, watering, compacting in layers of 200 mm or less etc. complete.The compacted MDD at OMC shall not be less than 97% as per IS-2720 (part-VIII) for each layer with contractor material, transportation, labour machinery tools and plants including dressing of top layer and in side slopes to required profile etc. complete. Payment shall be made on the basis of initial ground levels recorded before start of work and final level of compacted earth. |
| 489 | SANITARY INSTALLATIONS |
| 490 | Providing, fixing & testing and commissioning of 12mm thick High Pressure Laminates (HPL) Compact Board urinals partition of minimum size 500mm (Top width) x 400mm (Bottom width) x 900mm (Height) complete with fixing on wall with dash fasteners complete with cuttiing of wall and making good the same as directed complete in all respect as per direction of Engineer-in-charge. |
| 491 | Providing & fixing floor mounted water closet P/S trap type of size 740x520x835mm of approved shape sutaible for handicap toilet including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete in all respect as per direction of Engineer-in-charge. |
| 492 | Providing and fixing automatic SS 304 Grade 'NO-Touch' wall mounted type hand-driers with sensor range 12-15cm, brush AC type motor, 30,000 RPM speed, suitable for 220/240 Volts, single phase, 50 Hz A.C. supply complete with all accessories & fittings complete in all respect as per direction of Engineer-in-charge. |
| 493 | Providing & Fixing 750x100mm SS grab bars wall mounted hinged hand rail type fixed to wall with rawl plugs and CP brass screws complete in all respect as per direction of Engineer-in-charge. |
| 494 | Providing and fixing minimum 1mm thick stainless steel grating of approved make and quality grade 18/8 - 304 on top of floor trap & floor drain The rate includes the cost of all ancillary works and material as required to complete the works in all respect as per direction of Engineer-in-charge.-100mm |
| 495 | Providing and fixing minimum 1mm thick stainless steel grating of approved make and quality grade 18/8 - 304 on top of floor trap & floor drain The rate includes the cost of all ancillary works and material as required to complete the works in all respect as per direction of Engineer-in-charge-125mm |
| 496 | Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of width as/drain size, 600mm length, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100 mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick, 100 mm wide MS sheet duly painted over priming coat, reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge. |
| 497 | RO PLANT & WATER COOLER |
| 498 | 1) The pump shall be capable of developing the required total head at rated capacity for continuous operation. The pumps shall operate satisfactorily at any point on the Head-Discharge (H-Q) characteristic curve over a range of 50% to 130% capacity. 2) The total head capacity curve shall be continuously rising towards the shut off. The shut off head shall be at least 110% of the total head. The pump should deliver at least 125% of its rated capacity at 75% of the specified total head. 3) Wherever mechanical seal has been asked for, it must be `factory fitted` at pump manufacturer`s works. Inlet TDS < 1000 PPMOutlet TDS < 50 PPMCollection of water sample and getting it tested for all physical, chemical and becteriological complete tests from reputed lab as per IS:10500 |
| 499 | a) Before treatment |
| 500 | b) After treatment |
| 501 | Supplying, installing, testing and commissioning of filter water feed pump as per the following details : The filter feed pump unit shall be complete with GI \\"C Class\\" header. a) Pumps: Vertical Inline pump with mechanical seal \\"Material of Construction (M.O.C): Corrosion Resistant in generalPump Casing - Stainless Steel\\" Impeller - Stainless Steel Shaft - Stainless Steel Shaft Sleeve - Stainless Steel Duty: Discharge (Each Pump) : 6 M3/hr Head : 30 M Each |
| 502 | Providing, installing, testing and commissioning vertical down flow type Multi Grade Filter capable of filtering 6 cum/hour of water at prescribed filteration rate of 15 cum/sq.m/hr. The filter shall comprise of MSFRP lined shell, complete with GI \\"C Class\\" frontal piping and valves pressure guage, first charge of filter media. etc. Filteration unit as described above having following parametersDia - 750 mm (Min.)Height of Vessel - 1800 mm (Min.)Filtration Rate: 15 m3/hr/m2Media Bed Depth - 1000 mm (Min.) |
| 503 | Providing, installing, testing and commissioning vertical down flow type Activated Carbon Media Filter capable of filtering 6 cum/hour of water at prescribed filteration rate of 15 cum/sq.m/hr. The filter shall comprise of MSFRP lined shell, complete with GI \\"C Class\\" frontal piping and valves pressure guage, first charge of filter media. etc. Filteration unit as described above having following parametersDia - 750 mm (Min.)Height of Vessel - 1800 mm (Min.)Media Bed Depth - 1000 mm (Min.) |
| 504 | Antiscalent Dosing SystemDetails of Equipments Chemical Storage TankMaterial : Chemical Grade PolypropleneCapacity : 100 lts. |
| 505 | Electronic Metering PumpPositive displacement typeDischarge : 0 - 12 LPH (Each Pump)2 Nos. (1W + 1S) |
| 506 | pH Corection system Details of Equipment Chemical Storage TankMaterial : Chemical Grade PolypropleneCapacity : 100 lts. |
| 507 | Electronic Metering PumpPositive displacement typeDischarge : 0 - 12 LPH (Each Pump)2 Nos. (1W + 1S) |
| 508 | SMBS Dosing systemDetails of Equipment Chemical Storage TankMaterial : Chemical Grade PolypropleneCapacity : 100 lts. |
| 509 | Electronic Metering PumpPositive displacement typeDischarge : 0 - 12 LPH (Each Pump)2 Nos. (1W + 1S) |
| 510 | Chlorine Dosing systemDetails of Equipment Chemical Storage TankMaterial : Chemical Grade PolypropleneCapacity : 100 lts. |
| 511 | Electronic Metering PumpPositive displacement typeDischarge : 0 - 12 LPH (Each Pump)2 Nos. (1W + 1S) |
| 512 | Micron FilterDetails of Equipment Rating : 5 MicronFlow rate : 6 M3/hr.Type : Polyproplene CartridgeNo. of Cartridges : as requiredDia of Cartridge : 2.5 inchLength of Cartridge : 20 inchCartridge Housing MOC : Stainless Steel No. of Housing : as required |
| 513 | High Pressure Feed Pumps ( 1 Working + 1 Standby)Details of Equipment Type : Vertical Multistage TypeM.O.C : All Parts Stainless Steel (SS 316) Motor : TEFC, 3 Ph, 415 V, 2900RPMDischarge : 6 M3/Hr (Min.)* (Each Pump)Pressure : 10-12 Kg/cm2 (Min.)** OR as suitable for the proposed membrane type OR as suitable for the available raw water quality. |
| 514 | Membrane UnitSize : 4\\" X 40\\" (Min.)*No. : 12 ( Min)** OR as suitable for the available raw water quality |
| 515 | Membrane HousingMOC : Composite FRPTest Pressure : 300 PSI |
| 516 | Membrane Flushing SystemFlushing Pump - 2 Nos. (1W + 1S)Details of Equipment M.O.C : All Stainless Steel (SS 316)Motor : TEFC, 3 Ph, 415 V, 2900RPMDischarge : 3 M3/Hr (Each Pump)Head : 30 M |
| 517 | Micron Filter with pipeline and valvesRating : 5 MicronFlow rate : 2 M3/hr.Type : Polyproplene CartridgeNo. of Cartridges : as requiredDia of Cartridge : 2.5\\"Length of Cartridge : 20\\"Cartridge Housing MOC :Stainless SteelNo. of Housing : 2 |
| 518 | Providing, fixing, jointing, testing and commisioning interconnecting pipe work in Stainless Steel pipe and fitting of grade 316L as per IS : 6911:2017 and conforming to EN-10312 standards complete with press type fitting, bye-pass connection of solenoid valves, Rotameters to control the flow, stainless steel body pressure gauges with isolating cocks, all isolation valves, NRVs, Y` strainers etc. |
| 519 | Providing, fixing, connecting, testing and commissioning of electrical panel, power and control cabling between pump panel, pumps, dosers, level controller, solenoid valves etc. Provision for BMS Connectivity (with RS 485 output) The panel should have sufficient no. of potential free contacts for connectivity with Building Management System for monitoring purposes |
| 520 | Automation : The entire system is to be made fully automatic and intelligent using state of the art automation components. The system shall start and stop as per the drinking water level in the drinking water tank. Provision of level controllers in the drinking water tank is to be included in the Scope of Work. |
| 521 | Supplying, installing, testing and commissioning of following water quality monitring devices. |
| 522 | a) Online digital pH indicatorother essential RO instrumentation to have that provision of BMS compatibility, so the parameters can be monitored on SCADA/ Computer . It shall have RS 485 output) for BMS connectivity. |
| 523 | b) Online Total Dissoloved Solids (TDS) indicator , ORP meter and other essential RO instrumentation to have that provision of BMS compatibility, so the parameters can be monitored on SCADA/ Computer . It shall have RS 485 output) for BMS connectivity. |
| 524 | Providing, fixing, testing and commissioning of inline electromagnetic flow meter with BMS connectivity (4 to 20 ma and RS 485 output), IP68 sensor protection, fulll bore with PTEF liners, SS316L electrodes, SS-304 flow tube, 0.5% of accuracy Power Supply: 230VAC/24 VDC, Max temperature range of sensor: 120oC. as per model/selection, suitable for sewage including all fitting & accessories . |
| 525 | a) 25 mm dia nominal bore |
| 526 | b) 32 mm dia nominal bore |
| 527 | c) 40 mm dia nominal bore |
| 528 | Supplying, Installing, testing and commissioning Ultra Voilet Rays Unit in stainless steel sterlisation housing, complete with controls.a) 4000 Litres/hr. |
| 529 | Supplying and installing skid for mounting all the components of R.O. based water plant. The skid shall have SS 316 frame and stainless steel (Grade SS 316) members for supporting components, pipework, control instruments etc. |
| 530 | Supply, installing, testing and commissioning of clear water Factory assembled packaged hydro-pneumatic pumping system for R.O water supply ( with variable frequency drive for each pump) as per following details:The packaged unit shall be complete with :a) Pumps: Vertical monoblock booster pumpset with mechanical seal 2 no. (1 working +1 standby) : Impeller — Stainless Steel -316 : Shaft — Stainless Steel - 316 : Pump Head — Stainless Steel - 316 : Base — Stainless Steel - 316 : Motor Stool — Stainless Steel - 316 Motor: 2900 RPM; 3Ph 415V 50Hz Insulation Class - FProtection - IP54 Min.Duty:Discharge ( each pump) : 3 M3/hr. Working Pressure : 3.0 kg/sq.cm.b) Pressure Tank: FRP vessel with replacable polyetheruethane (PEU) bladder certified for drinking water. Minimum 8 Bar pressure rating — 1 No. 200 to 225 Lts. Capacity.c) Interconnecting Pipe work, Valves and Vibration Eliminators : Common suction & delivery headers instainless steel (Grade 316), Isolating valves, non return valves and vibration eliminators on suction & delivery sode of pumps.d) Common fabricated base frame, duly painted.e) Power and control cabling between panel and pumps. f) Accessories like presure guages, pressure switches etc.g) Electric control panel mounted on the skid for automatic operation of pumps comprising incoming switch fuse unit/MCBB, digital voltmeter & ammeter with selector switches, over load and under voltage protection devices, single phase preventors, MCB and DOL starter for each pump, indicating lights etc. all complete. Provision for BMS Connectivity ( (with RS 485 output). The panel should have sufficient no. of potential free contacts for connectivity with Building Management System for monitoring purposes |
| 531 | Supply, installation , testing & commissioning of SS 316 water tank for drinking water , tank shall be provided with Inner layer SS316L + Outer Layer SS316L of specified thickness, tank should be provided with inlet, outlet and vent/overflow connection of required sizes as per drawing, 75mm Puf Insulation , manhole cover 450mm dia, Inlet connection of water tank shall be of suitable nominal bore as shown in dwg, overflow/vent suitable nominal bore and outlet connection at bottom of tank of suitable nominal bore as shown in dwg. Cost of tank shall be inclusive of Angle stiffeners,stand leg, SS316 flanges connecting from water treatment facility and distribution system complete as per approved specifications.-5000 Liters tank capacity |
| 532 | Supply, installation , testing & commissioning of high efficiency SS316 Storage water cooler / Dispenser of follwing capacities with water at 15°C cooled from 40°C inlet water at 35°C ambient. Evaporator shall be high tank type and shall be encapsulated in insulation. R-404 refrigerant system shall be hermetically sealed and refrigerant shall be capillary tube controlled. An adjustable thermostat having an off position shall control refrigeration system. Cabinet shall be SS316L. Potable water system components shall comply with Safe Drinking Water Act Amendments, the 1988 Lead Contamination Control Act and shall be to ANSI/NSF 61 Section 9. chiller should be single phase 220 V, 50 Hz, with cooling coil, heavy gauge SS316L complete as required including foundation, complete as required-Cooling capacity : 225 lts/hr. And storage capacity 400 lts |
| 533 | Tube well |
| 534 | Supplying & installation of submersible pump set directly coupled with 7.5 HP motor nominal speed 2900 RPM suitable for operation on 3-phase, 50 cycles, 400 + 5% volts A.C. power supply to give yield of 30000/24000 LPH at a head of 50/70 mtrs. Total head = 50/70 Mt Flow rate = 36000/30000 LPH H P = Minimum 7.5 HP |
| 535 | Supply, installation and commissioning of panel board duly wired made of 16/18 SWG sheet including fixing of the same in wall/floor on angle iron frame as per site conditions, and fitted with the following: |
| 536 | 1 No. DOL starter. |
| 537 | 1 No suitable range voltmeter size 96 mm. |
| 538 | 1 No suitable range ammeter size 96 mm. |
| 539 | 1 No. single phase preventer. |
| 540 | 3 Nos MCB for lamps, ammeter and voltmeter |
| 541 | 3 Nos. indicating lamps |
| 542 | 1 No MCB of suitable range |
| 543 | Voltage selector switch- 1No. |
| 544 | Push button ON/ OFF switch - 1 No. |
| 545 | Supply & installation of 80 mm dia column pipe made out of 80 mm dia G.I. pipes (I.S. 1239 heavy duty C-class) including the cost of fittings complete in all respect. |
| 546 | Providing & fixing heavy duty PVC sheathed copper conductor 1100 volts grade cables with clamps complete in all respect.Control cable for low water level guard 2 core 2.5 Sq.mm. |
| 547 | Power cable 3 core 4 Sq.mm. |
| 548 | Furniture |
| 549 | The overall size of the table shall be 3000L x 950D x 760H with Side Unit Extension 1900L x 600D x 610H. The main table top shall be size of 2200L x 950D. The tabletop shall be 65mm thick. The tabletop shall be resting on one side of the gable end with the same thickness of table top and other side on the side unit. The table top and gable end shall have the same sleek chamfer design of 19mm straight and the rest will be 45 degree taper. The tabletop shall have a leather pad with size of 1145mm x 495mm that gives a premium look. The table shall not have any sharp edges. The tabletop shall have two flap access with size of 235mm x 120mm for easy wire access. The table shall be made of MDF with veneer finish. The modesty shall be made of MDF with veneer finish. The side unit shall be sized 1900L x 600D x 610H. It shall come with the configurations of 1 shutter 2 drawer and rest is open for CPU. The side unit shall have a net cutout for air ventilation for cooling the CPU. Drawer channels shall have soft close. All the Drawer and shutters shall be operated by finger grove with the help of V shaped aluminium extrusion on the top of Drawer and shutter facia shall have overall size of 20 L x 34 H x 1.5mm thick. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 550 | Back Unit : The Overall Size shall be W 1500 x D 450 x H 1800mm, Side & Front shall be made up of 18mm thick PLPB both E1 norms duly finished with 2mm pvc edge band. Back shall madeup of 9 mm thick PLPB both E1 norms duly finished with 2mm pvc edge band. Storages shall have multiples compartments with center locks and all other essential hardwares like hings, handles etc. The storage portion at lower level 750 mm shall have cover shutters and the upper part of the storage shall have open shelves to keep the awards, trophies or documents. All the visible surface shall be sealed with 2mm edge banding. Tolerance of +/- 5mm to be considered for product sizes i.e Length, Depth & height and tolerance of 5% to be considered in pipe thickness & Pipe sizes. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 551 | The overall size of Chair shall be width 600 +/-5mm, depth 640 +/-5mm. Total height shall be 995 to 1095 +/-5 mm, Back Width 425 mm at Top and 500mm at bottom, Seat Width 500 +/-5 mm, Seat Depth 460+/-5 mm and Seat height 470mm to 570 mm +/-5mm range. Seat shall be made up of foam pre moulded at 55 kg/m3 density. hardness of 25+ 3kgf at 50% deflection conforming to IS 3400. Seat shall be uplhostered with micro fabric 100% polyster 180 GSM abrasion > 50000 cycles. Fire rated fabric confirming to BS EN 1021 (match) should be used. The chair shall be supplied with cushion at the back. The back frame shall be made up of Injection molded PPGF 20% shade, armest support also in light grey shade. Adjustable Lumbar Support made up of PU having size 365 mm x 110 mm x 25mm thick shall be provided for better comfort. The Chair should be provided with Self Calibrating Multilock Mechanism (Bio Snchyro mechansim) that should adjust the tension of the back sensing weight of the user. The mechanism shall allow 360 degree revolving feature along with height adjustablility. The Chair shall have seat slide mechanism. One Way Adjustable Arms (Height) to be provied with height adjustment button made of Delrin P 500. The mechansim shall possess seat to back recline ratio of 3:7. The Gas Lift used shall be class 4 tested as per ANSI BIFMA standards. Nylon base shall be provided.Twin castors 50 mm dia with PA6 material complying to ANSI/ BIFMA X 5.1 2017 standards. The base shall be 660 mm PCD (26 inches) five pronged bases made up of PA6, 30% glass filled reinforced with bottom ribbing for additional buttress and strength. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 552 | 3 Seater Sofa : Overall size shall be 2020 mm W x 975 mm D x 820 mm H. Sofa inner frame structure shall be made from the combination of treated solid wood and plywood having high quality webbing belts to ensure good strength, rigidity & stable construction to offer high durability. There shall be extra padding between the armrest & the seat on both sides for better comfort & polyfilled in arms & backrest. The polyurethane (PU) foam shall be used in Seat & back rest having 40 density and 32 density respectively. Seat to backrest angle should be ergonomically designed to offer the best seating comfort. Seat height shall be normally between 16 to 18 inches and depth shall be between 20-22 inches. Sofa shall be elevated from ground by about 3 inches using Golden finished metal legs creating provision for easy cleaning & better look. Upholstery shall be of high quality Leatherite offer the best feel & comfort. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 553 | The Overal Size Of the Table shall be 1500L x1500Dx 750H.workstations of overall panel thickness 65 mm (+/-5mm) and height of 1200mm (+/- 5mm). The worktop shall be made up of 25mm E1 norm PLPB with matching PVC edge band 2mm thick. The worktop shall be provided with 65mm gromet cut & shall be supported on CRCA bracket with one side fixed on rectangular slot of frame vertical and other side to worksurface. The partition frame shall be made up of nonferrous 6063 grade alum alloy confirming to DIN ISO-2768-1 & fabricated through weldless technology & fitted with pre moulded M8 levellers zinc passivated for height adjustment. Frame shall have vertical & horizontal members, vertical channels have inbuilt groove with rectangular slots to fix cantilever / gable end brackets. Frame to frame shall be attached through male/ female hook mechanism pressure die casted parts made in zinc alloy Mazak5. Adequate ribs to be given in extrusion profiles having variable thicknesses of 1.10mm to 2.50mm for better durability. Frame to post shall be attached by male/female hooks made up of 2mm thick CRCA material zinc passivated to 10-12 microns. Each frame shall be fitted with tiles, male & female hooks, two end cap at top and bottom. Bottom caps shall be provided with leveller fixing arrangement. all caps shall be of aluminium ADC-12 pressure die cast. top trip shall be flat aluminium confirming to DIN ISO-2768-1. The data & power cables provision to be given at different levels. skirting raceways shall be designed for snap fitting for data cables and for power cables raceway below worktop shall be provided. Tiles of overall thickness 6mm thickness constructed out of PLPB E-1 norms upholstered with fabric or Laminated tile should be slide to the grooves provided in aluminium frame vertically, two tiles on either side of the frame to complete the assembly.Mobile Drawer Unit : It shall be of size of 400 x 450 x 600 (WDH) mm made up of 18mm thick Pre-laminate particle board as per E1 norms and its edges duly sealed with 2mm PVC Lipping on automatic machine at visible sides. Drawer front & sides shall be made up of 18mm, back 9 mm thick pre laminated particle board of E1 grade with visible edges sealed with 2mm PVC edge band. The drawer side surface shall be provided with finger groove handle-less design. Finger groove shall be created by providing a reverse tapered profile edge of 6mm straight surface & 12 mm tapered towards inside at 45 degree & then sealed with minimum 2mm thick PVC lipping on automatic machine. Suitable lock shall be provided. Tolerance of +/- 5mm to be considered for product sizes i.e Length, Depth & height and tolerance of 5% to be considered in pipe thickness & Pipe sizes. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 554 | Main Table of size 1500 x 750 x740 (WDH) with side unit size of 900 x 450 x 750mm(LDH).The worktop shall be made up of 25mm thick PLPB E1 norms duly finished with 2mm pvc edge band. The Modesty shall be made of 18mm thick pre laminated partical boards with E1 norms and all visible side 2mm pvc edge bending. Modesty shall be connected with 3 nos L-shape pressure aluminium die casted connector. MOdesty height shall be 450mm .The understructure shall be made of 18mm thick prelam partical board with 2mm pvc edge band all the visible side.Wire Management: 300 mm Anodised flip up Made of Aluminum in anodised finish, that shall have soft closure and three way wire acess & PVC cable tray. For entry of cables from the floor into the cable tray, Wire Entry. Side storage of size 900 x 450 x 750 H to be provided made up of 18mm thick PLPB E1 norms composite having two drawer & filling units/ shutters. back panel made up of 9mm thickn PLPB E1 norms. Finger groove shall be created by providing a reverse tapered profile edge of 6mm straight surface & 12 mm tapered towards inside at 45 degree & then sealed with minimum 2mm thick PVC lipping on automatic machine. Suitable lock shall be provided. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 555 | The overall size of Low height storage shall be 1200 x 450 x 750 (WDH) mm. Top shall be made up of 18mm thick pre laminated particle board E1 norms and Back shall be made up of 9 mm thick pre laminated particle board with 2mm PVC edge lipping, Shutters shall be made up of 18 mm thick pre laminated particle board. Shutters to be provied for compartment. The storage shall have adjustable shelf. Edge: All exposed shall be sealed with 2mm thick PVC edge lipping. The hinged doors top shall be provided with finger groove handle-less design for a streamlined look. Finger gAroove shall be created by providing a reverse tapered profile edge of 6mm straight surface & 12 mm tapered towards inside @ 45 degree & then sealed with minimum 2mm thick PVC lipping on automatic machine. Cam Lock faciltity should be provided for safe storage of documents. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 556 | The overall size of table shall be 1200 x 600 x 425mm (LDH). The table top shall provided 4mm thick clear glass.The understructure shall be made up of 25mm thick Stainless steel 202 (SS) round pipe with meatlic leverller. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 557 | 4 Door Locker Cabinets Overall Size : 400 x 450 x 1830 (WDH)mm. Manufacturing and supplying of 4 door Locker Unit made of 100% virgin Epoxy Powder Coated CRCA confirming to shall : 513 CR2 (Cold Reduced Carbon Steel Sheets & Strips (Part 1), 2016. Complete material should passes through 7 stage, based Pre-treatment plant prior to powder coating, making it highly corrosive resshall tant. Construction shall be welded from complete 0.6 mm thick CRCA sheet. Each Compartment Shelf shall have uniformly dshall tributed load capacity per shelf shall 35 kg. cam lock shall be provided with recessed handle. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 558 | The overall size of table shall be 1200l x 600D x 750HThe worktop shall be made of 25mm thick pre laminate partical boards with E1 norms dully finish with 2mm pvc edge band all the side of worktop.The Front and Side Modesty shall be made of 18mm thick pre laminate partical boards with E1 norms with 2mm pvc edge band all the visible side and connected with 2 nos L-shape pressure aluminium die casted connector. The height of the modesty shall be 450mm. The understructure will feature vertical legs made of 50 mm x 50 mm x 1.6 mm steel tubing, while the horizontal frame will be constructed from 50 mm x 25 mm x 1.6 mm steel. A cross beam, sized 40 mm x 20 mm x 1.6 mm across the length of the table, will be installed beneath the tabletop to provide additional support. This cross beam shall be connected on both sides with pressure die cast connectors of 50 mm height, 70 mm width & 35 mm depth designed in a shape acting as spacer between horizontal frame & worksurface. Pedestal : It shall be of size of 400 x 450 x 600 (WDH) mm made up of 18mm thick Pre-laminate particle board as per E1 norms and its edges duly sealed with 2mm PVC Lipping on automatic machine at visible sides. Drawer front & sides shall be made up of 18mm, back 9 mm thick pre laminated particle board of E1 grade with visible edges sealed with 2mm PVC edge band. The drawer side surface shall be provided with finger groove handle-less design. Finger groove shall be created by providing a reverse tapered profile edge of 6mm straight surface & 12 mm tapered towards inside at 45 degree & then sealed with minimum 2mm thick PVC lipping on automatic machine. Suitable lock shall be provided. Tolerance of +/- 5mm to be considered for product sizes i.e Length, Depth & height and tolerance of 5% to be considered in pipe thickness & Pipe sizes. