| 1 | S&F in replacement of LT FPB made out of CRCA sheet 3 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1500 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following:-Incoming : LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E eleteical draw type 1000 Amp, 100 KA , overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto - 01 NO for incoming.Outgoing:(a) a) ACB AC 3 Phase 415 V, 50Hz 4 pole 630A capactiy 100KA with adjustable type thermal and magnetic setting relays - 02 Nos ( one No working and stand by)(b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 200 A capactiy 36 kA with adjustable type thermal and magnetic setting relays - 04 Nos.(c) MCB SPN 40 Amps 2P - 01 for local lighting.(d) Intelligent Panel meter to measure voltage, current, frequency, power factor, etc with all connected CTs (e) LED indicating lamps with colour Red, Yellow, Blue - 01 Set |
| 2 | S&F in replacement of LT panel box, by means of nut bolts washer, and opening of existing LT cables properly stacking, and supply, installation, testing and commissioning of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA sheet for load bearing members and 16 SWG (1.6 mm thick) for doors covers and internal partitions and shall be powder coated both side. Base frame of the panel shall be made of ICMC channel of size 50 x50 x 6mm, duly grouted on platform made of brick work in CM (1:2:4), 15mm thick plastering in CM (1:6) having minimum height of 450mm. The panel shall be provided with separate compartments for each switch gears with hinged door including interlocking with switch gears. The panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with epoxy insulated 800 Amps rated high conductivity aluminium bus bars, supported with DMC / SMC barriers and coluor coded, prewired with copper cable, the degree of protection is IP-54. the panel shall be complete with instrumentation such as LED phase indicating lamps and CT's, including extended aluminium strip of rating of Incomer (400Amps), and outgoing as per rating of MCCB’s, including aluminium lugs to connect the cable dismantled before etc., and comprising of the following:- (a) MCCB 400 amps, 4 pole with breaking capacity 36KA (Adjustable thermal & magnetic release) - 01 Nos (Incomer) |
| 3 | (b) MCCB 160 amps, 4 pole with breaking capacity 25 KA (Adjustable thermal & magnetic release) - 01 Nos (outgoing)(c) MCCB 100 A 4 pole with breaking capacity 25 KA (Adjustable thermal & magnetic release) - 08 Nos (outgoing) (d) MCCB 63 A 4 pole with breaking capacity 25 KA (Adjustable thermal & magnetic release) - 08 Nos (outgoing)(e) Multifunctional meter Cat No 30332567 MAKE schneider(f) Moulded fuse holder 125 A including HRC fuses = 3 Nos(g) Indicator lamp RYB :01 Set(h) CT'S 400/5 01 Set Make-L&T |
| 4 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB, 63 Amps, 16 KA, ICS = 100% ICU, with adjustable thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 5 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB,100 Amps, 35 KA, ICS = 100% ICU, with with adjustable thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 6 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB, 160 Amps, 36 KA, adjustable type , including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 7 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB, 200 Amps, 36 KA, adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 8 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB, 250 Amps, 36KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 9 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with MCCB, 400 Amps, 36 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 10 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with ACB, 630 Amps, 50 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 11 | S&F, in replacement, LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with ACB, 800 Amps, 50 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge. |
| 12 | S&F in replacement of Aluminium bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1500 A capacity complete with powder coating, necessary internal electric connection as required. |
| 13 | Description all as per item No- 11.00 above but capacity of 1000 |
| 14 | Description all as per item No- 11.00 above but capacity of 800 |
| 15 | Description all as per item No- 11.00 above but capacity of 600 |
| 16 | Description all as per item No- 11.00 above but capacity of 400 |
| 17 | Description all as per item No- 11.00 above but capacity of 200 |
| 18 | Supply and fixing in repair on load change over switch 400 Amps capacity, 415 Volts, 50 Hz, 4 Pole with advance neutral complete open execution type Make : Standard Cat No : ISCNFO0250 |
