| 1 | Material & labour for excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified and directed by Engineer- in- Charge. |
| 2 | Material & labour for returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in- Charge. |
| 3 | Material & labour for removing excavated material (i.e. soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer- in- Charge. |
| 4 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed by Engineer- in- Charge.Note : Measurement shall be taken after punning down. |
| 5 | S&F of sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge. |
| 6 | All as per srl item No 5 here-in-before but using old bricks obtained under srl item No 1 complete all as specified and directed by Engineer- in- Charge. |
| 7 | Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed by Engineer- in- Charge. Cables of the following sizes:-Note : Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately. |
| 8 | 16 Sqmm 4 core |
| 9 | 35 Sq mm 3.5 core. |
| 10 | 50 Sq mm 3.5 core. |
| 11 | 70 Sq mm 3.5 core. |
| 12 | 95 Sq mm 3.5 core. |
| 13 | 120 Sq mm 3.5 core. |
| 14 | 240 Sq mm 3.5 core. |
| 15 | Supply and Fixing of Junction box of IP67 (as per IEC 60529) Thermoplastic PC- GFS Polycarbonate Weatherproof, UV resistant due to solar radiation, Rainwater proof, temperature resistant, Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 960 deg C (as per IEC 60695 – 2 – 11) Junction Box having size (205 x 255 x 112 mm) size on Pole with 1No. 10 Amp C Curve series, 10kA SP MCB i/c supply with pole mounting kit for clamping the box on pole, earthling the body connection, inter- connection, suitable terminal blocks, glands, locknut etc. complete set as reqd. for Pole lighting complete all as specified and directed by Engineer- in- Charge. |
| 16 | Supply and fixing of multi core round PVC insulated copper conductor (flexible) industrial cables PVC sheathed cables, 1100 volts conforming to IS : 694 of size 2.5 Sqmm, 3 core panel to street light inside/outside pole complete all as specified and directed by Engineer- in- Charge. |
| 17 | Supply and fixing of multi core round PVC insulated copper conductor (flexible) industrial cables PVC sheathed cables, 1100 volts conforming to IS : 694 of size 06 Sqmm, 3 core panel to street light inside/outside pole complete all as specified and directed by Engineer- in- Charge. |
| 18 | Supply and fixing of LED Flood lights 120 Watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by Engineer- in- Charge. |
| 19 | Supply & fixing of 90 Watt LED street light fittings made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by Engineer- in- Charge. Make Crompton Model No LFLN-120-CDL/60-M |
| 20 | Material & Labour for GI Tubes of size 50 mm dia light grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and directed by Engineer- in- Charge. |
| 21 | Supplying, fabrication, installation, testing and commissioning in replacement of LT panel not less than 3mm thick of modular polycarbonate thermoplastic enclosures outdoor type with copper bus bar of capacity 400A, factory made, CPRI approved,e floor mounting type, environment friendly, recyclable, UV resistant, halogen and silicon free, anti-acid and anti corrosive, enclosure should be IP-65 Protection in accordance with IEC 60529.The gasket material shall be polyurethane while the gasket shall be internally embedded including suitable working space in bus bar chamber suitable for 3 phase 4 wire system 415V,50HZ,AC supply and fixed on raised PCC 1:2:4,type B1 (20mm graded aggregate) raised base with cable glands, phase indicators, internal wiring, CT of suitable Ratio, digital voltmeter and ammeter, air passing holes with bproper spacing to accommodate to all control switches and other accessories, cable connections with suitable size of lugs/thimble etc including suitable size canopy to cover the panel with proper fixing arrangement including excavation and elarth work including dismantling the unserviceable panel and comprising the followings.Incoming:-(a) MCCB 250 Amps 4 Pole,36 KA- 01 No(b) Rotary handle- 01 No(C) spreader Link- 01 set( 06 Pcs)(d) RYB Indicating lamp(e) Digital laVoltmeter and ammeter of suitable rating(f) set of ibtCT of ratio - 250/05 AmpsOutgoing.(a) Suitable hole in bus bar for out going cable connection including suitable size nut bolt and fastener complete all as specified and directed. Please Enable Macros to View BoQ information |
| 22 | Supplying, fabrication, installation, testing and commissioning in replacement of LT panel not less than 3mm thick of modular polycarbonate thermoplastic enclosures outdoor type with copper bus bar of capacity 400A, factory made, CPRI approved,e floor mounting type, environment friendly, recyclable, UV resistant, halogen and silicon free, anti-acid and anti corrosive, enclosure should be IP-65 Protection in accordance with IEC 60529.The gasket material shall be polyurethane while the gasket shall be internally embedded including suitable working space in bus bar chamber suitable for 3 phase 4 wire system 415V,50HZ,AC supply and fixed on raised PCC 1:2:4,type B1 (20mm graded aggregate) raised base with cable glands, phase indicators, internal wiring, CT of suitable Ratio, digital voltmeter and ammeter, air passing holes with bproper spacing to accommodate to all control switches and other accessories, cable connections with suitable size of lugs/thimble etc including suitable size canopy to cover the panel with proper fixing arrangement including excavation and elarth work including dismantling the unserviceable panel and comprising the followings.Incoming:-(a) MCCB 250 Amps 4 Pole,36 KA- 01 No(b) Rotary handle- 01 No(C) spreader Link- 01 set( 06 Pcs)(d) RYB Indicating lamp(e) Digital laVoltmeter and ammeter of suitable rating(f) set of ibtCT of ratio - 250/05 AmpsOutgoing.(a) Suitable hole in bus bar for out going cable connection including suitable size nut bolt and fastener complete all as specified and directed. Please Enable Macros to View BoQ information |