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 559 | High Back Chair (Leatherite)High back Chair having overall height 1200-1300mm, back height of 790 mm from seat level and width of 460 mm from top & 520 from mid (lumbar) level. Seat Depth shall be 490 mm and adjustable upto 530mm. seat width shall be 520 mm measured at centre of the seat. Seat height shall range between 430 mm to 520 mm. Armest shall be finished with foam & leatherite on the top & the structure of the armrest shall a die cast aluminium with buffed finish & fixed with the seat below. The length of the top of the arm shall be 250 mm & width of 60 mm. Seat should be made up of foam pre moulded at 55 kg/m3 density. hardness of 25+ 3kgf at 50% deflection conforming to IS 3400. Seat, back & headrest shall be upholstered with Leatherette 75% PVC & 25% polyester – 640 GSM, Abrasion-100000 cycles over PU faom. The synchro mechanism shall be provided having 3 position multilocking & seat adjustable on the left hand side and height adjustment on the right hand side of the user.The mechanism shall allow 360 degree revolving feature along with height adjustablility. Aluminium die cast pedestal having length 5 twin 60 mm wheel castors heavy duty shall be provided. The Gas Lift used shall be class 4 tested as per ANSI BIFMA standards. tolerance of 25mm for seat & back size to be considered. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 560 | Medium Back Chair (Leatherite)Medium back Chair having overall height 1050-1150mm, back height of 590 mm from seat level and width of 460 mm from top & 520 from mid (lumbar) level. Seat Depth shall be 490 mm and adjustable upto 530mm. seat width shall be 520 mm measured at centre of the seat. Seat height shall range between 430 mm to 520 mm. Armest shall be finished with foam & leatherite on the top & the structure of the armrest shall a die cast aluminium with buffed finish & fixed with the seat below. The length of the top of the arm shall be 250 mm & width of 60 mm. Seat should be made up of foam pre moulded at 55 kg/m3 density. hardness of 25+ 3kgf at 50% deflection conforming to IS 3400. Seat and back shall be upholstered with Leatherette 75% PVC & 25% polyester – 640 GSM, Abrasion-100000 cycles over PU faom. The synchro mechanism shall be provided having 3 position multilocking & seat adjustable on the left hand side and height adjustment on the right hand side of the user.The mechanism shall allow 360 degree revolving feature along with height adjustablility. Aluminium die cast pedestal having length 5 twin 60 mm wheel castors heavy duty shall be provided. The Gas Lift used shall be class 4 tested as per ANSI BIFMA standards. tolerance of 25mm for seat & back size to be considered. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 561 | Visitor Chair (Leatherite)Visitor Chair having back height of 490 mm from seat level and width of 460 mm from top & 520 from mid (lumbar) level. seat width shall be 520 mm measured at centre of the seat. Seat height shall be 430 mm. Armest shall be finished with foam & leatherite on the top & the structure of the armrest shall a die cast aluminium with buffed finish & fixed with the seat below. The length of the top of the arm shall be 250 mm & width of 60 mm. Seat should be made up of foam pre moulded at 55 kg/m3 density. hardness of 25+ 3kgf at 50% deflection conforming to IS 3400. Seat & back shall be upholstered with Leatherette 75% PVC & 25% polyester – 640 GSM, Abrasion-100000 cycles over PU faom. The Frame shall be made out of ERW tubes with 25 mm diameter and 2.5 mm thickness pipe conforming to IS – 4923. Frame shall be welded by CO2 welding process for uniform finish conforming to IS 816. understructure shall connected with 4nos injuction ABS leg shoes. Understructure shall supplied with chorme finish.Tolerance of +/- 5mm to be considered for product sizes i.e Length, Depth & height and tolerance of 5% to be considered in pipe thickness & Pipe sizes.The OEM shall have ISO 9001, ISO 14001, Bifma Level 2, Green Guard by UL, India Design Mark & IGBC Gold rated factory certification. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 562 | The overall size of Chair shall be Total height 840+/-3 mm, Over all chair width should be 535 +/-5mm and Overall chair depth should be 535 +/-5mm. Back Width 360mm at Top and 440mm at bottom, Seat Width 420 +/-3 mm, Seat Depth 425+/-3 mm and Seat height 450mm +/-5mm. Seat and back shell should made by injuction moulding process with plastic material of PPGF20%. Seat and back shall be provided with cushion with fabir Upholstered. The Chair understructure should be provided with 12 mm thickness MS rod loop legs with rod conforming to IS – 7887. Injuction moulded Polycarbonate Leg shoes shall assembled to understructure. seat assembled shall be with silicon bushes to ensure stratch free when chairs stached. Understructure shall powder coated upto 40 to 60microns. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 563 | Vertical Filing Cabinets which use less floor space. Size of 4 Drawer VFC shall be 1320mm(H) x 460mm(W) x 620mm(D). All the components shall be made of CRCA. It should have 1 Point Locking Mechanism and a Rigid Knock Down Construction. The Top, Side & Drawer Front thickness should be 0.6mm. The Frames, Drawer-inside cover and Side Back Side thickness should be 0.6mm. The Back, Bottom and Drawer thickness should be 0.6mm. Easy to grip Full length Recess Handle shall be integrated into Metal Drawer for easy pull out convenience. The Centralized locking System shall be provided along with Shooting Bolt Mechanism and 10 lever Cam Lock. The VFC should have anti-tipping arrangement which ensures that when one drawer is opened for use, it does not allow other drawers to be opened. The High Quality Precision Ball Slide shall be provided with Drawer Load capacity of max 40 kg and UDL for 75,000 cycles (BS). Plain Triangular plate pop should be riveted at the bottom corners for rigidity. Optional Accessories like Drawer Partition and Cradle for hanging A4 file folders front to back should also be available. The finishing shall include Epoxy powder coated to the thickness of 50 microns (+/- 10). The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 564 | The overall size shall be table shall be 1050 x 750 x 750ht. The table shall have come with foldable top, easy to assemble (DIY table) comes in flat packs. Table top shall be made of - 25mm thk prelam partical board of E1 norm, with 2mm thk PVC edge binding all around. Under-structure shall come with Angular Legs, made of MS ERW Oval tubes, main leg is of 60x30x1.6mm(16g)thk & support leg shall from 48x22x1.60mm thk, fixed with Castors for smooth movements. Legs and top support beam of 60x30x1.60mm thk Rectangular tubular profiles are connected by diecast aluminium connectors of ADC12 material, the diecast part shall have in two designs, one shall LH & other shall be RH. One side of the connector comes with oval shape and other side comes with rectangular shape to have seamless connectivity of legs and the top beam to offer sturdy & robust joint. Top support beam shall be MS ERW Rectangular tube of 1.6mm (16g) thk, to offer adequate stability. The Diecast connector design shall a provision on one side to attach 60x30x1.60mm thk flat Oval Tube and another side it shall have a provision to attach 60x30x1.60 thk Rectangular tube. So the under-structure shall be built with weldless technology. The 60x30x1.60mm thk Top beam shall fixed with the Table Top. Flip Mechansim. This mechanism shall comes with Two 50x25x1.60mm thk rectangular tubes fixed with Aluminium diecast connectors, one of the diecast connector shall have hexagonal hole to lock with a polycarbonate / ABS injection moulded Knob with Hex rod & high quality compression spring shall used to lock & unlock the Flip mechanism.All metal parts shall be powder coated to 60-80 microns. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 565 | The overall size of meeting table shall be of size 2400 x 1200 x750 (WDH) The worktop shall be made up of 25mm thick PLPB E1 norms duly finished with 2mm pvc edge band. The Modesty shall be made of 18mm thick pre laminated partical boards with E1 norms and all visible side 2mm pvc edge bending. Modesty height shall be 450mm .The understructure shall be made of 25mm thick prelam partical board with 2mm pvc edge band all the visible side.Wire Management: 450 mm Anodised flip up Made of Aluminum in anodised finish, that shall have soft closure and three way wire acess & PVC cable tray. For entry of cables from the floor into the cable tray, Wire Entry. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 566 | The overall size of conference table shall be of size 6000 x 1200 x750 (WDH) The worktop shall be made up of 25mm thick PLPB E1 norms duly finished with 2mm pvc edge band. The Modesty shall be made of 18mm thick pre laminated partical boards with E1 norms and all visible side 2mm pvc edge bending. Modesty height shall be 450mm .The understructure shall be made of 25mm thick prelam partical board with 2mm pvc edge band all the visible side.Wire Management: 450 mm Anodised flip up Made of Aluminum in anodised finish, that shall have soft closure and three way wire acess & PVC cable tray. For entry of cables from the floor into the cable tray, Wire Entry. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 567 | METAL MOBILE PEDESTAL 1F + 1DSIZE: 400W X 450D X 600HT Specification:The overall size of metal pedestal shall be size of 400W x 450D x 600H. Metal pedestal shall be made of complete body and facia in 0.8mm thick CRCA.This pedestal shall be made of metal construction with anti-rust electrostatic spraying for long-lasting durability and bears up to 200lbs in total. Resistance soiling, resistance to water and resistance to stains. It drawer shall be operated by Telescopic channels.Drawers open completely and smoothly, allowing you to easily access the contents in the back of the drawers. Easy to classify and storage items.Pedestal handles shall be Finger grove and it is groove shall be generally located around the upper edge or perimeter of the pedestal for easy handling.Pedestal shall be cylindrical multi lock shall be provided. The manufacturer (OEM) shall have ISO 9001, ISO 14001, ISO 45001 & ISO 50001 issued from NABCB accredited agency, BIFMA Level 2, India Design Mark for Chairs & table category, Green Guard Gold certification for Chairs, workstation, Storage & tables, IGBC Gold rated factory certification, AIOTA certification. |
| 568 | Pumproom-STP |
| 569 | Domestic Water Pumps (Hydropneumatic System With Variable Speed Pumps)Providing, fixing and testing of factory fitted skid mounted variables frequency drive hydropneumatic system with variable speed system comprising of :- |
| 570 | Vertical, inline multistage centrifugal pumping set with stainless steel SS-304 stage casing and SS-304 impellers with stainless steel SS-304 shaft as per IEC standards and GJL250 cast iron suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply. |
| 571 | Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles. No. and capacity of Pressure Vessel – 01 Nos. x 200 Ltrs |
| 572 | Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump working sequence should change after every operation.Contractor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan. Main incomer MCB, Outgoing MCBs, Single phase preventors complete with auto manual swiches, Voltmeter/Ameter, Indication lights, Controller for dry run protection. |
| 573 | Pressure transmitting relay bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class. |
| 574 | GI Suction and delivery header with Ball valves Hot Pressed brass OT-58 with stainless steel ball and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement. |
| 575 | Complete set system to be mounted on a common base frame and shall follow following duty (Skid shall be powder coated ). |
| 576 | Domestic Water Pumps (Set of Two Pumps One Working + One Standby) Capacity : app. 550 lpm (Each Pump)Head : app. 50 m |
| 577 | Providing, fixing and testing of skid mounted pumping system comprising of :- |
| 578 | Horizontal centrifugal pumping set with CI body and bronze impeller with stainless steel SS 304 shafts connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply. |
| 579 | GI Suction and delivery header with Ball valves Hot Pressed brass OT-58 with stainless steel ball and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement. |
| 580 | Complete set system to be mounted on a common base frame and shall follow following duty. |
| 581 | Filter Feed Pumps(Set of Two Pumps One Working + One Standby)Capacity : app.400 lpmHead : 30m |
| 582 | Pressure Filter (Domestic Water)Providing and fixing vertical pressure filter with dual media filter (comprising of minimum 1050mm bed depth of graded sand gravel and Anthracite) fabricated from high performance M.S plate of minimum 6mm thick for shell & 8mm thick for dished ends with top and bottom flanged openings including top and bottom hub and lateral distribution and collection system complete with initial charge of filter media, face piping, valves, accessories, painting, testing and commissioning complete.(Tested to 6 Kg/m2)Discharge : 24000 lphFiltration Rate : 15000 lit./m2/h Suggested dia app. : 1.500 m |
| 583 | Activated carbon Filter (Domestic Water)Providing and fixing vertical activated carbon filter comprising of activated carbon filter media fabricated from high performance M.S plate of minimum 6mm thick for shell & 8mm thick for dished ends with top and bottom flanged openings including top and bottom hub and lateral distribution and collection system complete with initial charge of filter media, face piping, valves, accessories, painting, testing and commissioning complete.(Tested to 6 Kg/m2)Discharge : 24000 lphFiltration Rate : 15000 lit./m2/h Suggested dia app. : 1.500 m |
| 584 | Water SoftenerProviding and fixing ‘Cation’ ION exchange water softener fabricated from minimum 8mm thick M.S. plate on shell and 10mm thick M.S. plate on dished ends complete with initial charge of filter media and ION exchange resins, face piping accessories, piping testing and commissioning complete with resins of approved quality and make and brine tank of required capacity. (Bidder must indicate type and quantity of resin used and quantity of salt required per regeneration).Minimum expected rate of flow: 24000 lph Total soft water to be produced between two regeneration: app. 150 Cu.m Max. working pressure : 4 Kg/cm2 Total soft water to be produced between two regeneration: app. 150 Cu.m |
| 585 | Providing and fixing M.S salt saturator, internally rubber lined as per requirement and externally painted with suitable anti-corrosive paint, with all required accessories for holding and supplying salt for softener complete in all respects, with electrically operated stirrer and of capacity 1000 litres. |
| 586 | Providing and fixing M.S salt saturator, internally rubber lined as per requirement and externally painted with suitable anti-corrosive paint, with all required accessories for holding and supplying salt for softener complete in all respects, with electrically operated stirrer and of capacity 1000 litres. |
| 587 | (Part - I ) ITEMS BASED ON DSR (E&M) - 2025 |
| 588 | FIRE ALARM AND PA SYSTEM |
| 589 | Supplying, installation, testing & commissioning of UL listed- central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required |
| 590 | Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required |
| 591 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 592 | Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or separate) complete with emitter and receiver including connections with remote test features etc complete as required. |
| 593 | Supplying, installation, testing & commissioning of addressable manual call point dual inbuilt isolators, complete as required. |
| 594 | Supplying, installation, testing & commissioning of addressable horn cum strobe, Shall be UL & FM listed or EN & Vds certified. complete as required. |
| 595 | Supplying, installation, testing & commissioning of UL & FM Listed- fire fighter telephone handset complete as required. |
| 596 | Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire alarm control panel complete as required. |
| 597 | Supplying, installation, testing & commissioning of UL & FM Listed - fire fighter phone jack complete as required. |
| 598 | Supplying, installation, testing & commissioning of wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required. |
| 599 | Supplying, installation, testing & commissioning of 6 inches dia, 2 watts, 70/100 volts ceiling speaker complete as required. |
| 600 | CABLING & WIRING |
| 601 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. ( FAS & PA) |
| 602 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 603 | IPABX SYSTEM |
| 604 | Supplying, Installation, Testing & Commissioning of Type 1 IP Phone having 2 VoIP account, 120 x40 DOT matrix screen with backlight, Full HD duplex speaker phone, IPV6, Gigabit Etherent, PoE etc. complete as required. |
| 605 | LAN - ACTIVE AND PASSIVE |
| 606 | Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches.Must be hot Pluggable, RoHS Complaint, etc. complete as required |
| 607 | 10 G SFP + Single Mode/Multi Mode |
| 608 | Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel.24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 609 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required |
| 610 | Copper Patch Cords of length 1m (3ft) |
| 611 | Supplying, Installation, Testing and commissioning of following CAT6A Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 612 | Copper Patch Cords of length 1m (3ft) |
| 613 | Copper Patch Cords of length 3m (10ft) |
| 614 | Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) with face plate of color as per site requirement, Minimum 750 insertion cycles, Operating Life: - Minimum 20 re-terminations, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 615 | Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. I/O operating Life should be minimum 750 insertion cycles and contact material should be copper alloy, I/O contact plating should be 50μ Gold/ 50μ Nickel minimum,IDC Connector plastic housing should be polycarbonate and UL94V-0 rated, All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 616 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. |
| 617 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required.1 Run of cable |
| 618 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non-Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required1 Run of cable |
| 619 | Supplying and drawing following core Fiber Optic Cable having corrugated steel armoring. The Fiber should be SM Fiber Central -loose tube filled with Thixotropic jelly, duly following Standards: ISO 11801, IEC 60793-1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-20-core, High quality Electro Chromium Coated Corrugated Steel tape (ECCS ) and HDPE- Sheath, Operating ambient Temperature should be – 5 0C to +50 0C and Storage Temperature shall be – 5 0C to +50 0C, Max Attenuation ± 0.36 (db/ km) at Operational Wavelength 1310 nm and ± 0.22 db / km at Operational Wavelength 1550 nm. type of fiber should be 9/125 / G.652D & Refractive Indexshould be 1.4670/1.4675. The value for Mode-filed, Cladding Diameter 9.2 ± 0.4 μm and 125 ± 0.7 μm correspondingly. The Dispersion value < 3.5 < 18 ps/nm-km and PMD value < 0.2 ps/km and Cable Cutoff wavelength < 1260 nm i/c splicing & marking etc complete as required-Single Mode 12 Core Optical fiber cable |
| 620 | Supply and fixing following port Rack Mount loaded LIU with pigtail, Front-mounted cable saddles for jumper management, suitable to manage both splices and terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in, metal splice shelf to protect the fibers, 2 fiber spools built-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers for better access to interior of LIU, Should be Single / Multi mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiral wrap tube etc complete as required24 Port LIU |
| 621 | Supplying and fixing Patch Cord of Optical Fiber Multi Mode or Single Mode LC to LC Fiber Duplex having high precision ceramic ferrule with good concentricity, Fiber corning single mode G652D, Cable Type 2mm with Mechanical specification Apex Offset < 50 µm, Fiber Height + 100 nm, End-face radius of Curvature 7mm < R < 0.2 db, Working ambient Temperature – 5 0C to +50 0C, Storage Temperature – 10 0C to +50 0C, Length -- 2meter, Type -- LC-LC Duplex etc complete as required. |
| 622 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required9U Rack |
| 623 | Supplying and fixing 42U Rack with 6 inch Castor wheels and front brake Floor Standing Rack with Main Frame Pillar of 1.6mm CRCA Sheet with removable side panels, L- Shape adjustable Vertical Mounting Rail of 2mm with 'U'Marking completely knocked-down condition (CKD) Shape, fitted with 4 number cooling fans, minimum 8nos two line cable entry/exit provision at top and bottom with rubber protection, Front door 5mm Toughened Glass with MS frame or MS perforated with lock, Rear MS vented or perforated door, Powder coated Color- RAL- 7035 or black, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. |
| 624 | Supplying and fixing Outdoor Pole/ Wall mount 6U Rack, IP55, Front Door with Filter, Louver & Unique key Lock. 3 Socket PDU 5Amp - 1 No. Self adhesive thermal foam from inside. Hood For Air Inlet at front side.1U Cantilever Tray 250mmDepth, Gasket. etc complete as required. |
| 625 | CCTV AND ACCESS CONTROL SYSTEM-4MP IP IR Dome Camera |
| 626 | Supplying Installation Testing and Commissioning of 4MP IP IR Dome Camera having following specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date & Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at nightcondition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 3) Compression (Minimum): Video:- H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 4) Wide Dynamic Range:- WDR (120dB or more) 5) Digital Noise Reduction:- DNR (3D) On/Off 6) Video Streaming & Frame Rates :- Triple streaming , configurable Main stream: 4MP (2560×1440)25/30fps , Sub streams minimum: 720P@25/30 fps 7) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser, Edge Analytics: Tripwire, Intrusion, Motion Detection 8) Cyber Security: AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade 9) Onboard Storage: Camera should support built-in Micro SD/ SDHC/ SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card. 10) Recording Management: Format SD, overwrite, storage management, video to NAS device, 11) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 13) System Capability: ONVIF, Camera shall support open source VMS 14) Ethernet: 1 RJ 45 10/100 Ethernet port 15) Audio : It should support 1 x Built-In Mic and 1/1 Alarm In/ Out for External Mic. and Speakers as per site requirement. 16) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. 17) Power Requirement: 12VDC/24 VDC/PoE (802.3af)/ePoE 18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body 19) Operating Condition:- Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non- ondensing) 20) IR life: 40000 hours or higher 21) Video Bit rate: 32 KBPS - 8 MBPS or better 22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS4MP @ 25/30fps@1440P (2560 x 1440) Dome Camera with 2.8/ 3.6/ 6/8/12 mm fixed lens (as per site requirement). |
| 627 | Supplying Installation Testing and Commissioning of 4MP IP IR Outdoor Bullet Camera having following specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date & Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at nightcondition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control, White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 3) Compression (Minimum): Video:- H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 4) Wide Dynamic Range:- WDR (120dB or more) 5) Digital Noise Reduction:- DNR (3D) On/Off 6) Video Streaming & Frame Rates :- Triple streaming , configurable Main stream: 4MP (2560×1440)25/30fps Sub streams minimum: 720P@25/30 fps 7) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser, Edge Analytics: Tripwire, Intrusion, Motion Detection 8) Cyber Security: AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade 9) Onboard Storage: Camera should support built-in Micro SD/ SDHC/ SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card. 10) Recording Management: Format SD, overwrite, storage management, video to NAS device, 11) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 13) System Capability: ONVIF, Camera shall support open source VMS 14) Ethernet: 1 RJ 45 10/100 Ethernet port 15) Audio : It should support 1 x Built-In Mic and 1/1 Alarm In/ Out for External Mic. and Speakers as per site requirement. 16) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. 17) Power Requirement: 12VDC/24 VDC/PoE (802.3af)/ePoE 18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body 19) Operating Condition:- Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non-condensing) 20) IR life: 40000 hours or higher 21) Video Bit rate: 32 KBPS - 8 MBPS or better 22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS4MP @ 25/30fps@1440P (2560x1440) Outdoor Bullet Camera with 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens |
| 628 | Supplying Installation Testing and Commissioning of PTZ (Pan,Tilt and Zoom) IP IR Camera having following spcifications and features etc :-1) IP IR PTZ Camera: Motorized PAN TILT ZOOM with IR 2) Image Sensor: 1/2.8\\" or better progressive ScanCMOS 3)Signal System: PAL/NTSC 4) Minimum Illumination: 0.008 Lux@ F1.6, AGC ON, 0 lux with IR, or better 5) Imaging: 1/1s to 1/30000s, Auto Gain Control, White Balance- Auto, Back Light Compensation, Image Rotation, Multi zone Privacy Masking (Upto 24 Area), HLC, Defog, Region Of Interest and EIS features. 6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both. 7) Signal to Noise Ratio: > 50 dB 8) Event Notification: Through Relays, E-Mails or FTP 9) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's with effective distance. The camera should have IR LED’s and cover distance up to 300 meter or above 10) Auto Tracking: The camera should be equipped with Deep-learning-based auto tracking function using simultaneously all of the panning, tilting and zooming should be available. When a motion is detected in a registered monitoring area, the camera should track the motion (object) and capture it. 11) Pre/Post Event Buffering: The camera should support atleast of 5 seconds of pre & post event buffering. 12) Presets: 300 Presets 13) Video Compression (Minimum): H.265 or better, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 14) Wide Dynamic Range: WDR (120dB or more), HLC & BLC 15) Digital Noise Reduction: DNR (2D+3D) On/Off 16) Image Setting: Rotate Mode, ROI ,EIS, Defog, saturation, brightness, contrast, sharpness adjustable through client software or web browser 17) Profile Management: User configuration import, export 18) Cyber Security: Configuration encryption, AES 256-bit Encryption, Digest, account lockout, video encryption, IP/MAC filtering, trusted boot, trusted upgrade, trusted execution 19) Onboard Storage: Camera should support built in Micro SD/SDHC/SDXC Card slot upto 512 GB . It should be supplied with minimum 128GB Memory. 20) Recording Management: Format SD, overwrite, storage management, video to NAS device, remote archive access via FTP login 21) Edge based Video Analytics & Alarm Trigger: Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection, Tripwire, Intrusion, Object Abandon/ Missing, SMD, Face Detection 22) Network Protocol: SFTP, IPv6, IPv4, DNS,NTP, HTTP, HTTPS, SNMP, TCP/IP, PPPoE, NFS, ICMP, DHCP, SMTP, RTSPS. 23) System Capability: ONVIF Profile S, G & T. CCTV Camera OEM should be fulltime member of ONVIF and quoted models should be listed on ONVIF official website (All the certifications & Credentials should be valid on the date of technical evaluation). 24) VMS: Camera shall support open source VMS 25) Connectivity: 1x LAN RJ-45 (10/100Base-T) 26) Audio Support: Audio Interface : The camera should have 1/1 Audio In/Out to connect External Mic and Speaker Audio Compression : PCM, G.711U/A, G.711MU, G.726, MPEG2-Layer2, G.722.1 27) Alarm In/Out : Alarm In/out- 7/2 Ch In/Out 28) Power Input: The camera should support simultaneous dual power input—DC/ AC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. 29) Power Requirement: 24 VDC, 2.5 A (± 25%), PoE+ (802.3at) 30) Enclosure & Weather Proof Standard: IP67 weather proof and IK10, TVS 8000V lightning proof, surge protection, voltage transient protection31) Operating Condition:- Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non-condensing) 32) IR life: 40000 hours or higher 33) Video Bit rate: 32 KBPS - 8 MBPS or better 34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS |
| 629 | 4 MP IP IR motorized PTZ (4MP @25/30fps or better) camera, Triple streaming , configurable on resolutionMain stream: 4MP@25/30 fps Sub streams :1080p@25/30 fps & D1@25/30 fps or better, varifocal lens 4.5-135mm or better with Automatic & manual Focus Adjustment provisions, 30x Optical zoom and 12x Digital zoom with angle of viewH : 57˚–2.4˚, m, PAN Travel: Pan: 0° ~ 360° endless;Manual Pan: 300° /s, Preset : 300° /s, Tilt Travel: Tilt: 0-90°, auto flip 180°, Manual Tilt: 200° /s, Preset : 300° /s |
| 630 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Frequency tested up to- 250 MHz minimum, Tensile Strength -11 KG or better, Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. Warranty- 25-year systems warranty; Warranty to cover Bandwidth of the specified and installed cabling system, and the installation costs. Site certificate must be issued by OEM. |
| 631 | Part - II Market Rate Items |
| 632 | FIRE ALARM AND PA SYSTEM |
| 633 | Supply, Installation, Testing and Commisioning of 10 Loop- UL listed and FM approved of addressable, Peer to Peer Networkable, Analog Fire Alarm Panel shall be running on full digital protocol with 32 bit Microprocessor based panel , Networkable analogue addressable type Fire Alarm Control Panel . The Panel shall be complete with 6\\" color liquid-crystal display (LCD). LCD Display status highlights Alarm events appear in red; Trouble events appear in yellow; Supervisory events in blue, and Security events in magenta. System should be capable to have intelligent initiation devices per panel. Each addressable loop shall be capable of not less than 250 addresses per loop configuring either as all detectors or modules or any mix of both. The panel shall have the Fire Fighter Touch Screen Graphical Display panel to inform & guide Fire Fighter for carring out Fire Fighter operation. The display shall have Hazmat icons indicating the presence of explosive gas, liquids, poison,fumes etc . To expedite system troubleshooting, the system cards shall have ground fault detection and diagnostic LEDs by card. In the display,simple building floor plan can be loaded in bitmap or jpeg format, On the map, the user will see an icon indicating the location of the event in the building in addition to a 'You-Are-Here' symbol to tell the responding person exactly where they are in the building in relation to the event. The system shall be polarity insensitive. The panel shall support degrade mode operation and shall have battery backup of 24 hrs in normal condition and 30 minutes in Alarm condition. The Main Panel in Basement shall be a global Panel with Modbus Output for BMS Integration, Redundancy in CPU to be considered for all Panels, in line with Technical Specifications. |
| 634 | Supply, Installation, Testing and Commisioning of 2 Loop- UL listed and FM approved of addressable, Peer to Peer Networkable, Analog Fire Alarm Panel shall be running on full digital protocol with 32 bit Microprocessor based panel , Networkable analogue addressable type Fire Alarm Control Panel . The Panel shall be complete with 6\\" color liquid-crystal display (LCD). LCD Display status highlights Alarm events appear in red; Trouble events appear in yellow; Supervisory events in blue, and Security events in magenta. System should be capable to have intelligent initiation devices per panel. Each addressable loop shall be capable of not less than 250 addresses per loop configuring either as all detectors or modules or any mix of both. The panel shall have the Fire Fighter Touch Screen Graphical Display panel to inform & guide Fire Fighter for carring out Fire Fighter operation. The display shall have Hazmat icons indicating the presence of explosive gas, liquids, poison,fumes etc . To expedite system troubleshooting, the system cards shall have ground fault detection and diagnostic LEDs by card. In the display,simple building floor plan can be loaded in bitmap or jpeg format, On the map, the user will see an icon indicating the location of the event in the building in addition to a 'You-Are-Here' symbol to tell the responding person exactly where they are in the building in relation to the event. The system shall be polarity insensitive. The panel shall support degrade mode operation and shall have battery backup of 24 hrs in normal condition and 30 minutes in Alarm condition. The Main Panel in Basement shall be a global Panel with Modbus Output for BMS Integration, Redundancy in CPU to be considered for all Panels, in line with Technical Specifications. |
| 635 | Supply, installation, testing and commissioning of Addressable UL listed and FM approved Intelligent Addressable microprocessor based smoke detector inbuilt isolator or isolator mounting base complete as required, complete as required and as per Tender specifications. |
| 636 | Supply, installation, testing and commissioning of Addressable UL listed and FM approved Intelligent Addressable microprocessor based Thermal detector with rate of rise cum fixed temperature thermistor detector inbuilt isolator or isolator mounting base complete as required, complete as required and as per Tender specifications. |
| 637 | Supplying, installation, testing & commissioning of UL listred- DC 24V - 5Amp power supply with battery backup for FAS Hooter and Beam detector. |
| 638 | Supplying, installation, testing & commissioning of addressable fire control module, with dual built-in isolator, complete as required. (Note - In case inbuilt isolators are not present, Bidders to consider extra forward & backward isolators for Class-X wiring, in the same line item) |
| 639 | Supply Installation, Testing & Commissioning of UL listed Intelligent addressable monitor module with dual built-in isolator. complete as required and as per Tender specifications. |
| 640 | Supplying, installation, testing & commissioning of addressable fire relay module complete as required. |
| 641 | Supplying, installing, testing and commissioning of Digital Voice Evacuation Master controller with built in Amplifier. The System meet the standards of BS EN54 - 32 & EN 60849. The System have Built in 500W Class-D Amplifier and it should be capable for the EVAC, Paging, PA and BGM functions. The Controller have SD card option to store the EVAC and Alert Voice Message. The Controller have Speaker line supervision record out and amplifier auto changeover. The Controller have following features: Separate Zone volume control at the front side of panel, Status indications on the Panel for EVAC,Fault ,AC,DC ,Fault, ALERT & Fireman mic, Zone capacity up to 96 Zones, 8 programmable Control Input and output, Fireman Microphone with High Priority, THD<1%, Frequency response 80Hz - 20kHz, Up to 1000 Record files, 100V Class-AB Speaker Output. complete as required and as per Tender specifications. |
| 642 | Supplying, installing, testing and commissioning of Digital Voice Evacuation Router(expansion) controller with built in Amplifier. The System meet the standards of BS EN54 - 32 & EN 60849. The System have Built in 500W Class-D Amplifier. The Router have following features: Separate Zone volume control at the front side of panel, Status indications on the Panel for EVAC,Fault ,AC,DC ,Fault, ALERT, Zone capacity up to 96 Zones, 8 programmable Control Input and output, Frequency response 80Hz - 20kHz, Up to 1000 Record files, 100V Class-AB Speaker Output. complete as required and as per Tender specifications. |
| 643 | Supply, Installation, Testing & Commissioning of 500W Class-D Digital Power Amplifier with Switch power technology for power electricity saving. Amplifier shall have Following Features: 250W RMS per Channel, Amplifier Output 100V & 8 Ohm, THD < 0.1%, Frequency Response 50Hz - 20kHz, AC & DC Fuse, SNR > 80dB Short Circuit, Power, Tempreature, Overload Protection, Wide AC input switchable between 115V and 230V, Support 24V DC operation system, complete as required and as per Tender specifications.complete as required and as per Tender specifications. |
| 644 | Supply, Installation, Testing & Commissioning of Touch Screen Microphone for the Paging Announcement with Following features:- Remote paging microphone with touch screen display. 120 zone selection buttons through touch screen and all zone/talk button. Support PPT and normal paging two modes. DC24V power supply or POE. Frequency Response - 80Hz-14kHz THD <1% at RMS,1KHz S/N Ratio>70dB., complete as required and as per Tender specifications.complete as required and as per Tender specifications. |
| 645 | LAN - ACTIVE AND PASSIVE |
| 646 | Supply, Installation, Testing & Commissioning of 24×10/100/1000 Mbps ports, 4×10/25 GbE SFP28 stacking/uplink-ports, long distance stacking of min 8 switches required . Switch OS should be NDcPP certified. Switch should be TEC certified, ROHS6, 3 years OEM warranty with advance hardware replacement and 3 years OEM 24x7x365 remote TAC support . 4GB RAM, 8GB Flash, 4MB buffer. All types of Switches, transceivers, WIFI,WLC,AAA should be from the same OEM for better compatability,management and after sales support.For detailed specifications please refer tender document. ( For CCTV and Access control) |
| 647 | Supplying & Fixing of CAT 6A 24 PORT SHIELDED PATCH PANEL LOADED, Patch Panel Should be made of cold rolled steel, in 24 port configurations. Should come with 24 jack, Each I/O for the Patch Panel must provide a Shutter to avoid dust and contaminates entering the jack & for 100% dust free environment. I/O operating Life should be minimum 750 insertion cycles and contact material should be copper alloy. IDC Connector plastic housing should be polycarbonate and UL94V-0 rated. Operating Life sholuld be Minimum 20 reterminations and contact material should be copper alloy. Should have port identification numbers on the front of the panel.Should have self-adhesive, clear label holders (transparent plastic window type) and white designation labels with the panel, with optional color labels / icons.Each port / jack on the panel should be individually removable on field from the panel.Patch Panel Should be of shielded type. Patch Panel Should be RoHS Compliant, complete as required and as per Tender specifications. |
| 648 | Supply , Installation , Testing and Commissioning of 10Gbps Distribution Switch 24-port 1/10 Gbps SFP+ pors with 2-ports 40/100 GbE uplink/Stacking ports . The switch should be scalable to support either 4x10G SFP+ or 2x40G QSFP+ or 1x100G QSFP+ in future . Switch should have field replaceable redundant power supplies and FANs, switch OS should be NDcPP certified. Switch should be TEC certified, ROHS6, 3 years OEM warranty with advance hardware replacement and 3 years OEM 24x7x365 remote TAC support . 4GB RAM, 4GB Flash, 8MB buffer. Switch should support stacking of min 8 switches .All types of Switches, transceivers, WIFI,WLC,AAA should be from the same OEM for better compatability,management and after sales support.For detailed specifications please refer tender document. (Core switch in HA mode) 2 for Internet, 2 For Intranet (SAP+IPBAX) and 2 for CCTV and ACS |
| 649 | Supply, installation, testing and commissioning of DAC CABLE 40G FOR Distribution switch |
| 650 | Supply, installation, testing and commissioning of DAC CABLE 10G FOR Access switch |
| 651 | Supplying Installation testing and Commissioning of L2 Manageable GigE fixed chassis 24×10/100/1000 Mbps ports, 4×10/25 GbE SFP28 stacking/uplink-ports, long distance stacking of min 8 switches required, Switch OS should be NDcPP certified , Switch should be TEC certified, along with 5 years OEM TAC support and 3 years advance hardware replacement warranty, complete as required and asper Tender specifications. Note- 15% spare ports for future requirement. ( FOR Internet Points) |
| 652 | Supplying Installation testing and Commissioning of L2 Manageable GigE fixed chassis 48×10/100/1000 Mbps ports, 4×10/25 GbE SFP28 stacking/uplink-ports, long distance stacking of min 8 switches required, Switch OS should be NDcPP certified , Switch should be TEC certified, along with 3 years OEM TAC support and 3years advance hardware replacement warranty, complete as required and as per Tender specifications. Note- 15% spare ports for future requirement. ( FOR Internet points) |
| 653 | Supply, Installation, Testing & Commissioning of 24×10/100/1000 Mbps ports, 4×10/25 GbE SFP28 stacking/uplink-ports, long distance stacking of min 8 switches required . Switch OS should be NDcPP certified. Switch should be TEC certified, ROHS6, 3 years OEM warranty with advance hardware replacement and 3 years OEM 24x7x365 remote TAC support . 4GB RAM, 8GB Flash, 4MB buffer. All types of Switches, transceivers, WIFI,WLC,AAA should be from the same OEM for better compatability,management and after sales support.For detailed specifications please refer tender document. ( Access switch for Data and IPBAX) |
| 654 | Supply, Installation, Testing & Commissioning of 48×10/100/1000 Mbps PoE+ ports, 4×10/25 GbE SFP28 stacking/uplink-ports, 370 W PoE budget,long distance stacking of min 8 switches required . Switch OS should be NDcPP certified. Switch should be TEC certified, ROHS6, 3 years OEM warranty with advance hardware replacement and 3 years OEM 24x7x365 remote TAC support . 4GB RAM, 8GB Flash, 4MB buffer. All types of Switches, transceivers, WIFI,WLC,AAA should be from the same OEM for better compatability,management and after sales support.For detailed specifications please refer tender document. ( Access switch for Data and IPBAX) |
| 655 | Supply, installation, testing and commissioning of LC-LC- 25G SFP Single mode module for Building to Building Connectivity |
| 656 | Building Management Workstation:SITC of Tower Server Grade with Intel i-7 quadcore processor or Latest Technology, Windows® Server 2025 operating System, 1 TB HDD, 32 GB RAM, Enhanced graphic Card, DVD Combo Drive, Ethernet Port with 32\\" color monitor flat screen LED display, multimedia keyboard & optical mouse and microsoft office 2016 and anti virus as per Specification. |
| 657 | SITC of A4 B/W laser Printer |
| 658 | BMS Software:SITC of the window based graphical software for IBMS system with 3 Nos concurrent Client and 15 Nos of users license for Operator workstation. The following software packages shall have below minimum features and compliances. a) 3D & Scalable Vector Graphics (SVG) technology dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility b) BTL,UL,EN Certified Systemc) HTML5 based Web-Server software shall permit use of Standard Web-Browsers such as Microsoft Edge, Google Chrome, Mozilla Firefox, etc d) Seamless integration of Security certificates within customer IT infrastructure, Microsoft’s active directory-based authentication, Use of network infrastructure that supports physical network or VLAN segmentation, End-to-end encryption from client to server, End-to-end encryption between servers, Certificate-based data exchange, Encrypted backups e) Software shall have audit trail feature and Cricital alarms shall be sent over Email.f) Software should have capability to add minimum 40 servers under it g) It should supports the Enrollment over Secure Transport (EST) certificate protocolh) Ability to provide data to other systems through MQTT and / Or REST web services interface as an optional feature.( if required in future)h) Reports - Customized reports for Trends and alarm with Graphic screen shots. i) Alarm Escalation: Assisted treatment of alarms which helps in Predefined & fast intervention steps for faster response. Minimum number of active and viewable alarms shall be 10,000. It shall be possible for the user to sort, filter and search on any available criteria such as priority, category, origin, alarm type, etc. On alarm, it shall be possible to notify via email to a preconfigured list of recipients . through a Simple Mail Transfer Protocol (SMTP) or secure email using Simple Mail Transfer Protocol Secure (SMTPS). No special software interfaces shall be required and no email client software must be running in order for email to be distributed.j) The software should natively communicate with three of the most popular standards for buildings: BACnet, LonWorks, and Modbus k) Capability to add new and customisable user Intuitive Dashboards |
| 659 | Third Party Integartion: UL & BTL listed Gateway / Open Protocol Software for integrating the foll third party system communicating on one of the Standard Open Protocols such as BACNet , MODBUS, Lonworks- Vendor to consider required No. of Integrators for qty's mentioned in IO summary. Integrator/Gateway/supervisory controller shall be of the same OEM as field controllers & software. Gateway should be capable of auto-addressing. Integrator should also support TLS encyrption for data transport & Bacnet Secure Connect.Also Integrator should support IP whitelisting as per latest cybersecurity norm. Integrator should support I/Os along with ports for integration. Two on-board ethernet port & two RS-485 port should be inbuilt on integrator.Integration of following services should be considered as per IO summary & Specification. Integrator, controllers & software should be of same make. |
| 660 | DDC Field Controller: Supply, Installation, Testing and Commissioning of DDC should have on-board one RS-485 port for third party integrations.DDD should have inbuilt RTC and backup time upto 7days. DDC should be battery free with inbulit memory backup. DDC should have min RAM 256 MB & 4GB flash memory. DDC should have 16-bit A/D Converter resolution.DDC should support SMTP or SMTPS SSL/TLS based authentication, enables sending email messages triggered by schedule or alarm.All DDC Controllers shall be provided with hinged doors with locking facility. Apart from the controllers, the enclosers shall house the terminal blocks, load relays and associaetd equipment. The internal wiring in the enclosure shall be factory wired. The packaging shall be such that complete installation of the field equipment and field wiring can be done prior to the installation of the electronics. The controller shall be independent in operation and the failure of any other device / controller or the operator workstations, shall not cause any disruption to the function of the rest of the system. The DDC controllers shall have the facility to implement user modifiable time schedules as daily, weekly, monthly annual temporary schedules. |
| 661 | DDC Controllers for Chillers, Primary Pumps, Secondary Pumps, Condenser Pumps, Cooling Towers. |
| 662 | DDC for AHU/CSAHU ( 2 AHU Units/DDC) |
| 663 | DDC for Pressurization Fan (4 Fans/DDC) |
| 664 | DDC for Emergency Roof Extractor Fan (4 Fans/DDC) |
| 665 | DDC for Fresh Air Aixla Fan(4 Fans/DDC) |
| 666 | DDC for Emergency Exhaust Axial Fan (4 Fans/DDC) |
| 667 | DDC for Water Treatment Plant |
| 668 | DDC for firefighting/plumbing |
| 669 | DDC for HT/LT Panels, Transformer |
| 670 | DDC for Water Tank, Sump Pump. |
| 671 | Supply, Installation, Testing and Commissioning of Temperature Sensor with Stainless Steel thermowell, PT1000 or NTC output (±0.2°C~0.5°C Accuracy, SS304 Probe & Thermowell MOC, IP65 Protection). |
| 672 | Supply, Installation, Testing and Commissioning of Piezo Resistive Type Water Static Pressure Transmitter with 4-20mA/0-10VDC output (±0.5% Accuracy, IP65 Protection, SS316L Diaphragm MOC) |
| 673 | Supply, Installation, Testing and Commissioning of Submersible type Water Level Transmitter with 4-20mA/0-10VDC output (±0.5% Accuracy, 0-5meter Tank Height) |
| 674 | Supply, Installation, Testing and Commissioning of Over Flow Indicator |
| 675 | Supply, Installation, Testing and Commissioning of Water Differential Pressure Switch (1SPDT Contacts, IP65 Protection, Fireproof ABS MOC) |
| 676 | Supply, Installation, Testing and Commissioning of Air Differential Pressure Switch (1SPDT Contacts, IP54 Protection, Fireproof ABS MOC) ( DP switch Air, DP switch Filter) |
| 677 | Supply, Installation, Testing and Commissioning of Duct type Temperature Transmitter with 4-20mA/0-10VDC output (±2°CTd & ±0.3°C Accuracy, IP65 Protection, Stainless Steel Probe required for both Room type/Duct type) |
| 678 | Supply, Installation, Testing and Commissioning of Duct type Temperature & RH Transmitter with 4-20mA/0-10VDC output (±0.5°C & ±2%RH Accuracy, IP65 Protection, Dip Switch Settable Responce Time) |
| 679 | Supply, Installation, Testing and Commissioning of Outside Temp/RH Sensor with 4-20mA/0-10VDC output (±0.5°C & ±2%RH Accuracy, IP65 Protection, Dip Switch Settable Responce Time) |
| 680 | Supply, Installation, Testing and Commissioning of Flame DP switch |
| 681 | Supply, Installation, Testing and Commissioning of Flame Proof Flow Meter |
| 682 | Supply, Installation, Testing and Commissioning of Flamerproof Submersible type Diesel Level Transmitter with 4-20mA/0-10VDC output (±0.5% Accuracy, 0-1meter Tank Height) |
| 683 | Flame Proof Level Switch |
| 684 | Supply, Installation, Testing and Commissioning of Wall type CO2 Transmitter with 4-20mA and 0-10VDC both output (MEMS Principle, IP41 Protection for Room type/IP65 for wall type, Dip Switch Settable Range & Responce Time) |
| 685 | Supply, Installation, Testing and Commissioning of CO Sensor |
| 686 | Supply, Installation, Testing and Commissioning of Room type Combined Indoor Air Quality Transmitter with RS485 Modbus output with display (IAQ Parameters: CO2, PM2.5, PM10, Temp. & RH) as per required tender technical specifications. |
| 687 | Supply, Installation, Testing and Commissioning of Room type Combined Indoor Air Quality Transmitter with RS485 Modbus output with display (IAQ Parameters: CO2, PM2.5, PM10, Temp. & RH) as per required tender technical specifications. |
| 688 | Supply, Installation, Testing and Commissioning of Current Relay |
| 689 | Supply, Installation, Testing and Commissioning of Electromagntic Water Flow Meters- 400mm dia |
| 690 | Supply, Installation, Testing and Commissioning of PH Transmitter with PH Electrode with Temperature Compensation (Backlit LCD display, 4-20mA and RS485 Modbus both output) |
| 691 | Supply, Installation, Testing and Commissioning of TDS Transmitter with TDS Electrode with Temperature Compensation (Backlit LCD display, 4-20mA and RS485 Modbus both output) |
| 692 | Supply, Installation, Testing and Commissioning of Water Hardness Analyzer with mounting accessories (0-250PPM range, ±20PPM accuracy, Backlit LCD display, 4-20mA output) |
| 693 | Supply, Installation, Testing and Commissioning of Duct mounted C02 Sensor , 4-20mA/0-10VDC |
| 694 | Supply, installation, testing and commissioning of Layer 2 managed Gigabit switch. The switch shall have 2 RSTP enabled ports to communicate with other switches to built a star topology network with redundancy on CAT6 armourded UTP cable within the building complete as per specifications and as required for BMS DDC Panel Networking. 24 Port Switch |
| 695 | Supply, Installation, Testing and Commissioning of 2 x 1.5 sq.mm Annealed Tinned Copper Shielded armoured cable for signal and power as per specification. (for I/O points hard wired to DDC). |
| 696 | Supply, Installation, Testing and Commissioning of 4 x 1.0 sq.mm Annealed Tinned Copper Shielded armoured cable for signal and power as per specification. (for I/O points hard wired to DDC). |
| 697 | Supply, Installation, Testing and Commissioning of 3 x 1.5 sq.mm Annealed Tinned Copper Shielded armoured cable for signal and power as per specification. (power Cable). |
| 698 | RODENT, WATER LEAK DETECTION SYSTEM |
| 699 | Supply installation testing and commissioning of RS485 based Controller for active control over transducer & functioning of system. The maximum coverage for single controller among two operating rooms is approx 150m. Controlling upto 20-24 Transducert. |
| 700 | Supply installation testing and commissioning of Ultrasonic Rodent Repellet Transducers (coverage of 150sqft) |
| 701 | Supply installation testing and commissioning of MS Powder coated Stand Bracket, |
| 702 | Supply installation testing and commissioning of Electrical Cables in 20 MM PVC Conduit for trsnducer to controller. |
| 703 | Supply installation testing and commissioning of 2 Zone Hybrid Control Panel with LCD Keypad to make 2 Zone for identification of Water Leakage in the Specific Zone complete with transformer & cabinet With battery backup. |
| 704 | Supply installation testing and commissioning of Water leak detection module. Each Zone will have a separate Module to Identify the Leakage in specific Zone, |
| 705 | Supply installation testing and commissioning of 20 Mtrs. Length water leak detection cable, |
| 706 | Supply installation testing and commissioning of Electronic Hooter, |
| 707 | Supply installation testing and commissioning of LV Electric 2CX1.5sqmm armoured cable for Hooter to controller & module. |
| 708 | AV SYSTEM |
| 709 | Supply, Installation, testing and commissioning of Screen size: 98″ diagonal, Resolution: UHD 4K – 3,840 × 2,160 pixels (16:9 aspect ratio),Brightness (typical): 500 nits, Contrast ratio: e.g., 5,500 :1, Operation hours: Designed for 24 × 7 operation with 3 years hardware warranty. |
| 710 | Supply, Installation, testing and commissioning of Screen size: 65″ diagonal, Resolution: UHD 4K – 3,840 × 2,160 pixels (16:9 aspect ratio),Brightness (typical): 500 nits, Contrast ratio: 4000 :1, Operation hours: Designed for 24 × 7 operation with 3 years hardware warranty. |
| 711 | Supply, Installation, Testing & Commissioning of 24×10/100/1000 Mbps ports, 4×10/25 GbE SFP28 stacking/uplink-ports, long distance stacking of min 8 switches required . Switch OS should be NDcPP certified. Switch should be TEC certified, ROHS6, 3 years OEM warranty with advance hardware replacement and 3 years OEM 24x7x365 remote TAC support . 4GB RAM, 8GB Flash, 4MB buffer. All types of Switches, transceivers, WIFI,WLC,AAA should be from the same OEM for better compatability,management and after sales support.For detailed specifications please refer tender document. |
| 712 | Supply, Installation, Testing And Commissioning of Video Conferencing system for large room- Codec, 3x HDMI output, 4K Camera, 2x Microphone, built in USB Pass thru functionality, 3x 3.5 mm line in & 1x 3.5mm line out, 1x LAN Port, 9 Meter Cable, 10\\"inch Touch Controller, power adaptor. with 2 years hardware warranty. For detailed specifications please refer tender document. |
| 713 | Supply Installation Testing & Commissioning of HDMI Transmitter and Receiver Set for tranmitting the signal upto 70meter in 4K resolution . |
| 714 | Supply, Installation,Testing & Commissioning of table top gooseneck chairman microphone unit, with speaking button & indicating lamp.With president priority key, Auto cut function . the microphone should , adopted CAT 5(6 or 7 is ok)Cable RJ45 crystal rock, eectively resistance the interference and more reliable to transmission & shall have Zinc alloy material bottom, solid and generous, the gooseneck with red working indicating light with inbult digital processing unit.Type: CapacitanceDirectivity: Uni-directionFrequency Response: 60Hz-16KHzSensitivity: -45±3dB @ 1KHzInput Voltage: DC24V(power supply by host)Output impedance: 1KohmSNR: 68dB(A)Output jack: RJ45 Crystal standInput wire: 2 meter RJ45 CAT 5 |
| 715 | Supply, Installation,Testing & Commissioning of table top gooseneck delegate microphone unit, with speaking button & indicating lamp., Auto cut function . the microphone should, adopted CAT 5(6 or 7 is ok)Cable RJ45 crystal rock, eectively resistance the interference and more reliable to transmission & shall have Zinc alloy material bottom, solid and generous, the gooseneck with red working indicating light with inbult digital processing unit.Type: CapacitanceDirectivity: Uni-directionFrequency Response: 60Hz-16KHzSensitivity: -45±3dB @ 1KHzInput Voltage: DC24V(power supply by host)Output impedance: 1KohmSNR: 68dB(A)Output jack: RJ45 Crystal standInput wire: 2 meter RJ45 CAT 5( Shure/Televic./Heinrich) |
| 716 | Supply, Installation,Testing & Commissioning of Network digital conference system adopted modern digital mainstream connection method: RJ45 cable, interface, adopts originally imported high Performance CPU processor, fully digital signal processing can eectively enhance the whole system of Anti- interference ability, communication stability and confidentiality,the system adopted encryption intelligencedigital control technology. Connected with computer support USB interface, TCP/IP internet interface,Wi-Fi LAN and RS232 serial port control such multiple selection.Software supports venue layout, online testing, venue microphone ON/OFF control and adjust the Volume. The new generation multifunctional digital video tracking conference system of it can divorced from the computer operation.Output Impedance :REC : 200ohm , LINE : 200ohm,BALANCE : 300ohm, UNBALANCE : 400ohmS/N: 78dB(1KHz THD1% )Nominal voltage :AC110~270V±10% 50HzRated power: 100WFrequency response: 100Hz-12.5KHzSize: 480X270X88mm(19”International standard Rack(Shure/Televic./Heinrich) |
| 717 | Supply, Installation,Testing & Commissioning of 5\\"+1.5\\" Coaxial Ceiling speaker with ABS cover, 30W/15W, 100V, & 15/7.5W at 70V cutout 210 mm, ABS baffle & back cover, metal grille. The Speaker shall have following Feature: Max SPL > 105 dB, Sensitivity 93dB (1W/1M),Frequency Response 90-20kHZ. |
| 718 | Supply Installation Testing & Commissioning of 500W RMS DualChannel Class-D Digital Power Amplifier with Switch power technology for power electricity saving. Amplifier shall have Following Features: 250W RMS per Channel, Amplifier Output 100V, Short Circuit, Power, Tempreature, Overload Protection, Auto Cooling Fans. THD <0.1%, Frequency Response 20Hz - 20kHz, AC & DC Fuse, SNR >80dB. ( Bose/QSC/Heinrich) |
| 719 | Supply Installation Testing & Commissioning of 8-channel Phantom Power Microphone/Line input, 8-channel circuit Output; Loudspeaker Management System Frequency Response 20Hz ~ 20KHz, THD <0.003%, Channel Seperation >92dB,Seperate Mute Control each channel,CMRR>80dB, 12 independent parametric EQ, adjustable gain range up to 20dB, With, RS232 and internet to connect PC,High-speed processing DSP Chip, the new generation of AFC algorithm to eliminate the feedback faster and make system more stable.Application includes Auto Mixer (Limiter threshold and Gain), Routing, Audio Processing and special signal extension Processing.. - (Crestron/Bose/Heinrich) |
| 720 | Supply Installation testing and commissiong ofcable cubby having • 2 x HDMI input• 2 x Universal Power Socket• 1x USB Input• 2x RJ45 input• The cable cubby shall be flushed mounted type and shall be available in two different color ( Silver/Black)( Crestron/Extron/Heinrich) |
| 721 | Supply Installation Testing & Commissioning of 16 X 8 HDMI Matrix Switcher with HDCP Compliant, HDMI and HDCP as per technical specification. Card-insert construction, input signal types, VIDEO, VGA, YPbPr, DVI, HDMI, 3G-SDI, Fiber, HDBaseT, output signal types, HDMI, VGA format, DVI, HD BaseT, Fibre. Supporting forward direction high speed channel and embedded control signal separation switching mode. Supporting entire HD, HDPC,1920x1200P @ 60 24bit, HSTV,1920x1080 @60 36bit, Supporting entire HD, HDMI 1.4, HDCP 1.4, and DVI 1.0 protocol. Supporting high color depth and high 3.25Gbps speed 2 RS-232 communication interfaces 1 network interface and can be remote controlled by Ethernet, supporting 8 user connection simultaneously.(Crestron/Extron/Heinrich) |
| 722 | Supply Installation Testing & Commissioning of of Wireless Presentation system, supporting upto 4 user simultanously share the single screen , wireless video transmission at min 1080p @ 30 fps, VGA & HDMI output. With inbuilt WAP or supplied with external WAP. Simultaneous four feed viewing.It shall support iOS8 above,AirPlay mirroring,support multi-screens mirroring, Android 5.0 and above,(Crestron/Extron/Heinrich) |
| 723 | Supply Installation Testing and Commissioning of HDMI Audio Deembedder, with 1 HDMI connector Input and 1 HDMI connector, 1 TOSLINK® optical digital audio connector, 1 S/PDIF digital audio on an RCA connector, 1 unbalanced stereo audio on a 3.5mm mini connector Output as per technical specification. (Crestron/Extron/Heinrich) |
| 724 | Supply & Fixing of HDMI Cable, Data Cable, LR cable Video Cable for interconnection complete above system OEM Approved complete in all respect. |
| 725 | Supplying & Fixing of Floor Standing Network/Server Rack - 32U / 800w / 800d, with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of 500Kgs. Side Panels - 32U/800d Front MS Door Perforated honeycomb 32U/800w Rear MS Door Split Perforated honeycomb 42U/800wFan 90CFM 230V AC, 4” dia Castors with Brake (set of 4) Vertical Cable manager 80mmW 32U Shelf, Stationery 700mm N/W PDU 12Sockets 5/15Amps with MCB Mounting Hardware (Pkt. Of 20) earthing Kit 150mmH Cable manager 1U MS with Loops complete in all respect. |
| 726 | BILL OF QUANTITIES FOR HVAC WORKS |
| 727 | DSR ITEMS - 2025-WATER COOLED SCREW CHILLERS |
| 728 | Supplying, Installation, Testing and Commissioning of following capacity floor- mounted VFD (Variable Frequancy Drive) Operated water cooled screw-type chiller machine complete with single/multi semi-hermatic mono/multi screw type compressor, with independent circuits, water-cooled Shell & Tube type condenser, Shell & Tube horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with 19 mm nitrile rubber insulation i/c suitable foundation/mounting structure made ofRCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-in-charge, common base frame, interconnected copper refrigerant piping and wiring, vibration Isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly Chlorofluorocarbons (CFC)-free refrigerant gas R-134A. The refrigerant flow control shall use an electronic expansion valve. The chiller shall be designed for a Water Side working pressure of 150 psig and hydraulically tested at 1.5 times of design pressure . A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. The chiller shall be Building Management System (BMS) compatible The system shallbe in confirmation to IS : 16590 and CPWD Specification as amended upto date. BEE Star labeling and CPWD Specification as amended upto date and tested as per IS 16590.Chilled water Leaving Temp. (6.67°C)Chilled water Entering Temp. (12.2°C)Evaporator fouling factor = 0.018 m2 °C/kWCondenser water Entering Temp. (32.2 °C)Condenser water Leaving Temp. (36.4 °C)Suitable for Seismic Zone and Altitude as per location/site.Microprocessor based controller.301TR - 450 TR BEE 4 Star Rated |
| 729 | Supplying, Installation, testing and commissioning of Induced Draft counterflow cooling Towers(CTI approved). The Cooling Tower shall be of Fiber Reinforced Plastic (FRP) Construction. The casing, basin/sump, fan deck and fan cylinder shall be of FRP, with direct driven fans, Galvanised hardware complete with sump and drain connection with suitable valve, PVC Honey comb fill, louvers, drift eliminator completewith spray nozzle having self rotating sprinklers, steel ladder, Isolating switch and other accessories to make it fully operational and maintaince National Accreditation Board for Testing and Calibration Laboratories (NABL) & positioning of cooling tower at Terrace of Building. Propeller Type Fan, weather proof IP 55 and Direct driven.The fan motor shall be premium efficiency IE3 class , as per IS 12615 The Cooling tower shall be capable to communicate effectively with Building Management System (BMS). Range of CT: 6 0C. Designed Duty Conditions :- EWT, LWT , D/WBT Complete as per CPWD specification/drawings and as directed by Engineer-incharge.( Note - Cooling tower size depends on the ambient temperature conditions, contractor must check the required design temperature).1500 GPM |
| 730 | Supplying, installation ,testing and commissioning of Ceiling Concealed Fan Coil Unit comprising of 3 rows deep chilled water cooling coil, centrifugal blowers, fractional horse power (FHP) motor, synthetic fibre filters, insulated & extended condensate drain pan along with L-type auxillary tray, casing, coil piping connections, condensate drain piping connections & wiring. Fan coil units shall be suitable for operation on 220 + 10% Volts, 50Hz, single phase power supply of following sizes & capacities. Complete as per CPWD specification and as directed by Engineer-in-charge.2.5 TR, 1000 CFM with 3 Row Cooling Coils |
| 731 | Supplying, Installation, Testing and Commissioning of Air Cooled Cassette type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R410A/R-407 Green Refrigerant, wireless Remote, inbuilt drain pump, suitable for 400/230V, 50 Hz ,1 /3 phase AC supply, including surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5.5 Mtr (IDU to ODU), copper power and control cable upto 5.5 Mtr (IDU to ODU) including drain pipe, the system shall be capable of performing cooling, dehumidification, Air circulation, filteration & ventilation of following capacity with Scroll/rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB) as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards/Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required. |
| 732 | 2.0 TR with 5 Star BEE Rating |
| 733 | 2.5 TR with 5 Star BEE Rating |
| 734 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 735 | 1.0 TR with 5 Star BEE Rating |
| 736 | 1.5 TR with 5 Star BEE Rating |
| 737 | 2.0 TR with 5 Star BEE Rating |
| 738 | Supplying, Installation, Testing and Commissioning of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on R 32/R-410A /R-407 Green refrigerant comprising of Scroll type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system with min 5 year (OEM) warranty for both compressor and Printed Circuit Board (PCB) , Suitable capacity squirrel cage induction motor having class 'B' insulation suitable for operation on 415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine Isolation / disconnect switch, valves and accessories to inter connect compressor and condenser including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L ,U/V, phase reversal protection, single phase preventors i/c copper conductor control and power cable and drain pipe of suitable size and length etc complete as required. The total cooling capacity/heating capacity of tested unit shall have a capacity as per relevant IS code. The lab testing reports as per IS: 8148 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per ISO/International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification as required-5.5 TR (3.2 EER) |
| 739 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). |
| 740 | 15300 CMH |
| 741 | 20400 CMH |
| 742 | 23800 CMH |
| 743 | 28900 CMH |
| 744 | 39100 CMH |
| 745 | Supplying, Installation, testing and commissioning of Factory built ceiling suspended chilled water double skin type horizontal/vertical air handling units of following capacity, made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with Polyurethane Foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with Totally Enclosed Fan Cooled (TEFC) drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for Variable Frequency Drive (VFD) applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometres (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration Isolation arrangement, noise level shall not exceed 70 dB. AHU shall be AHRI/Eurovent certified, fan shall be AMCA certified etc. Complete as per CPWD specification/drawings and as directed by Engineer-in-Charge. (Total static pressure considered is 50 mm WG). |
| 746 | 5000 CFM |
| 747 | 8000 CFM |
| 748 | 4000 CFM |
| 749 | 1600 CFM |
| 750 | 2500 CFM |
| 751 | 3000 CFM |
| 752 | Supplying, installation, testing and commissioning of Chilled Water Ceiling Suspended Hydronic Cassette type fan coil unit, four(4) way directional flow, low noise, each complete with two(2) rows of deep chilled water cooling coil, multi-blade centrifugal fan, test reports from National Accreditation Board for Testing and Calibration Laboratories (NABL)/AHRI accerdited lab, electronic air cleaning system, required set of ball valves with & without strainers & 2 way Motorized valve, insulated condensate drain pans with drain pump assembly & drain pump failure alarm, pipe connections through copper pipes, Infra-red remote control, Liquid Crystal Display (LCD), four (4) speed motor , fan four(4) direction air flow, auto swing louver, decorative panel etc., condensation drain connections, All units shall be suitable for 220 +/- 10% Volts, 50 Hz, single phase power supply etc. complete as per specification. The wireless Remote temperature control / thermostat shall have memory back up for set point re-store in case of power failure and re-start. Four(4)hanger rods with required anchoring fasteners, hooks, washers etc.complete as per CPWD specification and as directed by Engineer-in-charge.1.5 TR nominal capacity with 600 CFM air quantity. |
| 753 | Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastomeric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respectNote:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 754 | 300 mm dia.(32 mm thick insulation) |
| 755 | 250 mm dia.(32 mm thick insulation) |
| 756 | 200 mm dia.(32 mm thick insulation) |
| 757 | 150 mm dia.(32 mm thick insulation) |
| 758 | 125 mm dia.(32 mm thick insulation) |
| 759 | 100 mm dia.(32 mm thick insulation) |
| 760 | 80 mm dia.(32 mm thick insulation) |
| 761 | 65 mm dia.(32 mm thick insulation) |
| 762 | 50 mm dia.(32 mm thick insulation) |
| 763 | 40 mm dia.(32 mm thick insulation) |
| 764 | 32 mm dia.(19 mm thick insulation) |
| 765 | 25 mm dia.(19 mm thick insulation) |
| 766 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified |
| 767 | 200 mm dia. |
| 768 | 150 mm dia. |
| 769 | 100 mm dia. |
| 770 | 80 mm dia. |
| 771 | 65 mm dia. |
| 772 | 50 mm dia. |
| 773 | 40 mm dia. |
| 774 | BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 775 | 200 mm dia. |
| 776 | 150 mm dia. |
| 777 | 100 mm dia. |
| 778 | Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. |
| 779 | 200 mm dia. |
| 780 | 100 mm dia. |
| 781 | 80 mm dia. |
| 782 | 65 mm dia. |
| 783 | 50 mm dia. |
| 784 | 40 mm dia. |
| 785 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. |
| 786 | Providing & fixing in position the mercury in glass industrial type thermometers. |
| 787 | Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 788 | 300 mm dia. |
| 789 | 250 mm dia. |
| 790 | 200 mm dia. |
| 791 | 150 mm dia. |
| 792 | 125 mm dia. |
| 793 | 100 mm dia. |
| 794 | Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Supplying, fixing, testing and commissioning of following sizes Motorized Butter fly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric signal and providing similar transduced feedback output to control system as required.-250 mm dia |
| 795 | BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. |
| 796 | 200 mm dia. |
| 797 | 125 mm dia. |
| 798 | 100 mm dia. |
| 799 | 50 mm dia. |
| 800 | Supplying, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation to IS : 655 and approved drawings and specifications of following sheet thickness complete as required. |
| 801 | Thickness 0.63 mm sheet |
| 802 | Thickness 0.80 mm sheet |
| 803 | Thickness 1.00 mm sheet |
| 804 | Thickness 1.25 mm sheet |
| 805 | Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required. |
| 806 | Thickness 0.63 mm sheet |
| 807 | Thickness 0.80 mm sheet |
| 808 | Thickness 1.00 mm sheet |
| 809 | Thickness 1.25 mm sheet |
| 810 | Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required-19mm |
| 811 | Supplying and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of ducts with cadmium plated nuts,bolts, stick pins, CPRX compound in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 812 | Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications. |
| 813 | Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 814 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required |
| 815 | Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required. |
| 816 | a) Fire damper |
| 817 | b) Actuator |
| 818 | Supplying, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in confirmation to SMACNA/IS and as per specifications complete etc. as required |
| 819 | Supplying, Fixing, installation, testing and commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 820 | Supplying, Fixing, installation, testing and commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required |
| 821 | Part - II Market Rate Items |
| 822 | Supply, installation, testing and commissioning of INTELLIGENT ANTI FOULING CONDENSER SYSTEM/AUTOMATIC TUBE CLEANING SYSTEM with Anti Fouling arrangement on chiller by automatic condenser cleaning for 3 numbers of Chillers, with a Common Skid for the required number of chillers in the plantroom. The system shall include IOT Ready, Industry 4.0 complaint device. The Panel should have minimum 7\\" Touch Screen Graphical HMI which will log the real time data related to chiller energy (KWH), Capacity (TR-480), Chiller Water Flow monitoring, Water Temperature profile on evaporator and condenser both and graphical representation of historic summary which shall be displayed on the Mobile App with unlimited user access on cloud based system. The data should also be retrieved in XL or PDF Format. The skid shall have IOT Panel, Injection/Collection pump, Motorized Valves & Fittings. Field Devices like Energy Mater, Flow Meter, Temp. Sensors shall be picked up from BMS/CPO Scope of Supply & Data shall be replicated from skid via Modbus protocol. The Common Skid piping, Ball Trap Size to suit chiller capacity requirement for the project. |
| 823 | Supply, Installation, testing and commissioning of End Suction back pullout Condenser water pump set capable of delivering 1425 USGPM of water against 24 Meter head each comprising of the following and complete as per specifications and as required.1 No.- end suction back pullout pump with minimum 75% efficiency.1 No. 30 KW TEFC squirrel cage induction motor with class 'F' insulation, 1500 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply. Motor efficiency shall be IE3.Lot- Mounting frame with Antivibration pads. 2w+1s |
| 824 | Supply, Installation, testing and commissioning of End Suction back pullout Primary chilled water pump set capable of delivering 960 USGPM of water against 15 Meter head each comprising of the following and complete as per specifications and as required.1 No.- end suction back pullout pump with minimum 75% efficiency.1 No. 15 KW TEFC squirrel cage induction motor with class 'F' insulation, 1500 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply. Motor efficiency shall be IE3.Lot- closed cell cross linked ployethylene insulation of 32 mm thick on pump assembly, all joints shall be sealed. Insulation shall be done according to chilled water piping insulation.Lot- Mounting frame with Anti-vibration pads.- 2w+1s |
| 825 | Supply, Installing, testing and commissioning of variable speed pumping system consisting of Adjustable Frequency Drive (AFD) for each pump, one dedicated microprocessor based Stand Alone Pump Controller housed inside a control cabinet or independently with parallel pumping software duly downloaded and single/ multiple differential pressure sensor/ transmitters as per the site requirement. The entire system alongwith secondary pumps of end suction back pullout Secondary Chilled Water pump set capable of following parameter and complete as per specification and requirement of pump and VFD (it must be sourced from single manufacturer only) to ensure unit responsibility. Necessary factory test certificate for entire system shall be submitted alongwith the equipment. The stand alone pump controller shall be suitable for taking analog inputs from 05 Nos. Sensor/ transmitter. The system shall comprise of the following:1 No.-End Suction back pullout Secondary chilled water pump set capable of delivering 960 USGPM of water against 40 Meter head each comprising of the following and complete as per specifications and as required.1 No.- end suction back pullout pump with minimum 75% efficiency.1 No. 37 KW TEFC squirrel cage induction motor with class 'F' insulation 1500 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply. Motor efficiency shall be IE3.Lot- closed cell cross linked ployethylene insulation of 32 mm thick on pump assembly, all joints shall be sealed. Insulation shall be done according to chilled water piping insulation. 2w+1s |
| 826 | Supply, installation, testing and commissioning of Expansion tank for total volume of water in chilled water circuits along with make up water pump set (skid mounted with suction and discharge header, pressure gauge, NRV, Pressure switch and isolation valve), air vent and Pressure reducing valve in order to keep chilled water system under (+) pressure with 2 nos pump(1w+1s) and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be with replaceable heavy duty butyl rubber bladder. The tank shall suitable size system, drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. It should be provided with sight glass. Body should be of carbon steel.The expansion tank shall be designed, constructed, and stamped in accordance with Section VIII, Division I of the ASME Boiler and Pressure Vessel Code, and registered with the National Board of Boiler and Pressure Vessel Inspectors. It should be with minimum 125 PSI working pressure or suitable working pressure as per the site requirement. Maximum operating temperature should be 240-degree Fahrenheit. U1 certificate should be provided for tanks. The complete system shall be sourced from single manufacturer. Expansion tank with external thermal insulation on tank with Duly laminated aluminum foil of mat finish closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.. The insulation material shall be fire rated for Class 1 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 0 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be not less than 0.024 per inch (2.48 x 10-14 Kg/m.s.Pa i.e. µ>7000: Water vapour diffusion resistance).The Material shall have Fire Approval from CBRI - Roorkee-1000Ltr |