| 19 | Supply and fixing in repair on load change over switch 315 Amps capacity, 415 Volts, 50 Hz, 4 Pole with advance neutral complete open execution type Make : Standard Cat No : ISCNFO0251 |
| 20 | Supply and fixing in repair on load change over switch 250 Amps capacity, 415 Volts, 50 Hz, 4 Pole with advance neutral complete open execution type Make : Standard Cat No : ISCNFO0252 |
| 21 | Supply and fixing in repair on load change over switch 200 Amps capacity, 415 Volts, 50 Hz, 4 Pole with advance neutral complete open execution type Make : Standard Cat No : ISCNFO0253 |
| 22 | Supply and fixing in repair on load change over switch 100 Amps capacity, 415 Volts, 50 Hz, 4 Pole with advance neutral complete open execution type Make : Standard Cat No : ISCNFO0254 |
| 23 | S&F in replacement of Intelligent Panel meter to measure voltage, current, frequency, power factor, etc on LT panel with all connected CTs complete all as specified and as directed by the Engineer in charge. |
| 24 | S&F in replacement of LED indicating lamps with colour Red, Yellow, Blue - 01 Set in LT panel with all connected CTs complete all as specified and as directed by the Engineer in charge. |
| 25 | S&F in replacement of Automatic 3 Phase 415 V, 50Hz, 500kW LT Distribution Control Panel (LBS) made up of MS plate with Aluminium Bus bar for Controlling and Monitoring the mains Supply from a centralized Location with Dimension of 8 x 13 x 2ft (H x W x D) Rectangular shape complete all as specified and as directed by the Engineer in charge. |
| 26 | Supply and fixing LED Solar street light fitting 36 Watt including galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor complete. (Excavation & earth work shall be measured separately) |
| 27 | S&F in placement 75AH, 12 Volt LMLA battery, suitable for long backup, including taking down old battery of any type, complete all as specified. Make: Exide / Amaron / Power zone |
| 28 | S&F in Replacement Solar light kit suitable for upto 36 Watt solar lights, fixed in repair, complete all as specified. Make: CG/Surya /Bajaj / Philips / Havells |
| 29 | Supply and fixing in replacement solar Panel suitable for 36 Watt LED solar street light fitting fixed to existing pole, including taking down old fitting, complete all as specified. |
| 30 | M & L for disconnection from terminals of Battery of capacity up to 12 Volt 150AH and transporting to Battery repair shop i.e. civil market for repairing and Recharging and fixing it back to its existing location after recharging and rewpairing complete all as specified and as directed at site. |
| 31 | M & L for filling/ topping up of electrolite water ( Distilled water ) in Batteries complete all as specified and as directed at site. |
| 32 | Supply and fix single pointed air termination aluminium rod 12mm dia 300mm long all as directed by Engr-In-Charge. |
| 33 | Supply and fix aluminium strip 25mmx3.15mm with PVC saddles and fixing screws etc. for roof conductors complete with saddle and fixing screws and down conductors above ground |
| 34 | Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw all as specified. |
| 35 | Excavation in trenches in hard / dense soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide and getting out including trimming of sides, for laying of cables & foundation of poles, stay assembly, complete all as specified and directed by Engr-in-Charge. |
| 36 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed by Engr-in-Charge. |
| 37 | Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engr-in-Charge. |
| 38 | Taking out old unserviceable/serviceable un-reinforced concrete PCC cable covers from excavated trench all as directed by the Engineer-in-Charge. Note:- Serviceable un-reinforced concrete PCC cable cover kept in safe custody for reuse at site and unserviceable un-reinforced concrete PCC cable cover through in low lying area. |
| 39 | Laying only old reinforced PCC cable cover of any size as retrieved from serial item No- 04 above, complete all as directed by Engineer-in-Charge. |
| 40 | M&L for factory made un-reinforced pre cast concrete cable protection cover LV class type - I with size 250mm x 150mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge. |
| 41 | M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 10cm after laying of cable in trenches complete all as directed and sand cover to UG cable, complete all as specified and directed by Engr-in-Charge. |
| 42 | Taking out old LT under ground cable from trenches / floor / road / wall / pipe / pole of any size and description incl joint, complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 43 | Taking out old LT under ground cable from trenches / floor / road / wall / pipe / pole of any size and description incl joint, complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |