| 1 | Part A: SITC of 1000 KVA (11/0.433 KV) HT Transformer and 750 KVA Servo voltage stabilizer, 320 DG set with other allied accessories |
| 2 | Supply,Installation,Testing & Commissioning of 1000 KVA , (11/ 0.433 KV ) 3-phase outdoor type oil immersed ONAN cooled Transformer complete with all fittings such as oil Conservator with drain plug,Silica gel,Breather,thermometer,tap changer,oil guage lifting lugs,Drain cum sampling value,filter valve with plug,first filling of fresh transformer oil ,weather proof HT Cable /LT cable Box earthing terminals etc complete .( Energy Efficient Level-2 ). of ALBA / Northsons /Northern / Zain Electricals make or any other brand as approved by department not below the rank of SDO (After examining of GTP ,type test certificate and other relevent documents to be provided by contracting firm ) . The transformer manufacture unit should have CPRI Registration and BIS Certificate upto required capacity/ level and type test of said capacity from last five years onlyThe complete testing of transformer will be carried out at manufacturing site by departmental representatives before assembling /despatching of same and contracting firm has to facilate in all aspects the deptt representatives upto manufacturing site for the carrying out the necessary testing of said job. The job further includes comphrensive maintenance contract (with p/f of spares if needed) of Transformer for a period of two years reckoned from date of sucessful comissioning |
| 3 | Supply,Installation,Testing & Commissioning of 750 KVA,3-Phase,415V,(Buck Boost type) L.T,Unbalanced Servo voltage stabilizer (OUT DOOR type) .that must take a load of 750 KVA at the Following Specifications No. of Phases = 3 No Input Voltage (L-L)= 224-460 Volts Output Voltage =415 volts ±1%(Phase to phase) & 230 volts±1%(Phase to neutral) Protection =Over voltage, under voltage & Overloading with TDR and neutral failure .The job further includes providing and fixing of Micropreceessor basd 1000 Amps 4-pole ACB having 65KA Breaking capacity of L&T /ABB /Legend / Simens (ACB Should be inbuilt to the Servo voltage Stabilizer) The Stabilizer should be in two seperate Chambers (i.e Dimmer and Control unit should be two seperate Chambers) The Stabilizer shall be servo-controlled automatic ,ONAN cooled and provided with first filling of fresh filtered transformer oil having required dielectric strength .The Stabilizer shall be capable of smooth operation upto 10 % un-balanced in the load currents.The contractor /supplier has to give guarantee for any manufacturing defect with three servicing of the equipment for two year reckoned from commissioning.Inclusive of all applicapable taxes (Andrew Yule / AE Electrical /Jindal) make or any other eq. bramd as approved by department not below the rank of SDO (After examining of GTP , test certificates and other relevent documents to be provided by contracting firm )) The contractor has to faciltate testing of stabilizer at manufacturing site to departmental representatives before Assembling and despatching of stabilizer to site of work.The Job further includes AMC for a period of two years reckoned from date of sucessful commissioning (The AMC includes quarterly servicing of Servo volatge stabilizer with replacement of damaged accessories /equipments both mechanical as well as electrical during operation as & when required) |
| 4 | 1(a) Providing, Installation, testing and commissioning 320 KVA of Silent Type Water Cooled diesel driven Generator Set Conforming to CPCB-1V /1V + NORMS of approved brand like Tata Motors/ Eicher / LARSEN & Toubro / KIRLOSKAR / CUMMINS INDIA / FG Wilson make , comprising of radiator ,4-Stroke multi cylinder engine of suitable BHP to deliver rated KVA at prevailing site conditions equipped with flywheel ,residential type silencer ,fuel governor ,fuel pump, built in fuel tank, electric starting equipment with required nos of suitable AH sealed maintenance free batteries etc., directly coupled to 320 KVA, 0.8 PF, alternator suitable for 3-phase , 4 wire 50 Hz Ac supply system with the entire system mounted on common base frame etc. on an exciting foundation exhuast pipeing with thermal insulation ,control wiring from alternator to control panel acoustisc enclouser, etc. as specified and consisting of the following as per sepecification given below etc as required one number multi cylinder ,four stroke , liquienance contract (with P/F of spares if needed) of transformer for a perios of 2 years reckoned from date of successful commissioning Gear compartment and the minimum nominal weight shall be 2.8 kg. Control gear compartments shall be top maintenable without accessing/ opening the optical compartment. the luminary shall have minimum windage area of 0.088 sq. km(+_5%) the luminary should have a minimum 10 KV/ 5KA SPD duly bolted in the luminary. the SPD should be able to sustain a 15 hits of 5KA rating i.e total of 45 hits across. the job includes CAMC of 3 years from date of handing over of site. |