| 827 | The Air and Sediment Separator shall be designed, constructed, inspected, and stamped per Section VIII, Division 1 of the ASME code. U1 certificate should be provided. Body shall be of Carbon Steel.The Air and Sediment Separator shall be rated for minimum 125 psi working pressure. The Air and Sediment Separator shall have a maximum temperature rating of 450°F (232°C).The Air and Sediment Separator body shall be made of carbon steel.The Air & Sediment Separator shall have an internal coalescing medium consisting of corrugated stainless steel sheets with 3/16\\" perforations and 58% open area. The coalescing medium shall be made of 304 stainless steel. The Air & Sediment Separator shall include a threaded skim valve connection on the side of the unit to allow floating sediment to be removed. The Air & Sediment Separator body shall be at least two times the nominal inlet/outlet pipe diameter and should include two equal chambers above and below the inlet/outlet nozzles.The Air & Sediment Separator shall include a magnetic insert for removal of iron oxide and other magnetic sediment. The magnetic insert shall be made of Neodymium 45H and should have a gauss strength of at least 13,550-300NB |
| 828 | Supplying, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (Total static pressure considered is max. 50 mm wg).40500 CFM, SP-60MMWC, TR-80, Motor-18.5 KW (BUILDING-1-GF) |
| 829 | Supplying, installation ,testing and commissioning of Ceiling Concealed Fan Coil Unit comprising of 3 rows deep chilled water cooling coil, centrifugal blowers, fractional horse power (FHP) motor, synthetic fibre filters, insulated & extended condensate drain pan along with L-type auxillary tray, casing, coil piping connections, condensate drain piping connections & wiring. Fan coil units shall be suitable for operation on 220 + 10% Volts, 50Hz, single phase power supply of following sizes & capacities. Complete as per CPWD specification and as directed by Engineer-in-charge.4.0 TR, 1600 CFM with 3 Row Cooling Coils (Building-1) |
| 830 | Supply, installation, testing and commissioning of Tube axial flow fans complete with TEFC motor, H-Class insulation, mounting arrangement, G.I. Welded wiremesh inlet guard, back draft gravity dampers, vibration isolator etc. complete in all respect as per specifications and drawings. The fans should be AMCA certified for air performance & sound ratings and the fan should be selected for maximum efficiency. Note:a) All motor shall be IE-3 and H-Class insulationb) Fan motor speed shall not exceed 1450 RPM c) Fan outlet Velocity shall not exceed 10.2 m/s (Norma mode fans) and 12.7 m/s (Smoke exhaust & pressurization fans )d) all accessories shall be part of the Tube Axial Fane) All Exaust Fans shall be fire rated for 250 deg C for two hours in accordance to BSEN12101-3:2015 standard. |
| 831 | Building-01-22500 CFM @ 25 MMWG SP, Motor 11 KW Emergency Exhaust |
| 832 | Building-02-22000 CFM @ 30 MMWG SP, Motor 7.5 KW Emergency Exhaust |
| 833 | Building-03-20500 CFM @ 30 MMWG SP, Motor 7.5 KW Emergency Exhaust |
| 834 | Building-04-20500 CFM @ 30 MMWG SP, Motor 7.5 KW Emergency Exhaust |
| 835 | Supply, installation, testing and commissioning of tube axial flow fans complete with TEFC motor, F-Class insulation, mounting arrangement, G.I. Welded wiremesh inlet guard, back draft gravity dampers, vibration isolator etc. complete in all respect as per specifications and drawings. The fans should be AMCA certified for air performance & sound ratings and the fan should be selected for maximum efficiency. a) All motor shall be IE-3 and F-Class insulationb) Fan motor speed shall not exceed 1450 RPM c) Fan outlet Velocity shall not exceed 10.2 m/s (Norma mode fans) and 12.7 m/s (Smoke exhaust & pressurization fans )d) all accessories shall be part of the Tube Axial Fan |
| 836 | Building-01 |
| 837 | 14500 CFM @ 25 MMWG SP, Motor 4.0 KW WareHouse Fresh Air |
| 838 | 11500 CFM @ 40 MMWG SP, Motor 5.5 KW Exhaust Air |
| 839 | Building-02 |
| 840 | 14500 CFM @ 25 MMWG SP, Motor 4.0 KW WareHouse Fresh Air |
| 841 | 6500 CFM @ 25 MMWG SP, Motor 2.2 KW Wip store fresh 7 Exhaust Air |
| 842 | UGT Room |
| 843 | 23000 CFM @ 30 MMWG SP, Motor 7.5 KW |
| 844 | 8500 CFM @ 25 MMWG SP, Motor 2.2 KW |
| 845 | 12000 CFM @ 25 MMWG SP, Motor 4.0 KW |
| 846 | 19500 CFM @ 30 MMWG SP, Motor 7.5 KW |
| 847 | SITC OF Direct driven fan. Cylindrical casing should be manufactured in mild steel or galvanised sheet steel mount on a horizontal square base. The rainhood are made of MS as protection against adverse weather conditions and impeller should have manual adjustable pitch blades. & blades made up of of PPG, PAG or pressure-casted Aluminium.Totally enclosed Class H motor, to a min. IP55 protection should be fitted as standard. |
| 848 | 11650 CFM Fro WareHouse Emergency exhaust Air Building-01 |
| 849 | 11650 CFM Fro WareHouse Emergency exhaust Air Building-02 |
| 850 | Supply, installation, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply. Quoted price shall be inclusive of electronic speed regulator and wiring between fan & speed regulator for single phase fans. Incase of 3 phase fans quated price shall be inclusive of DOL starter panel with cabling between starter panel and fan. The incoming power supply to speed regulator / starter panel shall be provided by electrical contractor. The fan shall have low sound level exceeding not more than 40 DBA at three metre distance. |
| 851 | Building-01 |
| 852 | 600 CFM @ 15 MMWG Static Pressure |
| 853 | 725 CFM @ 15 MMWG Static Pressure |
| 854 | 800 CFM @ 15 MMWG Static Pressure |
| 855 | 900 CFM @ 15 MMWG Static Pressure |
| 856 | 1200 CFM @ 15 MMWG Static Pressure |
| 857 | 1300 CFM @ 20 MMWG Static Pressure |
| 858 | 1600 CFM @ 20 MMWG Static Pressure |
| 859 | 1650 CFM @ 20 MMWG Static Pressure |
| 860 | 900 CFM @ 20 MMWG Static Pressure |
| 861 | 2400 CFM @ 20 MMWG Static Pressure |
| 862 | Building-02 |
| 863 | 300 CFM @ 10 MMWG Static Pressure |
| 864 | 400 CFM @ 15 MMWG Static Pressure |
| 865 | 500 CFM @ 15 MMWG Static Pressure |
| 866 | 700 CFM @ 15 MMWG Static Pressure |
| 867 | 1500 CFM @ 20 MMWG Static Pressure |
| 868 | 1600 CFM @ 20 MMWG Static Pressure |
| 869 | 1750 CFM @ 20 MMWG Static Pressure |
| 870 | 1900 CFM @ 20 MMWG Static Pressure |
| 871 | Supply, installation, testing and commissioning of direct driven PROPELLER FANS for exhaust / supply air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows :200 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply. |
| 872 | PLUMBING |
| 873 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.Supplying,Installation, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc,O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric signal and providing similar transduced feedback output to control system as required. (motorized butter Fly valve to be used up to 32 mmdia. and motoririzedball valve to used for 25 mm dia.) |
| 874 | 200 mm dia. |
| 875 | 100 mm dia. |
| 876 | 80 mm dia. |
| 877 | 65 mm dia. |
| 878 | 50 mm dia. |
| 879 | 40 mm dia. |
| 880 | 32 mm dia. |
| 881 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified-32mm dia |
| 882 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.-200mm dia |
| 883 | Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.-32mm dia |
| 884 | Supply,installation,testing and commissioning of Autometic Air Vents . |
| 885 | 15 mm |
| 886 | 20 mm |
| 887 | Supplying Installation, testing and commissioning of Pressure Independent Control Valve (PICV) complete with quick-fit pressure/temperature ports. Size DN 15 (from DN 15 to DN 25).Main connections 1/2” M (from 1/2” to 1 1/4”) (ISO 228-1). Dezincification resistant alloy body and headwork. Control stem, piston and springs in stainless steel. Pressure regulator diaphragm,obturator and seals in EPDM. Asbestos-free fibre seals. Pre-adjustment indicator in PA6G30. Knob in PA6. Maximum working pressure 25 bar. Maximum differential pressure with actuator code145013 (and 6565 series) installed 5 bar. Working temperature range -20–120°C. Nominal Dp control range 25–400 kPa. Accuracy± 5 % of the setpoint. Flow rate regulation range 0,02–0,2 m3/h (0,02–0,2 m3/h, 0,08–0,4 m3/h, 0,08–0,8 m3/h, 0,12–1,2 m3/h,0,18–1,8 m3/h, 0,3–3 m3/h and 0,37–3,7 m3/h). The adjustment position does not affect the obturator stroke. Full stroke modulation.Flow rate pre-adjustment device with at least 10 reference positions and continuous adjustment. Leakage class V according toEN60534-4. Diaphragm pressure regulator. Complete with On - Off OR Modulating actuator |
| 888 | 100 mm dia pipe for AHUs |
| 889 | 80 mm dia pipe for AHUs |
| 890 | 65 mm dia pipe for AHUs |
| 891 | 50 mm dia pipe for AHUs |
| 892 | 40 mm dia pipe for AHUs |
| 893 | 32 mm dia pipe for AHUs |
| 894 | Supply,installation, testing & Commisioning of Connection and regulation kit for HVAC fan coil units / hydronic cassette unit in heating/ cooling systems. Complete with: pressure independent control valve with proportional linear actuator (Modulating type ), three-way shut-off valves, integrated by-pass, Venturi device with pressure test ports, shut off valve with strainer and shell insulation made of PPE. NOTE : all given parts should be of one single manufacturer,no different manufacturer assembelled unit is acceptable. Linear or equipotential flow rate adjustment characteristic, which can be set up by actuator depending on the characteristics of the terminal unit. Maximum working pressure 25 bar. Maximum differential pressure with actuator installed: 5 bar. Nominal operation Δp range 25–400 kPa. Working temperature range -10−120°C. Ambient temperature range 0−50°C. Strainer mesh size 800 µm. Dezincification resistant alloy body and adjustment headwork; stainless steel strainer mesh; EPDM diaphragm, obturator and seals. One pair of flexible connection with threaded nut / clamp to be provided between the unit and kit of suitable length. |
| 895 | 25 mm dia for HCU/FCU |
| 896 | 32 mm dia for HCU/FCU |
| 897 | Supply,installation,testing and commissioning of PVC 6 Kg/Sqcm (Class-3) water piping duly insulated with 6 mm thick nitrile rubber on floor / ceiling /concealed in part of following size along with necessary clamps, fittings such as bends tees etc. specifications and as required. |
| 898 | 65 mm dia. |
| 899 | 50 mm dia. |
| 900 | 40 mm dia. |
| 901 | 32 mm dia. |
| 902 | 25 mm dia. |
| 903 | 20 mm dia. |
| 904 | Supply,installation,testing and commissioning of 25 mm dia Ball valves for header and equipment drain with fittings etc. |
| 905 | Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 906 | 80 mm dia. |
| 907 | 50 mm dia. |
| 908 | Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. |
| 909 | BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. |
| 910 | 300 mm dia. |
| 911 | 250 mm dia. |
| 912 | Supply, installation, testing and commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified-250mm dia |
| 913 | NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified.-250mm |
| 914 | Supply, installation, testing and commissioning of M.S Y-Strainer Complete with Stainless Steel Bucket having 03 mm Perforation, flanged ends. Filteration area 1:4-250mm dia |
| 915 | Supply, installation, testing and commissioning of M.S POT-Strainer Complete with Stainless Steel Bucket having 03 mm Perforation, flanged ends. Filteration area 1:4.-300mm dia |
| 916 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 917 | Providing & fixing in position the mercury in glass industrial type thermometers. |
| 918 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for Hvac system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 919 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13 mmthick insulation |
| 920 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13 mmthick insulation |
| 921 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13mm thick insulation |
| 922 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 13mm thick insulation |
| 923 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 13 mmthick insulation |
| 924 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 925 | Supply, Installation, testing and commissioning of BTU Meter of following sizes. Accuracy : 10\\" to 36\\" (1% Full Scale), process connection : Male NPT, Housing electrical connection - 1/2\\" female NPT conduit connection without cable, temperature sensor - Hot tap Thermowell Temperature Sensor Assembly with 10 Foot, BACnet / Modbus communication with LCD display, temperature limits; Ambient: -20° to 160°F (-29° to 71°C); LCD -4° to 158°F (-20° to 70°C); Process: 15° to 250°F (-9° to 121°C); Storage: -40° to 185°F (-40° to 85°F) including required accessories complete in all respect as required. |
| 926 | BTU Meter 300 mm |
| 927 | BTU Meter 200 mm |
| 928 | Supply, installation, testing and commissioning of Air Curtain suitable for generating a laminar stream of air with uniform pressure throughout the door and with sufficient air quantity & speed to offer the desired environment protection through door opening of below mentioned sizes. The Air Curtain shall have side mounted continuous duty direct driven energy efficient motor with 'F' class insulation and suitable for 220 + 10% Volts, 50 + 3% Hz AC supply (installed at the top of opening), aerodynamically designed radial flow fans for minimum noise levels with lifetime lubricated sealed ball bearings. The impeller blades shall be of plastic. The unit shall be compact in design and the body of unit shall be made of SS-304. The unit shall be provided with pre filters for dust and fluff filtration. The unit shall also be provided with auto actuation device to synchronize the functioning of air curtain with the opening or closing of the doors (sensors) and shall have automatic internal thermal overload switch protection. The operation of the air curtain shall be synchronized with the existing sliding door system. The unit shall include adjustable parameters for opening and closing speed, hold-open time, opening and closing force, night lock, and multi-sensor detectors. The permissible noise level of the unit shall be maximum 50–70 dB. The unit shall be complete with suitable remote control panel. Nozzle velocity in the range 21-25 m/s and at 7 feet 3.5 m/sec. Sound level in the range 65 dB at 5 feet distance from the unit, complete as per requirement and specifications. Size of the curtain as shown follows:Curtain Size 1200X230X212 |
| 929 | Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction fresh/exhaust air louvers with bird screen and without volume damper for exhaust air as per specifications and approved shop drawings. |
| 930 | Supplying & fixing of powder coated extruded aluminium continuous Griles with louvers but without volume control dampers complete as required.-150mm height |
| 931 | Supplying, fixing, testing and commissioning of aluminium volume control dampers as per specifications. |
| 932 | Supplying & fixing of powder coated extruded aluminium Supply Air Round diffuser with louvers but with volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required.-400mm dia |
| 933 | Supplying & fixing of powder coated extruded aluminium return Air Round diffuser with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required.-400 dia |
| 934 | FIRE FIGHTING WORKS |
| 935 | (Part - I) ITEMS BASED ON DSR - 2025 (Part A ) Piping and Valves |
| 936 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 937 | 25 mm dia |
| 938 | 50 mm dia |
| 939 | 80 mm dia |
| 940 | 100 mm dia |
| 941 | 150 mm dia |
| 942 | 200 mm dia (wall thickness 6.3 mm) |
| 943 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.-150mm dia |
| 944 | Providing, laying, testing & commissioning of 'B' class medium duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80mm |
| 945 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 946 | 80mm dia |
| 947 | 150mm dia |
| 948 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 949 | 80 mm dia |
| 950 | 100 mm dia |
| 951 | 150 mm dia |
| 952 | 200 mm dia |
| 953 | (Part - B) FIRE HYDRANT ACCESSORIES |
| 954 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required:Single headed Stainless steel |
| 955 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed Stainless steel |
| 956 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 957 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304) |
| 958 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required:Stainless Steel (Grade 304) |
| 959 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required: |
| 960 | 2 way-100 mm dia M.S. Pipe |
| 961 | 4 way - 150 mm dia M.S. Pipe |
| 962 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange..200mm dia |
| 963 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 964 | (Part - C) FIRE PUMPS & ACCESSORIES |
| 965 | (a) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required :(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e)Suitable cement concrete foundation duly plastered with anti vibration pads. |
| 966 | 1620 lpm at 88 m Head |
| 967 | (a) Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.(d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.-1620lpm at 8m head |
| 968 | (a) Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 969 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 970 | Fabrication, supplying, Installation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :Incomings : 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating, Digital Voltmeter 0-500V with selector switch, Ammeter (0-400 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps, Set of Copper Bus Bar 500AOutgoings : (Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump, 200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.Jockey Pump : 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.Diesel Engine ControlControl for diesel engine comprising - Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC AmmeterAll standard relays and accessories for automatic operation of diesel engineSystem Controller, Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. |
| 971 | (Part - II) ITEMS BASED ON MARKET RATE |
| 972 | Part - A (Piping & Valves) |
| 973 | Providing and fixing C.I. foot valves including nuts, bolts,1.5mm thick compressed asbestos gasket complete and companion flange as per table \\" E \\"in all respects-150mm dia |
| 974 | Providing and fixing brass ball valve (full bore type) with plastic coated lever and screwed female ends tested to 20 Kg/ cm2 of approved quality as specified. |
| 975 | 25 mm dia. |
| 976 | 50 mm dia. |
| 977 | Providing and fixing dial type pressure gauge with isolation cock and copper pipe at hydrant station.Dial diameter 100 mm calibration 0-15 kg/ sq.cm. |
| 978 | Providing and fixing blank flanges as per table 'E' with asbestos gasket, nut, bolts, washers complete-150 mm dia. |
| 979 | Providing and fixing one coat of 4 mm thick PYPKOTE/ COATAK anti-rust pipe protection including primer and lap of 25mm on external buried pipe including surface preparation, complete in all respects.80mm dia |
| 980 | Part - B (Fire Hydrant and Accessories) |
| 981 | Providing and fixing door with frame for all internal fire hydrants fabricated from 20x20x3 mm and 40x20x3 mm aluminium hollow box sections mounted with 3 no. of 100 mm Aluminium butt hinge on Aluminium angle frame of 45x45x5 mm size with hold fasts fixed to wall with P.C.C. (1:2:4) blocks 100x100x100 mm including 2 nos allen key lock for locking along with padlock arrangement & fully glazed with 4 mm thick float glass approved by local Fire Authority, powder coated fire red finish with \\" fire hose' written on front suitable to house 15 mm long two length of canvas hose with couplings, one no of branch pipe, one fire mans axe and two numbers of portable extinguishers, first aid fire hose and supports for hoses, branch pipes, Axe and hose reel. Size 2100x 900 mm complete as per approved design including necessary fixing arrangement for hoses & axe and branch pipe.) |
| 982 | Providing and fixing fire hose cabinet fabricated from 16 gauge M.S. Sheet with single or double glazed front door and locking arrangement, painted \\"Fire Red\\" with powder coated paint \\"Fire Hose\\" written on front including suitable supports to place 900 mm above ground level, approximately size 750x600x250 mm deep (to house two lengths of canvas hose with couplings, branch pipe and nozzle for external hydrants) |
| 983 | Supplying and fixing of Fire Man's Axe with heavy insulated rubber tested upto 20 KV and confirming to IS :926. |
| 984 | Constructing Solid blocks masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with FRP cover with frame 600x600mm internal dimensions (20 ton load bearing) i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design :Solid blocks of approved quality and class designation 5 having compressive strength of 4-6 N/sq.mm. |
| 985 | Part - C ( Fire Pumps and Accessories) |
| 986 | Providing and fixing of air vessel including spring loaded relief valve on top suitable for working pressure of 25 Kg / sqmcm and set pressure is above 10% of working pressure of the following specifications fabricated with MS sheets.a. Diameter : 450 mmb. Minimum Shell Thickness: 10 mm c. Minimum Dish Ends : 15 mmd. Height : 1500 mme. Finishing: Two coats of red enamal paint over primer out side and two coats of epoxy coating inside.f. Material of construction: M.Sg. Test Pressure: 40 Kg/Sq.Cm.h. Height of supporting legs: 400 mmi. QuantityNote: Contractor should submit general arrangement drawings before fabrication of vessel and ultrosonic test report to be submitted on supply of vessel and test to be conducted at the presence of Plumbing-In-Charge. |
| 987 | Providing and fixing liquid level controller for fire pump to stop fire pump in case of low level of water in tank , cost of conduit, cable and panel including making connection to pump panel and commissioning complete. |
| 988 | Float type Sensor with panel |
| 989 | Installation |
| 990 | Providing and fixing liquid level controller for tubewell pump to start both the tubewell pumps in case of low level of fire water in tank, stop manually (when fire extinguished) also provision of over riding domestic water pumps inter-locking in case of fire, cost of conduit, probes or float switches cable and panel including making connection to pump panel and commissioning complete. |
| 991 | Float type Sensor with panel |
| 992 | Installation |
| 993 | Providing and fixing resilient rubber neoprene lined arch vibration eliminators with unit control nuts, bolts, washers, companion flange as per table \\"E\\" complete suitable for working pressure of 16 Kg/sqcm. And temperature of 50°c. |
| 994 | 100 mm dia. |
| 995 | 150 mm dia. |
| 996 | Supplying & laying of following 1100 volt grade PVC insulated sheathed XLPE aluminium conductor armoured cables as per specification in cable trays, ducts, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.(For Main Pump)3 core 95 sqmm |
| 997 | Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc. complete as required3 core 95 sqmm Alumnium conductor cable |
| 998 | Supply and fixing of perforated type GI cable trays of the following sizes as per specifications |
| 999 | 150 mm x 40 x 40 x 2 mm thick |
| 1000 | 300 mm x 40 x 40 x 2 mm thick |
| 1001 | Supply, Testing & Commissioning, fixing of following bare GI/Copper tapes / wires including all necessary fixing accessories and effecting connections as per specifications. |
| 1002 | 6mm dia Copper wire |
| 1003 | 25 x 3 mm thick Copper tape |
| 1004 | Providing and fixing M.S. structural work fabricated from standard sections, (MS rounds, angles, channels ,slotted angle, etc.) including cutting to size, drilling ,welding or insert plates including cost of (Hilti) fasteners, clamp in RCC structural members as directed, including two or more coats of synthetic enamel paint over one coat of primer after surface preparation including cutting and making good walls. |
| 1005 | Part - D (Fire Extinguishers and Misc. Items) |
| 1006 | Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded M.S cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS : 15683 finished externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners complete with internal charge. Capacity 4.5 kg. ISI Marked.( Contractor should submit test certificate form manufacturer along with serial number of every extinguishers supplied.) |
| 1007 | Providing and fixing mechanical foam type (ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle suspension bracket ISI marked finished externally with red enamel paint and fixed to wall with brackets complete with internal charger.9 liters capacity. (IS. 15683) |
| 1008 | Providing and fixing water Co2 (ISI marked) extinguishers including all accessories as per IS specification, finished externally with red enamel paint and fixed to wall with brackets complete with internal charger.Capacity 9 liters.(IS:15683) |
| 1009 | Providing and fixing ABC powder type fire extinguishers consisting of welded M.S. cylindrical body automatic modular ABC powder type extinguisher actuated through a sprinkler head mounted on The extinguisher body finished externally with red enamel paint and fixed to ceiling with brackets complete with internal charge.Capacity 10 Kg.(IS:15683) |
| 1010 | Providing and fixing ABC powder type (ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle suspension bracket ISI marked finished externally with red enamel paint and fixed to wall with brackets complete with internal charger.Capacity 6 Kg (IS. 15683) |
| 1011 | roviding and fixing wet chemical type (ISI marked) fire extinguishers consisting of welded Stainless steel body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle suspension bracket ISI marked and fixed to wall with brackets complete with internal charger. (For Kitchen Area)Capacity 4 Kg. (IS:15683) |
| 1012 | Providing and fixing of self illuminated / auto glow \\"EXIT\\" signs printed on photoluminescent sheet containing self illuminated base chemical, of appropriate size not less than 400 x 150 mm, suspended from ceiling or fixed to the walls with accessories as required and as directed at site. |
| 1013 | Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded M.S cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, trolly mounted, confirming to IS : 15683 finished externally with red enamel paint complete with internal charge. Capacity 22.5 kg. ISI Marked.( Contractor should submit test certificate form manufacturer along with serial number of every extinguishers supplied.) |
| 1014 | Providing and fixing mechanical foam type (ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle, trolly mounted ISI marked finished externally with red enamel paint complete with internal charger.50 liters capacity. (IS. 15683) |
| 1015 | Providing & fixing of 4 nos. G.I. round bottom fire buckets of 9 liters capacity including proper supporting / mounting arrangements in MS angle iron frame, painted by fire red colour over two coats of red oxide paint and written with white paint \\"FIRE\\" complete in all respects as per the directions of Engineer-incharge. |
| 1016 | Supply and laying of 1800 mm x 900 mm x 20 mm thick chequered rubber matting of tested quality. |
| 1017 | Providing and fixing danger notice plate of 200 mm X 150 mm made of mild steel at least 2 mm thick vitreous enamelled, white on both sides and with inscription in signal red colour on front side as required. |
| 1018 | providing and fixing of shock treatment chart written in English and Hindi both properly framed and glass covered as required. |
| 1019 | Lifts |
| 1020 | (Part - I) ITEMS BASED ON DSR - 2025 |
| 1021 | Passenger Lifts |
| 1022 | Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required:-\\"(i) Speed-1 MPS(ii) Floors-5 (G+4)(iii) Travel -17 Meters (approx.)(iv) Stops & opening- 5 stops and 5 openings(v) Controller: A.C. variable voltage & variable frequency(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system(ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge.\\" |
| 1023 | (xi) Type of doors(a) Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish).(b) Landing doors: stainless steel scratch proof .(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii)Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.(xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection andprotection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder\\"\\"(xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency.(xvi) An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness.(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided\\"16 passenger (1088kg) |
| 1024 | Goods Lifts |
| 1025 | Supplying, Installation, Testing & Commissioning of 2000kg Machine room less (MRL) goods lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required :-\\"(i) Speed - 0.5 MPS(ii) Floors - 5(G+4)(iii) Travel - 17 metres(approx)(iv) Stops & opening : 5 stops and 5 openings(v) Controller: A.C. variable voltage & variable frequency(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.(vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system |
| 1026 | (ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be strong to take the rated load without any deformation or damage and antiskid as approved by engineer-in-charge.(xi) Type of doors:-(a) Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish).(b) Landing doors: stainless steel scratch proof .(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii) Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.\\"\\"(xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder.(xv) In case of failure of ARD or other electronic\\"2000 kg |
| 1027 | (Part - II) ITEMS BASED ON AP SR - 2025-26 |
| 1028 | Passenger Lifts |
| 1029 | Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required:-\\"(i) Speed-1 MPS(ii) Floors-2 (G+1)(iii) Travel -10 Meters (approx.)(iv) Stops & opening- 2 stops and 2 openings(v) Controller: A.C. variable voltage & variable frequency(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system(ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge. |
| 1030 | (xi) Type of doors(a) Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish).(b) Landing doors: stainless steel scratch proof .(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii)Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.(xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection andprotection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder\\"\\"(xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency.(xvi) An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness.(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided\\"8 passenger (544 kg) |
| 1031 | Electrical Internal |
| 1032 | ( Part - I )Delhi Schedule Rate - 2025 |
| 1033 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.-Group C |
| 1034 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc .as required. |
| 1035 | Wiring for light/ power plug with 2X4 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing asrequired. |
| 1036 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 1037 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 1038 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 1039 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 1040 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 1041 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 1042 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 1043 | 20 mm |
| 1044 | 25 mm |
| 1045 | 32 mm |
| 1046 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 1047 | 20 mm |
| 1048 | 25 mm |
| 1049 | 32 mm |
| 1050 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A Modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 1051 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 1052 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 1053 | Group C |
| 1054 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 1055 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required |
| 1056 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 1057 | 100 A, 16 KA,TPMCCB |
| 1058 | 125 A, 16 KA,TPMCCB |
| 1059 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) |
| 1060 | 8 Way Double Door |
| 1061 | 12 Way Double Door |
| 1062 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) |
| 1063 | 8 Way ( 4+24 ) Double Door |
| 1064 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 1065 | 4 way (4 + 12), Double door |
| 1066 | 8 way (4 + 24), Double door |
| 1067 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1068 | Single pole |
| 1069 | Double Pole |
| 1070 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1071 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1072 | Supplying and fixing following rating, double pole, (single phase and neutral), 240V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1073 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1074 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 1075 | Hot Dipped Galvanized Iron Cable Tray |
| 1076 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required |
| 1077 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 1078 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 1079 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 1080 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 1081 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1082 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1083 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 1084 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required |
| 1085 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 1086 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 1087 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 1088 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 1089 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1090 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1091 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 1092 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 1093 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 1094 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 1095 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 1096 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 1097 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1098 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 1099 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 1100 | EARTHING |
| 1101 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 1102 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 1103 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 1104 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 1105 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 1106 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 1107 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 1108 | PProviding and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 1109 | LIGHTNING CONDUCTOR |
| 1110 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 1111 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 1112 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 1113 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 1114 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required |
| 1115 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 1116 | Supplying, Installation, Testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor with day light dimming (lighting level shall be regulated as per availability of natural day light in an area along with occupancy detection.) having high performance, regulating programmable suitable for connected load upto 10Amp ,for mounting height up to 3 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. |
| 1117 | LED Down lighter (SMD Type) (System lumen efficacy >135lm/Watt)Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim |
| 1118 | 8 - 10 watt |
| 1119 | 12 -15 wat |
| 1120 | LED LIGHT |
| 1121 | LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS :10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19,Flicker free,(flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with ,70% of initial Lumen maintained till life ends ,CCT 3000°K /4000°K /5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness >1.20 mm)36 watt LED Panel Light 2x2 ft. |
| 1122 | LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS :10322 with driver (Replaceable) as per the requirement with Driver efficiency > 85% ,Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0 C to 40 0 C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥ 0.95, IP20, CRI > 80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 36 watt LED Batten Light |
| 1123 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 1124 | Supplying and fixing Suitable rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1125 | 40 A, 10 KA,TPN MCB |
| 1126 | 63 A, 10 KA,TPN MCB |
| 1127 | (Part - II ) AP PWD SR 2025-26 - Electrical |
| 1128 | SITC of 10 W WH LED Mirror Light as / Specification, Polycarbonate housing, system wattage -10 w,Lumen pack - 1000w with eficacy - 100lm/w,CRI-80. , IP -20 with IS 10322 (part 5/Sec.1)-2012. |
| 1129 | Supply and transportation of LED High Bay Luminaire with high power COB LED made of pressure diecast aluminum housing with powder coated, supply input voltage 120 - 270 V AC, P.F > 0.90, high power LEDs, having system efficacy >=120 lumens/watt and junction temperature < 70°C, with ingress protection IP66, IK05, Driver surge protection 4KV, in-house additional surge protection ≥ 5KV with wide/narrow beam optics,THD<10% at 110 Volts AC, driver efficiency >90%, , CCT: 3000K - 5700K, minimum CRI>70, etc., complete with earth connection and not less than two years warranty. Makes: As per list of recommended brands as category I-60watt |
| 1130 | Market Rate Items-Lighting Control System |
| 1131 | Supply of central processor assembled processor with two configurable links. Each processor link can be configured to be a dimmer link, shade link, or dimmer power panel link. Processor accpets 220-240V, 1 phase, 2 wire, 10A feed, (throiugh power supply) Similar to Lutron Qunatum/ Athena |
| 1132 | SITC of Eco system/DALI Dimming controller; Controls 2 independent DALI links with up to 64 DALI ballasts per link. 4 groups of sensors inputs: Occ sensor, daylight sensor and IR sensor. Requires mains/line voltage feed Similar to Lutron QSNE-2DALUNV-D |
| 1133 | SITC of Switching module with 4 channels, each channel with minium 5 amp rating with provisions of sensors inputs: Occ sensor, daylight sensor and IR sensor. Requires mains/line voltage feed Similar to Lutron QSNE-4S 5230D module |
| 1134 | Supply of Lighting control and monitor software, captures floor wise consumption, each event, Energy Reporting & monitoring per processor. |
| 1135 | Supply of Lighting control BACnet softwares for BMS integration |
| 1136 | Power Supply Unit for supply PDUs to Antenna devices Similar to Lutron QSPS-DH -1 -75 |
| 1137 | SITC of Wireless Occupancy/Vacancy Sensor for rooms with a frequency of 865 MHz, Ceiling mount, infrared, 37.2 sq m (400 sq ft), battery-powered, 102 mm (4.0 in) diameter |
| 1138 | Same occupancy sensor as abobve but with differenmt form factor for Corridors - wall mounted. |
| 1139 | SITC of Sensor Module, to connect 10 number of sensors either of the Occupancy / Daylight / Personal sensors/PIco. No wired connections, ceiling mount. |
| 1140 | SITC of Wireless personlised control Keypad with a WPC approved frequency of 865 Mhz, 3 Button with raise and lower for smaller rooms, with faceplate, mounts on glass surfaces also, with 10 year battery life along with necessary fixing arrangements and programming at site etc, complete as required. Similar to Lutron PN2 3bRL series with face plate |
| 1141 | SITC of Wireless personlised control Keypad with a WPC approved frequency of 865 Mhz, 6 Button with raise and lower for bigger rooms, with faceplate, mounts on glass surfaces also, with 10 year battery life along with necessary fixing arrangements and programming at site etc, complete as required. Similar to Lutron PN2 3bRL & PN2 3B series with dual gang face plate |
| 1142 | SITC of desktop server with Microsoft Windows 2010 Server Operating System Installed. The hardware Includes the computer with a high performance hard drive for maximum data integrity, a monitor, a keyboard and a mouse. |
| 1143 | Network Swithch - 6 port |
| 1144 | DB BOX for mounting dimming , swithcing module - 4 tier 56 module flexi db |
| 1145 | QS cable for power and data. Cable Common – 12 AWG (4.0 mm2); Power – 12 AWG (4.0 mm2); MUX Data – 22 AWG (0.25 mm2); Data – 22 AWG (0.25 mm2); Sense Line – 18 AWG (0.75 mm2); Drain Wire – 24 AWG (0.2 mm2) |
| 1146 | Supplying and fixing of Metal Socket set of 2pole and earth plugs and socket for incorporating SP and TP MCB (Without MCB). The entire plug and socket shall be mounted in a thermoplastic / powder coated metal box & wired Completely. TP&N 30A |
| 1147 | Supplying & Fixing Chemical earthling for grounding. Conduits, IC cut-outs & other equipments backfill compound which is non corrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm - Using 6 ft. Copper bonded rod with backfill compound |
| 1148 | Providing, supplying, installing, testing and commissioning G.I. floor raceway of the sizes mentioned below, with 1 or 3 compartments, including all necessary civil works such as cutting, chasing, making openings, grouting, finishing and making good the surface, complete with supports, covers, fasteners and all required accessories, complete as per specifications and directions of the Engineer-in-Charge. |
| 1149 | 300 x 38 x 2.0 mm |
| 1150 | 150 x 38 x 2.0 mm |
| 1151 | 100 x 38 x 2.0 mm |
| 1152 | Hybrid Power factor Correction (HPFC) System |
| 1153 | Supply, Installation, testing and commissioning of 800 KVAR HYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity,3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangment for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEE recommended limits.APFC should be designed as per IS 16636 Or IEC 61921. The active section and passive section shall work in sync to give optimized output. The degree of protection of passive section should be IP 42, and of active section should be minimum IP 21.The switching device for APFC passive section should be through capacitor duty contactor and for the active compensation system shall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensation system should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. The active compensation system should have feature to improve PF correction and harmonic filtration having response time < 100 Micro second. The hybrid panel shall be indoor type floor mounted free standing totally enclosed, extensible, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports,bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details. |
| 1154 | (A) INCOMMERSuitable capacity MCCB/ACB (Upto 300 KVAR, MCCB and above 300 KVAR, ACB ) Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set alongwith required Instruments and accessories with extended rotary handel and door interlocking arrangment. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating. |
| 1155 | (B) Instruments & Indications a)For Passive Section :i) 3-Phase current sensing APFC microprocessor relay/controller, advance 12/16 stages (12 stages for overall capacity of panel (active + passive) below 500 KVAR and 16 stages 500 KVAR & above) and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V, THD-I, harmonics up to 31 level. ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode. iii) Digital multi-function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V & I, Frequency. (iv) Suitable rating control transformer shall be provided for control and indication circuit. (v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB's. vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire. vii)Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. |
| 1156 | b)For active Section :Dedicated HMI (Human Machine Interface) (Minimum 7-inch display) for controlling and communication and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V, THD-I, harmonics up to 50th level. Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge.800KVAR |
| 1157 | UPS (3 phase input & 3 phase output) Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part |
| 1158 | 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS, Inverter, PFC. g) EventLogging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like:Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / InverterFail / Rectifier Fail / Bypass Fail, etc. h) StatisticalData: No. of power failures / Transfers to Bypass /Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging,overload, battery voltage and battery capacity. j)Audible Alarms : Mains Failure, Battery Low Alarm,UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over,Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc |
| 1159 | 20 KVA (Each Power module shall be < 10 KVA) . |
| 1160 | 30 KVA (Each Power module shall be < 10 KVA) |
| 1161 | 40 KVA (Each Power module shall be < 10 KVA) |
| 1162 | 80 KVA (Each Power module shall be < 25 KVA) |
| 1163 | Lighting Control for Feeder Pillar.Supplying, Installation, Testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 1164 | 3 output(1output per phase) and suitable for three phase supply |
| 1165 | HT CABLE LAYINGLaying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm |
| 1166 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm |
| 1167 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm |
| 1168 | HV CABLE JOINTING & END TERMINATIONSupplying and making straight through cable jointing with cast resin compound, including ferrule and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required300 sq. mm |
| 1169 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with allaccessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required300 sq. mm |
| 1170 | Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required300 sq. mm |
| 1171 | MV CABLE LAYINGLaying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 1172 | Upto 35 sq. mm |
| 1173 | Above 35 sq. mm and upto 95 sq. mm |
| 1174 | Above 95 sq. mm and upto 185 sq. mm |
| 1175 | Above 185 sq. mm and upto 400 sq. mm |
| 1176 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 1177 | Upto 35 sq. mm |
| 1178 | Above 35 sq. mm and upto 95 sq. mm |
| 1179 | Above 95 sq. mm and upto 185 sq. mm |
| 1180 | Above 185 sq. mm and upto 400 sq. mm |
| 1181 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required |
| 1182 | Upto 35 sq. mm |
| 1183 | Above 35 sq. mm and upto 95 sq. mm |
| 1184 | Above 95 sq. mm and upto 185 sq. mm |
| 1185 | Above 185 sq. mm and upto 400 sq. mm |
| 1186 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing masonry open duct as required. |
| 1187 | Upto 35 sq. mm |
| 1188 | Above 35 sq. mm and upto 95 sq. mm |
| 1189 | Above 95 sq. mm and upto 185 sq. mm |
| 1190 | Above 185 sq. mm and upto 400 sq. mm |
| 1191 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 1192 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 1193 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 1194 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 1195 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 1196 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required |
| 1197 | MV CABLE JOINTING & END TERMINATIONSupplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 1198 | 2 X 10 sq. mm (19mm) |
| 1199 | 3½ X 35 sq. mm (32mm) |
| 1200 | 3½ X 50 sq. mm (35mm) |
| 1201 | 3½ X 70 sq. mm (38mm) |
| 1202 | 3½ X 120 sq. mm (45mm) |
| 1203 | 3½ X 150 sq. mm (50mm) |
| 1204 | 3½ X 185 sq. mm (57mm) |
| 1205 | 3½ X 240 sq. mm (62mm) |
| 1206 | 3½ X 300 sq. mm (70mm) |
| 1207 | 4 X 10 sq. mm (25mm) |
| 1208 | 4 X 16 sq. mm (28mm) |
| 1209 | 4 X 25 sq. mm (28mm) |
| 1210 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required |
| 1211 | Above 4.5 Meter and upto 6.5 Meter |
| 1212 | Above 8.0 Meter and upto 10.0 Meter |
| 1213 | LED Smart Street light fixture, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) - 72 watt .Supplying, installation, Testing & Commissioning of Smart Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement ( < 700ma), Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK08, CRI >70, under voltage and over voltage protection, EMI- EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink |
| 1214 | 1.Control and monitor LED luminaries with bi directional control ( Status, Fault, Alarm, dimming level, wattage, energy) 2. to measure voltage, current, power, power factor, apparent energy, active energy, operating hours.3. Inbuilt ambient light sensor, motion sensor based on Passive Infra Red (PIR).4.Wi-Fi LoRA/Zigbee/Powerline with etherne network based IOT feature as per site requirement or engineer in charge. 5.should be controlled through auto/ manual 6.Programmable level of not less than 48 different light intensity settings, 7. inbuilt repeater & relay signals function to other controllers72 watt. |
| 1215 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt) Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 1216 | 150 watt |
| 1217 | 250 watt |
| 1218 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 1219 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 1220 | EARTHINGEarthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 1221 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 1222 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 1223 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 1224 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 1225 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 1226 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 1227 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 1228 | Bus Trunking (Sandwich type)Supplying, installation by suspension on ceiling, testing and commissioning of following capacitySandwich Type Bus-Trunking for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal cladenclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required4000 A, Isc= 50kA for 1 sec |
| 1229 | Part - II - AP SR 2025-26Control CablesSupply, laying & end termination including all accesorios of following sizes of 1.1 KV PVC insulated, inner & outer PVC sheath extruded type ST-2, Copper conductor, armoured cables conforming to IS : 7098 (Part-II) and as per specification.(For HT Panel controls, Transformer Protection, PLC controls.) including cost of termation.12 x 2.5 sq. mm. |
| 1230 | 10 x 2.5 sq. mm. |
| 1231 | 6 x 2.5 sq. mm. |
| 1232 | 4 x 2.5 sq. mm. |
| 1233 | 2 x 2.5 sq. mm. |
| 1234 | 2 x 1.5 sq. mm. |
| 1235 | 3 x 1.5 sq. mm. |
| 1236 | Part - III - Market Rate Items2000 KVA, 11/0.433 KV Outdoor Typpe with OCTC TransformerSupplying, Installation, Testing and Commissioning of following capacity (continuous loading) Energy Efficiency Level 2 (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV Step down, 3 Phase, 50 Hz, Dyn 11 vector group, KNAN [K(K-Class insulating liquid) Natural Air Natural] copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better), Dielectric material shall be type -A, suitable for out door/indoor applications with Off Circuit Tap Changer (OCTC) on HV in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS 1180 (Part-3) including first filling of filtered dehydrated Natural Ester Oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 (Part-3) and as per CPWD specifications complete in all respects etc as required at site. |
| 1237 | The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with +12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 55 °C for oil and 60 °C for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition : a) air temperature 50 °C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. |
| 1238 | Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent ; k) One filter valve on the upper side of the tank; l) Unidirectional flat rollers; m) Inspection hole; n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators with suitable tripping mechanism above permissible limit s) Jacking pads; t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. |
| 1239 | (2W + 1S)2000 KVA |