| 5 | 1(b) Alternator One No. syncronous alternator rated 320 KVA, 415 Volts at 1500 RPM, 3-Phase, 50 Hz AC supply with 0.8 lagging PF at 40ᵒ C., 50% RH and at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless continous duty, self excited and self regulated through AVR conforming to IS; 4722/ BS 2613 suitable for tropical conditions and with class F/H insulations. |
| 6 | 1( c) Base frame and foundationBoth the engine and alternator shall be mounted on suitable base frame made of MS channel which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. |
| 7 | 1(d) Fuel tank:In built daily service fuel tank as per manufactures specification complete with all standard accessories and fuel piping between fuel tank and diesel engine, complete with valves, level indicator and accessories as required as per specification attached. |
| 8 | 1(e) Exhaust System:Dry exhaust mainfold with hospital exhaust silencer and catalytic convertol as per site requirement and as per instructions of Engineer Incharge |
| 9 | 1(f) Starting System:starting system comprising of starter motor, voltage regulator and arrangement for initial excitation, complete with required nos of suitable batteries as required and as per specification. |
| 10 | 1(g) Acoustic Enclosure:Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere as per specification attached. AS PER CPCB-IV/IV+/MOeF regulations. |
| 11 | (a) Supplying and fixing exhaust gas piping of suitable dia. Welded black MS 'B' class pipe conforming to IS:3589 cut to required length and installed with necessary bends, supports and clamps, anti vibration mountings, insulation of exhaust system with mineral wool/Rock wool 50mm thick, wire mesh and aluminium cladding etc. as required as per detailed specification to be communicated |
| 12 | Carrying out test at site at rated KW for the 320 KVA DG Set for a period of 12 hours continuous run including 10% over load for one hour after 12 hours of continuous operation including supply & filling of 500 Ltrs of high speed diesel (HSD) after test run |
| 13 | Supply ,Installation ,testing and commissioning of AMF Panel suitable for 320 KVA DG Set having following techanical specifications (A) General 1. DG Capacity Supported :- 320KVA 2. phase :- 3 -phase ,4 wire 3. System voltage :- 415 V AC ± 10 % 4. Frequency :- 50 HZ ± 5% 5. Mounting type :- Floor mounted ,Sheet Metal enclosed (B) Construction 1 .enclosure :- CRCA Sheet Steel ,min 14/16 guage 2. . Paint Finish :- Powder coated (with anti-rust primer ) 3 . Ingress Protection :- IP54 Outdoor use (C) Main Components1. Programmable Microprocessor Based Controller 2. Auto /Manual /off Modes 3. Parameters Monitoring : Voltage , Current , Frequency .Battery ,Run time 4. Engine Protection (Low oil pressure ,High Temperature etc) (D) Circuit Breakers /Contractors (1) Main Contactor /Breaker :- 630 Amps 4-Pole ,50 KA ACB (Specifications already mentioned above) (2) DG Contactor /Breaker :- 630 Amps 4-Pole ,50 KA ACB (Specifications already mentioned above) (3) Interlocking between mains and DG Set to prevent backfeed(E) Battery Charger (1) Float-Cum boost Charger (12V/24 vDC ) with Auto Cut-Off (2) Suitable for DG Battery maintenance (F) Indication and Meters (1) LED indicatiors :- Mains on , DG on , Load on DG ,Load on Mains ,DG Fault etc (2) Digital metering : V ,A ,KW ,KWH ,PF HZ,with energy meter (G) Protections (1) Under voltage /Over Voltage , Overload / Short Circuit , Phase Failure / Reversal (2) Engine Fault :- Low oil pressure ,High Tempt , Over Speed The other features includes Manual Change over switch ,Remote Monitoring & BMS Connectivity (RS-485/Modbus) ,Genset Start /Stop with delay timers ,Load management (for multiple loads) with wiring and termination should be Copper Bus bars fully insulated suitable for 630A ,Terminals with proper ferruling ,Cable Lugs and Labeling etc complete job |
| 14 | Earth work excavation of foundation trenches including dressing of sides and ramming of bottom, lift upto 1.5 mtrs, including getting out excavated soil and disposal of surplus soil lead upto 25 mtrs |
| 15 | Providing & laying of stone soiling dry hand packed complete, including carriage of materials from source upto site of work. |
| 16 | Providing & laying of mud mat at a depth in 1:4:8 Mix, including carriage of materials from source upto site of work. |
| 17 | Providing and laying of R.C.C 1:2:4, including carriage of materials from source upto site of work. |
| 18 | Reinforcement for R.C.C Work, incl carriage of materials. |
| 19 | Centering & shuttering including Shuttering propping etc and removal of form work after completion of job. |
| 20 | Providing, fabrication and fixing of 4\\" dia, 10 feet long G.I Pipe Class -B . The job further includes providing and fixing of channel Iron sections (100 mmx50 mmx5 mm) with 1.5 ft including cutting, drilling & welding fixed on top & bottom of G.I pipe |
| 21 | Providing and fixing of Angle /Channel Iron Sections including cutting, drilling and bends. The job includes providing anf fixing of ribs, nuts & bolts with washers of sorts. The job further includes Supply & applying of one coat of red oxide and two coats of aluminium paint. |
| 22 | Supply & fixing of corrigated C.G.I sheets with 0.67 mm thick having Zinc coating not less than 2.257 gm/mts, 8mm dia meter bitumun, fixed with hooks & bolts including cost of G.I Lintel washers of sizes for construction of shed for housing of D.G. Set.including cost of ridges |
| 23 | Providing and installation of GI Chain Link fencing of required width in mesh size 50 mm x 50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per directions of engineer incharge 4 mm dia of GI Wire. The job includes providing and applying of one coat of redoxide paint and two coats of aluminium paint. |
| 24 | Providing and Laying of 75 mm (I/d) HDPE (Heavy duty ) Air Cushion pipes ,including execuation upto 2 ft deep rench and refilling back and disposal of surplus soil |
| 25 | Proving of earthlings with Chemical Earthing with G I to G I electrode, 50 mm dia and 2 Mts long Pipe incl cost of boring and refilling of same with chemicals with man hole at the top with 19 x 3 mm G I Strip from Earthings terminal seperately to D G Set Body ,& neutral, and Servo Stabilizer Body and Neutral ,Panels etc..The job includes providing and fixing of main hole PVC chamber |
| 26 | Providing and laying of shock proof Rubber mats of 2mt. x 1 mt. and 12 mm thick in size |
| 27 | Supply and Errection of 9 mtrs long Steel Tublur poles heavy weight (minimum wall thickness 4.0 mm and minimum weight not less than 22o0 MKgs suitable for 11KV Line & DT Structure) with base plate and caps duly welded conforming to IS 2713 (Part-2) ,the pole is planted at 5- feet deep pit to be excavated and refilled with stones/boulders .The complete testing of poles will be carried out at manufacturing site by departmental representatives before despatching of same to site of work and contracting firm has to facilate in all aspects the deptt representatives upto manufacturing site for the said job for departmental team. |
| 28 | Providing and Laying of cement concrete for pole bottoms laid in 1:2:4 ratio of cement ,sand and 20 mm nominal size of aggregates complete job including its form work and carriage of materials upto laying site. |
| 29 | Supply and applying of one coat of Red oxide paint & two coats of Aluminium Paint Complete job. |
| 30 | Supply & Fixing of Channel Iron Cross Arms of Size /Angle Iron Braces of required size and length duly painted with red oxide and Al. paint fitted with required size of nuts & Bolts |
| 31 | earthing of poles with 32-38 mm dia GI rod of 6 ft long to be embedded in a pit with extending of earthing from rod to pole by way of p/l of 25 mm flat iron strip from electrode to pole |
| 32 | Supply,Laying , stringing , jumpering , binding , testing & commissioning of 0.05 ACSR ,incl making of all necessary connections |
| 33 | Supply,Installation,Testing & Commissioning of Earthing to poles using 1 inch dia GI Strip from battom upto pole |
| 34 | Supply,Installation,Testing & Commissioning of 11 kv lighting Arrestor heavy type/station type with nuts & bolts |
| 35 | Supply,Installation ,Testing & Commissioning of 11 kv fuse set with allied fittings complete job. complete with nuts & bolts. |
| 36 | Supply,Installation ,Testing & Commissioning of 11kv G.O set (heavy type) with allied fittings and handle complete job. complete with nuts & bolts. |
| 37 | Providing of G.I Plate earthing with 6-feet long G.I rod embedded underground with insertion of G.I pipe for watering and filling of char coal or Clay & salt in alternate layers also extension of eathing from rod to lighting arrestors , transformer body & Neutral of Transformer with Al. Strip fitted on poles with cliffs of Sub Stations frame..The Job further Includes providing and fixing of 1 ft x 1 ft main Hole PVC Chamber with main hole cover on top |
| 38 | Providing and fixing of Epoxy (Baby) insulators with its all accessories like fabricated steel cliffs of adequate sizes and nuts & bolts complete for resting/fixing of G.I earth upto lighting arrestor |
| 39 | Supply,Laying,Testing & Commissioning of 400 Sq.mm Single Core XLPE Al.Cable unarmoured 1100 volts of of Havells /Grandlays / Polycab / KEI make and making of necessary connections.The Job further includes cost of P/F of required Size of thimbles duly crimped with hydraulic crimping tool & making of necessary connections. The job further includes providing and fixing and making of making end termination with brass compression glands and aluminium lugs of required no. and size & as per instructions of site Incharge |
| 40 | Supply,Laying,Testing & Commissioning of 400 Sq.mm Single Core XLPE Al.Cable armoured 1100 volts of Havells /Grandlays / Polycab / KEI make and making of necessary connections.The Job further includes cost of P/F of required Size of thimbles duly crimped with hydraulic crimping tool & making of necessary connections. The job further includes providing and fixing and making of making end termination with brass compression glands and aluminium lugs of required no. and size & as per instructions of site Incharge .The cable is to be laid as per instructions of EIC ,laying of cable also includes digging upto 2ft deep trench and refilling or as per instructions |
| 41 | Providing and fixing of Al.Solder Less Clamps for HT Transformer duly fitted with necessary nuts & bolts. |
| 42 | Supply & fixing of Anticlimbing Devices for HT /LT Poles. |
| 43 | Supply & Fixing of Danger plates for HT /LT Poles. |
| 44 | Supply ,Installation ,testing and commissioning of 1000Amps F.Pole Bypass Change over switch having fitted with Sheet Steel enclosure of required sized fabricated out of heavy guage sheet steel dully powder coated paint .The Job includes providing and fixing of Angle iron Stand With Angle iron Legs to be grouted in cement concrete ( Length of Legs 1 ft under ground in cement concrete and 1.5 ft Above ground having four legs) |
| 45 | Supply, Installation, testing & commissioning of high-quality group control enabled integrated LED Street Light with a minimum system lumen of 21000lm and system wattage not exceeding 150W (±5W). The luminaire should have minimum system efficacy of 140 lumen/watt for the offered wattage. The LED used shall have CCT of 5700K, SDCM ≤5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted/welded/mechanically joined to the luminaire housing to ensure robust design. The luminaire shall have Integrated IP66 polycarbonate front cover/lens. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. The luminaire LED shall have declared Lifetime of 75K hours@L70. Product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10. The minimum luminaire dimensions shall be L: 555mm including spigot, W: 210MM, H: 135MM (Including Control Gear Compartment) & the minimum nominal weight shall be 2.8KG. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The luminaire shall have minimum windage area of 0.088Sq.mt. (±5%) The Luminaire should have a minimum 10 KV/5KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 5KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The LED used in the luminaire shall be SMD type only & shall be from either Lumileds, Osram, Nichia, Signify, APT Electronics Co. Ltd., CREE make or equivalent. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall be replaceable. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @full load, THD ≤10% @ full load, In-built surge protection of 4KV. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown/cut-off at less than 90V & 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2. The driver shall be EMI/EMC Complied as per EN55015/CISPR15. The luminaire shall be able to give Constant Light output (CLO) between voltage range of 140V to 277V. The luminaire driver & it’s SPD shall be of the same make/manufacturer/Lighting company as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer within 5 days of award of LOI. The LED Luminaire & it's driver both should be BIS registered. Approved make Philips / Lighting techology / Trilux /Endo / Zumtobel / Ligman (to be approved before installation) The Agency / firm has to submit Techanical data sheet (TDS) along with above mentioned requisite certificates before supply of materials for approval from department not less than rank of SDO.The Job includes providing and fixing of 38 mm dia GI Pipe bracket (Single arm ) upto 1 meter in length having bend at suitable angle with allied hard ware suitable for holding of 150 watt LED Luminary to be fitted on HT Poles below conductor wth flat iron clips complete job |
| 46 | Supply, Laying, Testing and Commissioning of 10 Sq.mm 2 Core XLPE insulated PVC inner sheathed steel armoured Al Cable of Havells make incl making of necessary connections with proper size of Al Thimbles dully crimped with crimping tool in cable trench incl excavation upto 2 inches in trench and refilling back or as per instructions of EIC |
| 47 | Supply and laying of 38 mm dia HPPE flexible Pipe (air Cusion) for laying of Cables in cable trench. |
| 48 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface! recessed steell PVC conduit as required. |
| 49 | 3x1.5sq. mm |
| 50 | Supply ,installation ,Testing and Commissioning of Pole Boxes made of heavy guage Sheet Steel dully powder coated painting with pole mounted clamp with nuts and bolts |
| 51 | Supplying and fixing 5 A to 32 A rating SPN , 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. |
| 52 | Single pole |
| 53 | Supplying and fixing 32-40 rating, 240/415 V, 10 kA, \\"C\\" curve DP MCB , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. |
| 54 | Supply ,installation ,Testing and Commissioning of 63-100 Amps 4-pole Connector |
| 55 | Dismentling of existing Poles and lighting fixtures along with allied accessories and stacking of same and handing over the intending department for clearing of corridor |
| 56 | Design, Fabrication, Assembly, wiring, supply of front operated cubical type compartmentalized as per form 4, rear access free standing dust and vermin proof with ingress protection IP 54 for outdoor application for main switchboards suitable for use at 415 volts, 3 Phase 4 Wire 50 Hz system suitable for fault level of required value symmetrical at 415 Volts, fabricated from 2 mm thick CRCA MS sheets with hinged, gasketed (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat section including 3 mm thick gland plated on top and bottom and fitted with lifting hooks, Galvanized hardware's with zinc passivation shall be used in fabrication of panels and including Gi strip of required size with 2 no earthing and including powder coated paint finish of approved shade over metal surface cleaned complete with interconnections etc. as per relevant IS as detailed below.Approval shall be taken for each panel in the form of shop drawings before fabrication. Note:- Panel Should be CPRI: IS/IEC:61439-1,2011&IS/IEC:61439-2,2011. |
| 57 | The CT burden shall be minimum 15VA or more as required |
| 58 | The switch board shall have provision for entry of all PVC cables/ bus duct from the top / bottom as required. |
| 59 | All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbar insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and Busbar support shall be used. Padlocking facility shall be provided on all outgoing feeder doors and switch handles shall be lockable in OFF position |
| 60 | All ka rating shall be ICS values. |
| 61 | The cost shall include providing and fixing of 100x50x6 mm channels for switchboard support |
| 62 | Short Circuit capacity for MCCB's shall be Icu values and Icu values shall not be less than 100% Icu |
| 63 | All incoming Bus Sections and out going feeders shall have fault trip auxiliary contacts for wiring to annunciation fault indication panel |
| 64 | Valid Type test certificates from independent testing lab for short circuit and fault with stand for 1 sec |
| 65 | All ACB ratings in panel capacities at 45'C ambient temperature |
| 66 | All MCCB'S shall be provided with Motor wound spring closing mechanism with 2 no spare NO/NC contact in main panels |
| 67 | All ACB shall be EDO with 2 no spare NO/NC contact in main panels: |
| 68 | The Panel Manufacturing unit Shall be CPRI registered & must comply with IEC 61439-2 .The firm /Agency has to sumit SLD of Panel and TTA certificate of manufacturing plant and completes test report of switch gear for approval before manufacturing and shall facilitate departmental representative for manufacturing site visit All MCCB'S /ACB's shall be of Legrend /L&T /ABB / Scheinder make |
| 69 | Panel near Transformer (For Details Refer SLD) (MLTP) |
| 70 | INCOMER |
| 71 | 1No ACB 2000 Amps 4 P EDO with Breaking Capacity 65 KA(Icu=lcs=Icw=100%) |
| 72 | 1 Sets Indicating Lamps RYB |
| 73 | 1 Sets Voltmeter-0-500 Volts |
| 74 | 1 No Ammeter(0-3000 A) |
| 75 | 1 No Selector Switch |
| 76 | 1 Set Current Transformer 2000/5 A 10 VA Burden, Class-1 |
| 77 | 1 set Aluminum Busbar 3000 Amps FP E-91 E Grade Electrolytic Aluminum |
| 78 | 3 No S.P MCB 2A |
| 79 | 1 Set ON/OFF/Trip |
| 80 | 1 No Multifunction Meter with RS-485 Port |
| 81 | OUTGOINGS |
| 82 | 1 No ACB 1000 Amps F.P EDO with Breaking Capacity 50 KA(Icu=Ics=Icw=100%) |
| 83 | 1 No ACB 1600 Amps F.P EDO with Breaking Capacity 50 KA(Icu=Ics=Icw=100%) |
| 84 | 4 No 630 Amps 4P 36 KA MCCB Microprocessor Based with Breaking Capacity 36 KA(Icu=lcs=100%) and ROH |
| 85 | 6 Sets Indicating Lamps ON OFF TRIP or as req. |
| 86 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet |
| 87 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 88 | Gland Plates to be 3.0 mm Thick. |
| 89 | Servo /Generator Panel Main Panel (For Details Refer SLD) |
| 90 | INCOMER |
| 91 | 1 No ACB 1200 Amps 4 P EDO with Breaking Capacity 50 KA(Icu=lcs=lcw=100%) |
| 92 | 1 Set Indicating Lamps RYB |
| 93 | 1 No Voltmeter-0-500 Volts |
| 94 | 1 No Ammeter(0-2000 A) |
| 95 | 1 No Selector Switch |
| 96 | 1 No Current Transformer 1600/5 A 10 VA Burden, Class-1 |
| 97 | 2 set Aluminum Busbar 1600 & 1000 Amps FP E-91 E Grade Electrolytic Aluminum |
| 98 | 3 No S.P MCB 2A |
| 99 | 1 set ON/OFF/Trip |
| 100 | 1 No Multifunction Meter with RS-485 Port |
| 101 | OUTGOINGS |
| 102 | 8 No 630 Amps 4P 36 KA MCCB Microprocessor Based with Breaking Capacity 36 KA(Icu=lcs=100%) and ROH |
| 103 | 1 No 630 Amp 4 P Change over Switch of Havels /L&T /HPL Make |
| 104 | 6 No 100 Amp 4P 36 KA MCCB Microprocessor Based with Breaking Capacity 36 KA(Icu=lcs=100%) and ROH |
| 105 | 16 Set ON/OFF/Trip or as required |
| 106 | Part B: S.I.T.C. of Audio Conferencing Solution for the for Administrative Block of BSF at Humhuma Budgam |
| 107 | Supply Installation Testing and Commissioning of Digital Chairman Unit as per Annexure 1.Make: Bosch/ TOA/ Marconi/ Heinrich .The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 108 | Supply Installation Testing and Commissioning of Digital Delegate Unit as per Annexure 1. Make: Bosch/TOA/ Marconi/ Heinrich.The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 109 | Supply Installation Testing and Commissioning of Digital conference system controller as per Annexure 1.Make: Bosch/ TOA/ Marconi/Heinrich .The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 110 | Supply, installation, testing & commissioning of Wall Mount Loudspeaker as per Annexure 1. Make: Bosch/Telvic/ TOA/Heinrich. The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 111 | Supply Installation Testing and Commissioning of 240 W Mixer Amplifier as per Annexure 1. Make: Bosch/Telvic/ TOA/ Heinrich.The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 112 | Supply, installation, testing & commissioning of Handheld Wireless Mic system as per Annexure 1.Make: Bosch /AKG /Heinrich .The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 113 | Supply, installation, testing & commissioning of 65 inches LED TV with specifications as per Annexure 1.Make:SAMSUNG/SONY/LG.The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 114 | Supply Installation Testing and Commissiong of HDMI Splitter as per Annexure 1.Make: Cypress/Kramer/Creston .The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 115 | Supply, Installation, Testing and Commissiong of HDMI Tx/Rx pairs with specifications as per Annexure 1. Make: Cypress/Kramer/Creston .The job includes AMC for a period of three years reckoned from date of sucessful commissioning |
| 116 | SITC of 2 Core speaker wire |
| 117 | SITC of 2 core power wire insulated in PVC conduit pipes |
| 118 | SITC of 9 U Rack Please Enable Macros to View BoQ information |