| 1240 | INCOMER: 2 No. 800 Amp 11KV 26 kA for 1 sec VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switch and comprising of following items:Voltage Transformer comprising three (3) single-phase units, connected in star (Y) configuration, dual accuracy class, rated for 11 kV / √3 / 110 V / √3 class 0.5 accuracy for metering & class 3P for protection.The PTs shall be draw-out type with automatic shutters, suitable for installation in 11 kV switchgear panels.Each PT shall have a rated burden of 100 VA on both the bus side and line side, and shall be provided with primary and secondary fuses.The PT shall be manufactured and tested in accordance with the relevant IS/IEC specifications. Digital Voltmeter & Ammeter with inbuilt Selector SwitchPhase indication lamps protected through 3 nos. 2A SP MCBs Under Voltage & Over voltage protection device protected through 3 Nos. 6A SP MCBs. One (1) set comprising three (3) dual-core, dual-ratio current transformers (CTs), having a ratio of 300/150 A / 5 A, with a rated burden of 15 VA per core. Accuracy class: 1.0 for metering and 5P10 for protection.CTs shall be resin-cast type, suitable for indoor installation in 11 kV switchgear panels, and shall conform to the requirements of IS/IEC 61869-2 (formerly IS 2705).The following protections shall be provided : 1 No. Microprocessor based numerical relay (IDMT relay) with 2 levels of over current and earth fault protection, 3 O/C and 2 E/F element with LED’s for fault indication and at least 15 trip records for over current & 15 for earth fault. Trip records must be with date & time stamping Ground Detector Relay (64R) Antipumping relay & Master trip relay (86). Over Voltage Relay with Timer (59) Trip Circuit Supervision Protection Relay (95) Non-directional overcurrent relay (50/51) Non-directional earth-fault sensitive (51N/50N) Under Voltage Relay with Timer (27) 3 Nos. Transformer Supervision Relays 1 Set of multifuction meter with basic parameters like frequency, KW,KWH KVA, KVAR, Power Factor, total harmonic distortion, MDI etc. shall be suitable for EMS(Energy Management system) function with RS 485 port for communication. 1 Set of following indicating lamps. Amber for Trip indication. Red 'ON' Green 'OFF' Spring charge indication. Trip Circuit Healthy indication. Breaker positioning lamps & DC Circuit Healthy indicaton lamp. TNC (Trip, Neutral, Close) breaker control switch with indication. arrangement. 1 No. Hooter with Accept/Reset & Test Push Button Local/remote Selector Switch & Emergency Push Button with necessary NO/NC Contacts. 8 window annunciation panel with audio and visual indicator common for the full panel. |
| 1241 | BUS BAR: 850A TP tinned CU Bus Barit shall be single bus bar pattern with air insulated encapsulated bus bars housed in a separate compartment, segregated from other compartments. The Bus bar material shall be high conductivity tinned Copper rated as specified. Max. Bus Bar temp shall not exceed 90 degree C in any conditions viz. rated and short circuit current.Short time current rating : 26kADuration of Short circuit withstand : 1 SecBus-Couple1 No. 800 Amp 11KV 26kA for 1 sec VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switch and comprising of following items:800 amp air insulated but encapsulated copper bus bars (26 KA For 3 Sec.).Under voltage (27) & over voltage (59) relays.Antipumping relay & Master trip relay (86).Ground Detector Relay (64R)Trip Circuit Supervision Protection Relay (95)Non-directional overcurrent relay (50/51)Non-directional earth-fault sensitive (51N/50N)Danger Plate (as per IS specification)50 x 6 mm AL earth bus shall be provided for the full length of the panel.Emergency trip push button on front doorLimit switches with 6 NO/ 6 NC breaker auxiliary contactsSpace heater with thermostat for moisture absorptionSurge Arrestor, 10KA, Class II.Out going: 4 nos1 No. 800 Amp 11KV 26kA for 1 sec VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switch and comprising of following items:Digital voltmeter and Ammeter with inbuilt Selector SwitchOne (1) set comprising three (3) dual-core, dual-ratio current transformers (CTs),having a ratio of 160/80 A / 5 A, with a rated burden of 15 VA per core.CTs shall be resin-cast, indoor type, suitable for mounting in 11 kV switchgear panels, and shall conform to the requirements of IS/IEC 61869-2 (formerly IS 2705). |
| 1242 | The following protections shall be provided :1 No. Microprocessor based numerical relay (IDMT relay) with 2 levels of over current and earth fault protection, 3 O/C and 2 E/F element with LED’s for fault indication and at least 15 trip records for over current & 15 for earth fault. Trip records must be with date & time stamping. ANSI : 50, 50N, 51, 51NGround Detector Relay (64R)Antipumping relay & Master trip relay (86).Over Voltage Relay with Timer (59)Trip Circuit Supervision Protection Relay (95)Non-directional overcurrent relay (50/51)Non-directional earth-fault sensitive (51N/50N)Under Voltage Relay with Timer (27)3 Nos. Transformer Supervision Relays1 Set of multifuction meter with basic parameters like frequency, KW,KWH KVA, KVAR, Power Factor, total harmonic distortion, MDI etc. shall be suitable for EMS(Energy Management system) function with RS 485 port for communication.1 Set of following indicating lamps.Amber for Trip indication.Red 'ON' Green 'OFF' Spring charge indication. Trip Circuit Healthy indication.Breaker positioning lamps & DC Circuit Healthy indicaton lamp.TNC (Trip, Neutral, Close) breaker control switch with indication. arrangement.1 No. Hooter with Accept/Reset & Test Push ButtonLocal/remote Selector Switch & Emergency Push Button with necessary NO/NC Contacts.8 window annunciation panel with audio and visual indicator common for the full panel. |
| 1243 | Note:Panel shall have incomer & Outgoing connections suitable for 1R x 3C x 300 sq. mm. XLPE 11KV cable (cable entry from bottom side) with indoor kit, end termination with heat shrinkable jointing kit etc. as required.Bus-bar arrangement should be such that in future similar cubicles can be connected with this cubicle.All nut & bolts used inside the panel should be of high tensile, bright zinc plated, hexagonal headed, metric size, manufacture to DIN-931 of steel, tensile strength as per standard, coarse threaded with two nos. bright zinc plated flat and spring washers.50 x 6 mm Cu. earth bus shall be provided for the full length of the panel.Danger Plate shall be provided (as per IS specification)Surge Arrestor, 10KA, Class II shall be provided.Space heater with thermostat for moisture absorption shall be provided.02 (Two) Nos. cubicle lamps (LED) in each cubicle shall be provided along with switch.Power Pack 230V AC/24V DC, 42AH, 2X12V battery for providing auxiliary power to Trip Coil and other necessary equipments as required. |
| 1244 | 11 KV, Seven (7) Panel Board ( 02 I/C+01B/C+ 04 O/G ) All Services as described above and as per technical specifications & SLD |
| 1245 | GENERAL SPECIFICATION FOR All LV & HPFC Panels1.0 SCOPEa) The scope of work includes the design, manufacture, and supply of all Low Voltage (LV) panels from reputed manufacturers, type-tested with arc type tested at ASTA/ CPRI/ ERDA in accordance with IEC 61439 (Part 1 & 2) along with IEC 61641. The panels shall be suitable for a 415 V, 50 Hz, 4-wire system and shall incorporate circuit breakers of various types, bus bars, interconnections, metering, and other accessories as required. The design shall comply with the requirements indicated in the Bill of Quantities (BOQ), Single Line Diagrams (SLDs), and technical specifications specified in the contract.b) The LT Panel shall undergo seven/nine tank process of degreasing, pickling in acid, cold rinsing, phosphating, passivating and then be powder coated and painted with dry epoxy paint in Siemens gray RAL 7032 shade or approved by Engineer-in-charge. Painting thickness shall not be less than 65 microns.2.0 CONSTRUCTION FEATURES: GENERAL :LT Panel shall have following features : a) Panel board shall be of modular cubical construction and extensible type made of CRCA steel sheet - 2.00 mm thick for load bearing and 1.6 mm for other sections. b) Panel shall be suitable for floor mounting free standing, dust and vermin proof confirming to IP42 degree of protection. c) Panel shall be provided with base channel of 75 mm X 40 mm fabricated out of 5 mm thick hot rolled sheet steel painted black. d) For convenience of operation and ease of cable termination, there shall be a gap of at least 150 mm between the floor level and the bottom-most unit.e) Removable Gland plates of adequate size made of 3 mm thick MS sheet, properly screwed to the panel base shall be provided. Cut outs for cable glands shall be provided as per the direction of Engineer-In-Charge. f) Each incoming circuit breaker/switchgear shall be housed in a separate enclosure and the panel shall conform to Form 3b as per IEC. g) Outgoing links from feeders shall be rigidly supported and suitably extended in cable box chamber for incase of cable connections. Cable lugs and links shall be covered by insulated shields. Barriers shall be provided between the modules accommodating equipment associated with the outgoing circuits. h) Control wiring shall be done by minimum 2.5 sq mm FRLS copper wire i) All control wiring shall be fitted with identification ferrule and shall be terminated by using crimping lugs. j) All cable termination shall be fitted with suitable capacity Lugs.k) The switchboard shall be designed to accommodate 1100 V grade Copper or Aluminium conductor PVC/XLPE cables, with provisions for cable entry from the top and/or bottom, as applicable. l) Labels shall be provided on all the incoming and outgoing feeder compartments. m) The LT Panel shall be provided with two earth bars made of 50 mm × 6 mm aluminium strips, securely fastened to the enclosure body. The earth bars shall run along the full length of the panel and shall be brought out for the termination of earthing conductors. |
| 1246 | 3.0 CIRCUIT BREAKER3.1 AIR CIRCUIT BREAKER :a) ACBs shall by Electrically draw-out type (EDO).b) Short Circuit rating : Icu = Ics = Icw = 50 kA for all transformer incomers, bus couplers & rest ACBs.c) ACBs shall have Closing Time less than 70 ms & opening time less than 30 ms.d) All ACBs shall have Microprocessor based, self-powered, true RMS sensing Release having front display unit to show % Loading and bar-graphe) All 4P ACBs shall have fully rated neutral equal i.e. 100% Neutral.f) All ACBs shall have inbuilt LSING protection (Overload/Short-circuit/Instantaneous/Neutral/Ground Fault) with settable time delayg) ACB shall show 20 trip datah) Breaker shall have U/V release and shunt trip coili) Minimum 6 nos. of NO and 6 nos. of NC auxiliary contacts to be provided.j) ACB shall be able to communicate ON/OFF/Trip on Modbus TCP / IP protocol (Ethernet).k) ACBs shall conform to IS/IEC 60947-2 & IEC 60947-23.2 Moulded Case Circuit breakers (MCCB)a) All MCCBs Shall be four pole unless and until specifically mentioned. TPN MCCB if mentioned shall be considered as 4 Pole.b) All MCCBs shall have Ics = 100% Icuc) MCCBs upto 160A shall be 25 kA breaking capacity and above that shall be 36 kA/50kA as per BOQ.d) All MCCBs up to 250 amp MCCB shall have thermal magnetic based release and above 250A shall have Microprocessor based release.e) All MCCBs shall have variable thermal (0.67 - 1 In) & variable magnetic settingf) All Microprocessor based MCCBs shall have in-built LSING ( (Overload/Short- circuit/ Instantaneous/ Neutral/Ground Fault) protection.g) All MCCBs shall have 100% rated Neutral (100% of Ir)h) All MCCBs equal and above 100A must be provided with OEM manufactured spreader linksi) All MCCBs shall be with extended rotary operating handle.j) MCCBs shall conform to IS/IEC 60947-2 |
| 1247 | 4.0 BUS BARS :a) Three Phase & Neutral (100%) Tinned Copper bus bars shall be provided of specified rating. Bus bar selection shall be designed as per current ratings and match the short circuit fault level rating as well as temperature rise of 45 degree over an ambient temperature of 45 degree. Design calculation to be shared at the time of GAD approval.b) Bus bar shall be insulated with heat shrinkable sleeves in distinguished color so as to identify the various phases of the busbrs. No exception to this will be considered.c) Bus bar shall be housed in separate bus bar chambers. Horizontal busbars shall extend through out the length of the panels. Bus bars shall be supported on unbreakable non-hygroscopic phenolic laminated sheet/bus bar insulators rigidly held to the framework of the chamber. Bus bar chamber shall have a separate screwed cover.d) Vertical busbars shall be accessible from the front. Connection between horizontal and vertical bus bar shall be made by overlapping the vertical bus bar over horizontal bus bar covering its full wide section.e) The clearance between phase-to-phase bus bars and phase-to-neutral bus bars shall be in accordance with the relevant IEC standards.f) The horizontal bus bar shall be designed to facilitate easy extension in the future.MAIN LT PANEL (UTILITY BUILDING) Supply, installation, testing, and commissioning of the Main LT Panel suitable for 415 V, 4-pole, 50 Hz A.C. supply. The Main LT Panel shall be of single-front or double-front, totally enclosed, compartmentalized, free-standing, floor-mounted, indoor type construction. The enclosure shall be dust and vermin proof, fabricated from CRCA sheet steel — 2.0 mm thick for load-bearing members and 1.6 mm thick for non-load-bearing members. The panel shall be complete with tinned copper bus bars, multifunction meters, indicating lamps, protection relays, CTs, protective MCBs, and all necessary interconnections using suitably sized solid copper strips or power cables and control wiring, including breaker control switches and other accessories as required. The bus bar system shall be rated for 4000 A, TPN, made of electrolytic grade E91-E tinned copper, with a short-circuit withstand capacity of 50 kA for 1 second. The Main LT Panel shall be designed to facilitate termination of: Incoming 4000A Al. sandwich type bus ducts from three 2000 KVA transformers. The panel shall also be provided with provisions for outgoing (O/G) terminations through adequately sized copper/aluminium cables, as specified in the Bill of Quantities (BOQ) and approved drawings.All terminations shall be suitably supported, shrouded, and arranged to ensure ease of connection, maintenance, and compliance with IEC 61439 requirements for clearances, creepage distances, and thermal performance. |
| 1248 | INCOMER FROM 2000KVA TRANSFORMER-1,2&3 - 3 Sets. and each set comprising of3200A,50kA FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No.Digital Ammeter with Selector Switch - 1 No.Digital Voltmeter with Selector Switch - 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 3200/5 ratio, 15 VA Class 1.0 for metering6 nos NO/NC contacts for remote opening & closing.Red/Green/Amber ON/OFF/TRIP indicating lamps with 6A SP MCB backup protection.1 set of three phase indicating lamps along with 6A SP MCB backup protection.ON/OFF/ TRIP/Spring Charge/Test Service Indication Lamp - 7 No.Spring charge & DC supply healthy indicating lamp with 6A SP MCB backup protection.1 Nos. current transformer of 3200/5A ratio Class 1.0, 15 VA Burden for PF correction relay.Motor wound spring closing mechanism.Suitable arrangement to receive incoming 4000 Amp. Al. Sandwitch Type Busduct.T-N-C Breaker control switch Control MCB, control terminals& wiring as required.One auto/manual selector switchUnder voltage and over voltage relay ,3 Phase with Time delay setting.Instantaneous Overcurrent Relay (50).Time Overcurrent Relay (51).Instantaneous Neutral Overcurrent Relay (Earth Fault) (50N)Time Overcurrent Neutral Relay (Earth Fault) (51N)Trip Circuit Supervision Relay (95)Lockout Relay (86)1No. 32 Amp , 4P , MCB (10KA).1No. current transformer of 3200/5A ratio Class PS 15 VA Burden to be supplied loose to mount in Transformer.Surge Protection Device with type |
| 1249 | BUS COUPLER - 2 Sets and each set comprising of3200A, 32kA FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No.6 Nos. NO/NC contacts for remote opening & closingBreaker shall have manually operated /motorised / manual spring charge fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS -60947 (as amended up todate).Cast resin type current transformer of ratio 3200/5 A for metering and protection3 Nos. LED showing R, Y, & B voltage and 16 Amp TNC switch for ON / OFF/ Close ACB required. Suitable nos. and appropriate rating of HRC fuses/ MCB required for protection of LED and auxiliary power supply, control circuit for closing, tripping and indication circuit and numerical relay etc.Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing |
| 1250 | 4000A TPN 50 kA tinned AL. Busbar With PVC Heat Shrinkable sleeveOUTGOING 3200A ACB FEEDER -02 Sets and each set comprising of:3200A,50kA, FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 3200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.OUTGOING 2000A ACB FEEDER - 02 sets and each set comprising of:2000A,50kA FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 2000/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.OUTGOING 1600A ACB FEEDER - 02 sets and each set comprising of:1600A,50kA FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 1600/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No. |
| 1251 | OUTGOING 800A ACB FEEDER - 01 sets and each set comprising of: 800A,50kA FP EDO TYPE ACB with Microprocessor release ( S/C, O/L, E/F ) - 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 800/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. OUTGOING 630A MCCB FEEDER - 07 sets and each set comprising of: 630A FP 50kA MCCB WITH Microprocessor release (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 630/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 250A MCCB FEEDER - 04 No. 250A FP 36kA MCCB WITH Microprocessor release (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 200A MCCB FEEDER - 03 sets and each set comprising of: 200A FP 25 kA MCCBWITH THERMAL MAGNETIC(TM) RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 125A MCCB FEEDER - 09 sets and each set comprising of: 125A FP 25kA MCCB WITH THERMAL MAGNETIC(TM) RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 63A MCCB FEEDER - 02 sets and each set comprising of: 63A FP 25kA MCCB WITH THERMAL MAGNETIC(TM) RELEASE(O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B Note: The contractor shall ensure that synchronization is properly achieved for all DG sets. Prior to procurement, the contractor shall obtain approval from the Engineer-in-Charge for the sequence of operations, synchronization scheme, and control logic of the DG sets. |
| 1252 | ELECTRICAL PANEL FOR BUILDING -01 ( PCB & ADMIN BUILDING ) for Equipments ( AS PER SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER :3200A,65kA, FP EDO TYPE ACB with Microprocessor release (O/L & S/C,E/F) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 3200/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 2000A ACB FEEDER - 2 sets and each set comprising of: 2000A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE(O/L & S/C,E/F) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 2000/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 1000A ACB FEEDER - 1 sets and each set comprising of: 1000A 4P 50kA EDO ACB WITH MICROPROCESSOR RELEASE (O/L & S/C,E/F) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 1000/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 250A MCCB FEEDER - 1 sets and each set comprising of: 250A 4P 36kA MCCB WITH Microprocessor based (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/B OUTGOING 200A MCCB FEEDER - 1 sets and each set comprising of:200A 4P 25kA MCCB WITH TM RELEASE(O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B |
| 1253 | OUTGOING 125A MCCB FEEDER - 6 sets and each set comprising of:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 1 sets and each set comprising of:63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B4000A TPN 50 kA tinned copper Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1254 | ELECTRICAL PANEL FOR BUILDING - 01 ( PCB & ADMIN BUILDING ) for Light & Power (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:630A,50kA, FP, MCCB with Microprocessor release (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 630/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 200A MCCB FEEDER - 2 sets and each set comprising of:200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B |
| 1255 | OUTGOING 160A MCCB FEEDER - 2 sets and each set comprising of:160A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 4 sets and each set comprising of:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 1 sets and each set comprising of:63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B |
| 1256 | 1000A TPN 50 kA tinned copper Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1257 | MAIN ELE. PANEL FOR BUILDING -01 ( PCB & ADMIN BUILDING ) for HVAC (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER : 630A 4P 50kA MCCB WITH MICROPROCESSOR RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 630/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B, OUTGOING 200A MCCB FEEDER - 03 sets and each set comprising of 200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 6 sets and each set comprising of 100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 03 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B, OUTGOING 63A MCB FEEDER - 03 sets and each set comprising of 63A 4P 16 kA MCB Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 40A MCB FEEDER - 12 sets and each set comprising of 40A 4P 10 kA MCB Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B |
| 1258 | 800A TPN 50 kA tinned copper Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1259 | Sub-Panel for Light DB's (Building-01) Ground Floor (As per SLD) Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 03 sets and each set comprising of100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 02 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.160A TPN 25 kA tinned copper Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1260 | Sub-Panel for Power DB's (Building-01) Ground Floor as per SLDSupplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 3 Nos125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 02 Nos63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 250A TPN 25 kA tinned copper With PVC Heat Shrincable sleeve |
| 1261 | Sub-Panel for Light DB's (Building-01) First Floor (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 01 sets and each set comprising of100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 04 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 250A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1262 | Sub-Panel for Power DB's (Building-01) First Floor as per SLDSupplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:160A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 06 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 200A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1263 | ELECTRICAL PANEL FOR BUILDING -02 for Equipments (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 250A 4P 36kA MCCB WITH MICROPROCESSOR RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 200A MCCB FEEDER - 01 sets and each set comprising of 200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B,OUTGOING 125A MCCB FEEDER - 4 sets and each set comprising of 125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 03 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BBUSBAR: 315A TPN 50 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1264 | MAIN ELE. PANEL FOR BUILDING -02 for Light & Power (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 800A,50kA, FP, ACB with Microprocessor release (O/L & S/C,E/F) with rotary operating handle(ROH) - 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 800/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 250A MCCB FEEDER - 03 sets and each set comprising of: 250A 4P 36kA MCCB WITH MICROPROCESSOR BASED (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B, OUTGOING 160A MCCB FEEDER - 01 sets and each set comprising of: 160A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 160/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 5 sets and each set comprising of: 125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 01 sets and each set comprising of:63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BBUSBAR: 1000A TPN 50 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1265 | MAIN ELE. PANEL FOR BUILDING -02 for HVAC as per SLDSupplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 630A 4P 50kA MCCB WITH MICROPROCESSOR RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 630/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 200A MCCB FEEDER - 02 sets and each set comprising of: 200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 125A MCCB FEEDER - 3 sets and each set comprising of: 125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 1 sets and each set comprising of: 100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 63A MCCB FEEDER - 10 sets and each set comprising of: 63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 63A MCB FEEDER - 03 sets and each set comprising of: 63A 4P 16kA MCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 63/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. indicating Lamp - R/Y/B OUTGOING 40A MCB FEEDER - 10 sets and each set comprising of: 40A 4P 16kA MCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 800A TPN 50 kA tinned copper With PVC Heat Shrincable sleeve |
| 1266 | Sub-Panel for Light DB's (Building-02) Ground and First Floor(As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 03 sets and each set comprising of100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 01 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCB FEEDER - 01 sets and each set comprising of63A 4P 16kA MCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeve |
| 1267 | Sub-Panel for Power DB's (Building-02) Ground and First Floor(As per ) Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:250A 4P 36kA MCCB WITH Microprocessor Based RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 3 sets and each set comprising of125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 01 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCB FEEDER - 01 sets and each set comprising of63A 4P 16kA MCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 315 TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1268 | UTILITY BUILDING PANEL (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCB FEEDER - 05 sets and each set comprising of63A 4P 16 kA MCB-05 Nos.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1269 | LIFT PANEL FOR BUILDING-1 (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 04 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 40A MCB FEEDER - 04 sets and each set comprising of40A, 4P, 10kA MCB - 1 No.OUTGOING 40A, DP MCB FEEDER - 01 sets and each set comprising of40A DP 10kA MCB – 1 No.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1270 | MAIN LIFT PANEL FOR BUILDING -02 (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:250A 4P 25kA MCCB WITH Microprocessor Based RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 250/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 160A MCCB FEEDER - 02 sets and each set comprising of160A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 125A MCCB FEEDER - 2 sets and each set comprising of125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 63A MCCB FEEDER - 01 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.BUSBAR: 315A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1271 | LIFT PANEL for lift of Building-2 (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 04 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 40A MCB FEEDER - 04 sets and each set comprising of40A, 4P, 10kA MCB - 1 No.OUTGOING 40A, DP MCB FEEDER - 01 sets and each set comprising of40A DP 10kA MCB – 1 No.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1272 | LIFT PANEL FOR (04 NOS.) lift of Building-2 (As per SLD- RITES/BLD/ELE/SLD/006.)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:160A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 160/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 05 sets and each set comprising of63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.OUTGOING 40A MCB FEEDER - 05 sets and each set comprising of40A 4P 10kA MCB-01No. OUTGOING 40A DP MCB FEEDER - 01 sets and each set comprising of40A DP 10kA MCB -01No.BUSBAR: 200A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1273 | UPS PANEL-1 for Building -01 & 02 Light & Power & Equipments load of Building-1 (As per SLD )Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 125A, 4P, 25kA, MCCB-02 sets and each set comprising of 125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B BUS COUPLER - 01 NO. 125A,4P, 25kA, MCCB with thermal magnetic release ( S/C, O/L, E/F ) with ROH - 1 No. ON/OFF/ TRIP - 3 Nos. Indicating Lamp - R/Y/B OUTGOING 100A MCCB FEEDER - 5 sets and each set comprising of 100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCB FEEDER - 02 sets and each set comprising of63A 4P 16kA MCB – 1 No.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1274 | UPS PANEL-2 OF BUILDING-02 FOR IT SERVICES (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 125A, 4P, 25kA, MCCB-02 sets and each set comprising of125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/BBUS COUPLER - 01 NO.125A,4P, 25kA, MCCB with thermal magnetic release ( S/C, O/L, E/F ) with ROH - 1 No.ON/OFF/ TRIP - 3 Nos.Indicating Lamp - R/Y/BOUTGOING 100A MCCB FEEDER - 6 sets and each set comprising of100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCB FEEDER - 02 sets and each set comprising of63A 4P 16kA MCB – 1 No.BUSBAR: 160A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1275 | UPS PANEL OF BUILDING-02 FOR IT SERVICES GROUND AND FIRST FLOOR (As per SLD- )Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER: 100A, 4P, 25kA, MCCB-02 sets and each set comprising of125A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/BBUS COUPLER - 01 NO.100A,4P, 25kA, MCCB with thermal magnetic release ( S/C, O/L, E/F ) with ROH - 1 No.ON/OFF/ TRIP - 3 Nos.Indicating Lamp - R/Y/BOUTGOING 63A MCCB FEEDER - 2 sets and each set comprising of100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 63A MCB FEEDER - 05 sets and each set comprising of63A 4P 16kA MCB – 1 No.BUSBAR: 125A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1276 | PANEL FOR ELV SYSTEM FOR BUILDING-01 & 02 (AS PER SLD.)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 100/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 32A MCB FEEDER - 04 sets and each set comprising of32A 4P 10 kA MCB-01 OUTGOING 16A DP MCB FEEDER - 05 sets and each set comprising of16A DP 10 kA MCB-01BUSBAR: 125A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1277 | Main HVAC Panel (HVAC Plant room)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 1600A,50kA, FP EDO TYPE ACB with Microprocessor release (O/L & S/C,E/F) – 1 No.Digital Ammeter with Selector Switch - 1 No. Digital Voltmeter with Selector Switch - 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 1600/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BBUSBAR: 2000A TPN 50 kA tinned copper With PVC Heat Shrincable sleeveOUTGOINGS: 4 Nos. 630 amp 50 kA 4P MCCB with microprocessor release having overcurrent and short circuit protection for Chiller (260 KW)4 Nos. 160 amps 25kA 4P MCCB with thermal magnetic release having overcurrent and short circuit protection with space provision of VFD for Secondary Chilled Water Pump (55 KW). 3 Nos. 125 amps 25 kA, 4P MCCB with Star Delta starter for 45 KW motor , over load relay with built in single phasing protection and outgoing feeder to Conderser Water Pump. The compartment shall contain an indicating lamp with MCB for ON & OFF status of pump motor.3 Nos. 63 amps 4P MPCB with Star Delta starter for 22.2 KW motor , over load relay with built in single phasing protection and outgoing feeder to Primary Chilled Water Pump. The compartment shall contain an indicating lamp with MCB for ON & OFF status of pump motor.6 Nos. 32 amps 4P MPCB with dol starter for 5.5 KW motor , over load relay with built in single phasing protection and outgoing feeder to Cooling Tower Fan Motor. The compartment shall contain an indicating lamp with MCB for ON & OFF status of fan motor.Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1278 | EMERGENCY PANEL BUILDING-1&2Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOutgoings25 Nos. 32 A,4P, MPCB with DOL starter for 4.0 KW motor, with built in single phasing protection and outgoing feeder to fresh air fan Fan Motor. The compartment shall contain ammeter in one phase with CT. Auto/Manual selector switch along with ON/OFF/TRIP indicating lamp with MCB for ,ON, status of fan motorBUSBAR: 250A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1279 | Panel for BUILDING-01 Smoke Exhaust fan (As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER:200A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOutgoings13 Nos. 63 amps 4P, MPCB with Star Delta starter for 11 KW motor, with built in single phasing protection and outgoing feeder to Emergency Exhaust air & Fresh air Fan Motor. The compartment shall contain ammeter in one phase with CT. Auto/Manual selector switch along with ON/OFF/TRIP indicating lamp with MCB for ,ON, status of fan motor2 Nos. 32 A,4P, MPCB with DOL starter for motor, with built in single phasing protection and outgoing feeder to fresh air fan Fan Motor. The compartment shall contain ammeter in one phase with CT. Auto/Manual selector switch along with ON/OFF/TRIP indicating lamp with MCB for ,ON, status of fan motorBUSBAR: 250A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1280 | Panel for BUILDING-02 Smoke Exhaust fan ((As per SLD)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOutgoings2 Nos. 32A,FP MPCB with DOL starter for 5.5 KW motor, with built in single phasing protection and feeder to Emergency Exhaust air Fan Motor.. The compartment shall contain ammeter in one phase with CT. Auto/Manual selector switch along with ON/OFF/TRIP indicating lamp with MCB for ,ON, status of fan motor3 Nos. 40A, FP MPCB with Star Delta starter for 7.5 KW motor, with built in single phasing protection and outgoing feeder to Emergency Exhaust air Fan Motor. The compartment shall contain ammeter in one phase with CT. Auto/Manual selector switch along with ON/OFF/TRIP indicating lamp with MCB for ,ON, status of fan motorBUSBAR: 250A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1281 | AHU PANEL (11.0 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER :63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/B BUSBAR: 100A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings1 Nos. 32 amps 4P MCB for AHU motor with VFD of 11 KW 1 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERSNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1282 | AHU PANEL (7.5 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/BBUSBAR: 100A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps 4P MCB for AHU motor VFD of 7.5 KW 2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1283 | AHU PANEL (18.5 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 125A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings2 Nos. 63A,4P MCB for AHU motor with VFD of 18.5 KW 2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation.The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1284 | AHU PANEL (7.5 KW AHU Fan Motor) -Floor Mounted AHU (Building-02)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER : 63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/B BUSBAR: 100A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps, 4P MCB for AHU motor with VFD of 7.5 KW 2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1285 | AHU PANEL (15 KW AHU Fan Motor) -Floor Mounted AHU ( Building-02)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 100A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/BBUSBAR: 125A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings2 Nos. 63 amps, 4P MCB for AHU motor with VFD of 15 KW 2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERSNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1286 | AHU PANEL (11.0 KW AHU Fan Motor) -Floor Mounted AHU (Building-02)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 63A 4P 25kA MCCB WITH TM RELEASE (O/L & S/C,E/F) with Rotary operating handle(ROH) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 25 kA tinned copper With PVC Heat Shrincable sleeveOutgoings2 Nos. 32A, 4P MCB for AHU motor with VFD of 11 KW 2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation.The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1287 | AHU PANEL (2.2 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A FP 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps TPN MCCB for AHU motor VFD of 2.2 KW with Bypass Star-Delta Stater2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories. Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1288 | AHU PANEL (3.8 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A FP 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps TPN MCB for AHU motor VFD of 3.8 KW with Bypass Star-Delta Stater2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories. Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1289 | AHU PANEL (1.1 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A FP 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings 2 Nos. 25 amps TPN MCCB for AHU motor VFD of 1.1 KW with Bypass Star-Delta Stater2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories. Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1290 | AHU PANEL (0.8 KW AHU Fan Motor) -Floor Mounted AHU (Building-01)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A FP 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps TPN MCCB for AHU motor VFD of 0.8 KW with Bypass Star-Delta Stater2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories.Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1291 | AHU PANEL (2.2 KW AHU Fan Motor) -Floor Mounted AHU (Building-02)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A TPN 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps TPN MCCB for AHU motor VFD of 2.2 KW with Bypass Star-Delta Stater2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories. Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1292 | AHU PANEL (1.5 KW AHU Fan Motor) -Floor Mounted AHU (Building-02)Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER 40A FP 16kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 40/5A,15 VA Class 1.0 for metering. ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No. Indicating Lamp - R/Y/BBUSBAR: 100A TPN 10kA AL. Busbar With PVC Heat Shrincable sleeveOutgoings2 Nos. 25 amps TPN MCCB for AHU motor VFD of 1.5 KW with Bypass Star-Delta Stater–2 No. 6 amps 2 Pole MCB for fire damper actuator.1 No. 6 amps 2 Pole MCB for UVGI Lamp.1 No. 6 amps 2 Pole MCB for room thermostat/PICV valve.1 No. 6 amps 2 Pole MCB for return air temperature sensor/differential pressure transmitter.NO/NC Contact for BMS as required.\\"All VFD (as per list of make) shall be with in built harmonic filter & capable to provided digital display showing electrical parameters like voltage, current and power consumption (both KW & KWH) as well as % speed indication. It shall also have. contactor, Communication Port compatible with BMS etc. complete as required The Drive is having IP 55 Enclosure for safe and reliable operation. The Drive should have 3C3 Coating on PCBs to safeguard the Drives from any contaminants in the ambient.VFD HAVE THE FOLLOWING CONTROLS:-1-TEMP. SENSOR FEEDBACK TO CONTROL THE FAN SPEED FROM VFD.2-TRIGGERING THE AHU SHUTDOWN DURING THE FIRE ON GETTING SIGNAL FROM FIRE DAMPERS3- A bypass starter shall be provided complete with all necessary components and accessories.Note: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge |
| 1293 | Surface Mounting Technology & Wave Soldering Assembly Panel ( AS PER SLD) Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER - 1 sets and each set comprising of: 2000A,50kA, FP EDO TYPE ACB with Microprocessor release (O/L & S/C,E/F) – 1 No. Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 3200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos. Neutral Link - 1 No.Indicating Lamp - R/Y/B OUTGOING 200A MCCB FEEDER - 06 sets and each set comprising of:200A TPN 25kA MCCB WITH TM RELEASE(O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 27 sets and each set comprising of:125A TPN 25kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B2500A TPN 50 kA AL. Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1294 | Electronic Assembly & PCB Inspection Panel Supplying, installation testing and commissioning of cubical type electrical panel board suitable for 3 phase, 415 + 10% volts, 50 + 3% Hz.fabricated from minimum 2 mm thick CRCA sheet powder coated through seven/Nine tank process facility for prickling and degreasing complete with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required. INCOMER - 1 sets and each set comprising of: 1000A,50kA, FP EDO TYPE ACB with Microprocessor release (O/L & S/C,E/F) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 3200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos.Neutral Link - 1 No. Indicating Lamp - R/Y/B OUTGOING 200A MCCB FEEDER - 02 sets and each set comprising of:200A TPN 25kA MCCB WITH TM RELEASE(O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 200/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos. Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/BOUTGOING 125A MCCB FEEDER - 25 sets and each set comprising of:125A TPN 25kA MCCB WITH TM RELEASE (O/L & S/C) with Rotary operating handle(ROH) – 1 No.Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port with 3 Nos. current transformers of 125/5A,15 VA Class 1.0 for metering.ON/OFF/ TRIP - 3 Nos.Control 6A SP MCB - 3 Nos.Neutral Link - 1 No.Indicating Lamp - R/Y/B1250A TPN 50 kA AL. Busbar With PVC Heat Shrincable sleeveNote: Prior to procurement, the contractor shall obtain approval of the GA drawings of the panel from the Engineer-in-Charge. |
| 1295 | Feeder Pillar. (External Lighting)Design, manufacturing, testing at works, supply, delivery at site including supervision during installation of double door panel fabricated with minimum 2mm thick CRCA sheet, Conform to IS Specification, with IP-55 enclosure protection, as per IS-2137(Revised), floor mounting free standing on a suitable massanory pedestal outdoor type panel, provided with hinged detachable and lockable outer opening doors with the following incoming/outgong MCCB/ MCBs mounted therein including making connections/ interconnections, earthing, painting etc. as required.The panel shall have canopy arrangement on the top.All MCB to be C curve. Protection -IP-55.Incoming:1 Nos. of 125 Amp FP MCCB of 25KA breaking capacity.Bus BarsElectrolytic high conductivity Aluminium three phase and neutral busbars rated at 160 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoing: 3 Nos. 40A DP MCB 10 KA breaking capacity controlled by 3 Nos 40 A DP contactor and Timer.18 Nos. 25A DP MCB 10 KA breaking capacity.EXTERNAL LIDHTING DB- X (Typ. for DB-Y) described as above and all as per specification. |
| 1296 | Supply of following sizes of 11 KV (E) grade, aluminium conductor, XLPE insulated, inner & outer PVC sheath extruded type ST-2 armoured cables conforming to IS : 7098 (Part-I), and as per specification. |
| 1297 | 3C X 300 sq. mm |
| 1298 | Supply of following sizes of 1.1 KV grade XLPE insulated aluminium conductor, inner & outer PVC sheath extruded type ST-2 armoured power cables conforming to IS : 7098 (Part-II) and as per specification. (Note: Upto 16 SQMM Cu. Conductors & Upto 300 SQMM Al. Conductors will be Considered) |
| 1299 | 3.5 x 300 Sq.mm. |
| 1300 | 3.5 x 240 Sq.mm. |
| 1301 | 3.5 x 150 Sq.mm. |
| 1302 | 3.5 x 120 Sq.mm. |
| 1303 | 3.5 x 70 Sq.mm. |
| 1304 | 3.5 x 50 Sq.mm. |
| 1305 | 3.5 x 35 Sq.mm. |
| 1306 | 4 x 25 Sq.mm. |
| 1307 | 4 x 16 Sq.mm. |
| 1308 | 4 x 10 Sq.mm. |
| 1309 | 4 x 6 Sq.mm. |
| 1310 | 3 x 6 Sq.mm. |
| 1311 | 2 x 10 Sq.mm. |
| 1312 | 4 x 16 Sq.mm. (Copper Unarmoured) |
| 1313 | 4 x 25 Sq.mm. (Copper Unarmoured) |
| 1314 | 4 x 35 Sq.mm. (Copper Unarmoured) |
| 1315 | 4 x 50 Sq.mm. (Copper Unarmoured) |
| 1316 | External Lighting Fixtures and poles : Supplying, installation, Testing & Commissioning of the all in one integrated type solar PV lighting system on the existing pole structure, comprising of Mono Passivated Emitter and Rear Contact (PERC) Solar Panel (minimum efficiency 21%), Pulse with modulation (PWM)/Maximum Power point tracking (MPPT) charge Controller in the box with a sleek appearance and a sturdy structure, is weather-proof, and is simple to install, With Lithium- Iron Phosphate Battery (LiFePO4), charging time 8-10 hours, Battery backup time 12 hours (minimum), LED fixture watt 72 watt, Input voltage: 12V DC , Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, IP-66,IK-08, CRI >70 , under voltage and over voltage protection, Electro Magnetic Interference (EMI) Electro Magnetic Compatibility (EMC) As per CISPER 15 A, lenses for beam angle as per Illuminating Engineering Society of North America (IESNA) type I/II/III as per the width of the road and the project requirement, Correlated Colour Temperature (CCT) 5700°K (As per American National Standard Institute (ANSI Bin)) , life time (LED,Driver & electrical circuitary) of 50K hours lamp buring hours till the 70 % of initial Lumen maintained as per LM80 extrapolation IES TM-21-11 report, automatic swich on/off, Alliuminium or Acrylonitrile Butadiene Styrene (ABS body), can be installed on a pole or wall. System lumen efficacy >120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. All as per pre approved by Engineer in-charge complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required, complete with mounting structure for the battery and accessories suitable for withstand wind storm speed as per the site location. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 80 Watt |
| 1317 | GI OCTAGONAL POLE Height of Pole 9 Meter Material construction of Shaft Hot Rolled Steel Plate as per IS 2062 / BS EN 10025 Or Equivalent. Grade of Steel Hot Rolled Steel Plate as per IS 2062 / BS EN 10025 Or Equivalent. Thickness 3 mm, Bottom 155, top 70mm No. of longitudinal welds /section One Cross section of Pole Octagonal (8-sided polygon) Base diameter and top diameter (A/F) As per structural design calculations. Metal protection treatment for Pole Section Hot Dipped Galvanized, as per BS EN ISO 1461 Height of door 500 mm Door type Hinged door Dimension of base plate As per structural design calculations. Thickness of base plate As per structural design calculations. Grade of Steel for Base Plate As per IS 2062 Max. wind speed As per IS 875 Part III – 2015, FOUNDATION BOLTS Number of foundation bolts 4 nos. PCD of foundation bolts As per structural design calculations. Grade of Foundation Bolts As per structural design calculations.Bolt diameter/Length As per structural design calculations with J-Bolt |
| 1318 | Supply and Transportation of 35/40 W Post Top lantern made with high Pressure die cast aluminum body with polycarbonate / high impact PMMA protector for optimal luminous flux, IP66 suitable for vertical mounting of 76 mm dia. the luminaire shall have CCT 3000-4000K with internal surge protection of 4KV and External Surge Protection of 10 KV, p.f>0.95 etc., complete with not less than two years warranty. Makes: As per list of recommended brands. |
| 1319 | Supply and fixing of IP65 surface ground mounted luminary fitted with 700ma 11 W LED bollard with 8 deg-24 deg 3000K-4000K CR I80+ nondimmable LED power supply built in Color tolerance. |
| 1320 | High Mast Light : SUPPLY, INSTALLATION, TESTING AND COMMISSSIONING OF 20 METER HIGH MAST POLE DESIGN STANDARD - PLG 07 OF ILP, BASIC WIND SPEED- IS: 875 PART Ill: 2015DESIGN LIFE - 25 YEARS, TERRAIN CATEGORY - 2, SHAFT: HOT ROLLED STEEL PLATE CONFORM TO IS 2062 / BSEN 10025 OR EQUIVALENT GRADE, FLANGE/GUSSETS/DOOR STIFFENER : AS PER IS-2062 / BS EN 10025 OR EQUIVALENT GRADE, FOUNDATION BOLTS: T.S. 600 N/Sq.mm., FINISHING: HOT DIP GALVANIZED TO BS EN ISO 1461., THE TOLERANCE IN A/F DIMENSION ARE ±3mm., THE TOLERANCE IN THICKNESS DIMENSION ARE ±5%., THE DOOR SHALL BE VANDAL PROOF AND WEATHER PROTECTED, THE MAST WILL HAVE PADLOCKING ARRANGEMENT IN THE CENTER AND 2 Nos ALLEN BOLT AT TOP AND BOTTOM, MAKE OF THE INTEGRAL MOTOR SHALL BE HEM OR EQUIVALENT, TRAILING CABLE MAKE SHALL BE SUN BRAND / BMI / BHUWAL OR EQUIVALENT., WIRE ROPE MAKE SHALL BE SSWRL /RELIANCE / APOLLO ROPE AND ALLOYS INDIA PVT. LTD. OR EQUIVALENT, THERE SHALL BE ONE OR MORE LONGITUDINAL WELDS DEPENDING ON THE AVAILABILITY OF SHEET.\\" High Mast 20 Mtr. TOP A/F 150Mm, BOTTOM A/F 460Mm, No. of Sec. No.-2, Bottom Thickness - 3mm, Top Sec.-3mm, Size Base Plate-dia.670mm x 25mm thick, Foundation Bolt Size M36x1000mm,25MM THK. PLATE 8 NOS. 036MM HOLE TO SUIT M30x850LONG ANCHOR BOLTS PROVISION FOR EARTHING HOG BOLT 2 NOS. 012MM WITH 3 NUTS & 2 WASHERS, incluiding electrical panel |
| 1321 | 11 KV VCB Panel ( 02 Nos. additional VCB panels as extension to the existing 11 kV HT switchgear panel) at Existing Main Receiving StastionSupply, Installation, Testing & commissioning of extension of 11 KV VCB Panel in Existing (OEM Built HT Panel with internal arc type tested. Additionally arc flash sensors shall also be provided for each VCB cubical - 3 nos for each cubical) panel comprising of 02 nos. of indoor type VCB panels.The VCB (cubicle and circuit breaker) panel should be made of steel clad, free standing, floor mounting, dust and vermin proof and horizontal isolation horizontal draw out, compartmentalized type, indoor switch board in standard execution with VCB. The draw out type circuit breaker cubicles should be fabricated using high quality 2mm thick CRCA steel sheet. The sheet metal should be given minimum seven/nine tank anti corrosion treatment & then powder coated colour- SIEMENS GREY or equivalent complete with totally enclosed & fully interlocked, horizontal drawout, horizontal / vertical isolation type breaker as per IEC 62271-100/200, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, Manually spring charged breaker and manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of maximum 500 MVA and rupturing capacity 25kA for 1 sec, complete with self contained, fully interlocked, rack in and rack out mechanism, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 6 NO + 6 NC contacts and equipped with following switchgears and accessories as required and instruction of Engineer Incharge.The panel shall be supplied with following accessories as per single line diagram and Technical specifications mentioned in the contract (suitable for indoor installation complete as required). The panel shall be manufactured only OEM.Out going: 2 nos1 No. 1250 Amp 11KV 25kA for 1 sec VCB with Closing coil to be operated with 230V AC & Tripping Coil operated with 24V DC auxiliary, supply TNC Switch and comprising of following items:Digital voltmeter and Ammeter with inbuilt Selector Switch\\"One (1) set comprising three (3) dual-core, dual-ratio current transformers (CTs),having a ratio of 300/5 A, with a rated burden of 15 VA per core.CTs shall be resin-cast, indoor type, suitable for mounting in 11 kV switchgear panels, and shall conform to the requirements of IS/IEC 61869-2 (formerly IS 2705).\\" |
| 1322 | The following protections shall be provided :1 No. Microprocessor based numerical relay (IDMT relay) with 2 levels of over current and earth fault protection, 3 O/C and 2 E/F element with LED’s for fault indication and at least 15 trip records for over current & 15 for earth fault. Trip records must be with date & time stamping. ANSI : 50, 50N, 51, 51NGround Detector Relay (64R), Antipumping relay & Master trip relay (86). Over Voltage Relay with Timer (59) Non-directional overcurrent relay (50/51), Non-directional earth-fault sensitive (51N/50N)Under Voltage Relay with Timer (27), 1 Set of multifuction meter with basic parameters like frequency, KW,KWH KVA, KVAR, Power Factor, total harmonic distortion, MDI etc. shall be suitable for EMS(Energy Management system) function with RS 485 port for communication. 1 Set of following indicating lamps.Amber for Trip indication. Red 'ON' Green 'OFF' Spring charge indication. Trip Circuit Healthy indication.Breaker positioning lamps & DC Circuit Healthy indicaton lamp. TNC (Trip, Neutral, Close) breaker control switch with indication. arrangement. 1 No. Hooter with Accept/Reset & Test Push Button Local/remote Selector Switch & Emergency Push Button with necessary NO/NC Contacts. 12 window annunciation panel with audio and visual indicator common for the full panel. Note: Panel shall have incomer & Outgoing connections suitable for 1R x 3C x 300 sq. mm. XLPE 11KV cable (cable entry from bottom side) with indoor kit, end termination with heat shrinkable jointing kit etc. as required.Bus-bar arrangement should be such that in future similar cubicles can be connected with this cubicle.All nut & bolts used inside the panel should be of high tensile, bright zinc plated, hexagonal headed, metric size, manufacture to DIN-931 of steel, tensile strength as per standard, coarse threaded with two nos. bright zinc plated flat and spring washers. 50 x 6 mm Cu. earth bus shall be provided for the full length of the panel. Danger Plate shall be provided (as per IS specification)Surge Arrestor, 10KA, Class II shall be provided.Space heater with thermostat for moisture absorption shall be provided.02 (Two) Nos. cubicle lamps (LED) in each cubicle shall be provided along with switch.Power Pack 230V AC/24V DC, 42AH, 2X12V battery for providing auxiliary power to Trip Coil and other necessary equipments as required.11 KV, TWO (2) Panel Board ( 02 O/G ) All Services as described above and as per technical specifications . Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy