| 1 | Supply istallation testing and comm. of LED street light Luminaire having housing made of pressure die cast aluminium alloy (ADC12/LM6). The system wattage shall be 120W( & the luminaire shall deliver system lumens ≥ 16000lumens. The system efficacy of the luminaire shall be ≥140lm/w. The LEDs used in the luminaire shall be from either Lumileds, Osram, Nichia, APT Electronics and CREE make, shall have CCT of 5700°K, CR≥70, SDCM≤5, Life of 50000Hrs @ L70B50. The luminaire shall have IP rating of IP66 & IK rating of IK07. The luminaire shall have lens made of polycarbonate & optical cover made of toughened glass. The LED driver shall have operating voltage range of 140V to 270V, PF≥0.95 @ full load, THD≤ 10% @ full load, In-built surge protection of 4KV, HV Cut off @ 325V (±15V). The luminaire shall have 10KV SPD in-built inside the luminaire. The maximum dimensions of the luminaire shall be, L: 503M, Depth: 89MM at fins & height without cradle: 248MM. The nominal weight of the luminaire shall be maximum 7KGs. The luminaire driver & it’s SPD shall be of the same make/manufacturer/Lighting Company as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material for approval. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. Similar to above specs in Philips , LT & Ligman., wipro/ equivalent make ( sample to be approved before installation) |
| 2 | Supply fixing testing and comm.of decorative ornamental translucent luminarie having IP-65 protection ( glowmac ( Amphore-PRISMATIC-A-300PC-201 ) bajaj/havell equivalent make) |
| 3 | S/F/T/C of 18-22 Watt LED Philips/ Havell/Finolex /Crompton greaves or equvilent make. |
| 4 | Engaging of highly skilled labour / Electrician/ IT Related personal for carrying out I.T repairs at site, Dismentling of old damaged materials like wires in scraps, fixtures switches-sockets, servicing of panels and allied works, complete as directed by the engineer at site and stacking and handing over to concerned department including carrying out repairing works etc. |
| 5 | S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size. |
| 6 | a) 10 sq.mm 4 core |
| 7 | Supplying and fixing of following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. legrand / Schinider/ L&T ./equivalent make as directed by engineer incharge. |
| 8 | a) 6-32 Amp SP MCB |
| 9 | b) 40-63amp DP MCB |
| 10 | Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium body, Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/Helonix /Wipro make / sample to be approved before installation.. |
| 11 | Supply installation testing and comm. of flood light 100 W ( warm, white ), Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ Trilux/Wipro/LT make. the job also includes the angle iron stand of suitable size to be grouted in cement concrete with hold fasteners complete job. |
| 12 | Supply and errection of Cast iron ornamental lamp post 90 cm. ( bollard type) ( As per Approved sample/ drawing enclosed) having provision at bottom for built in gear box fitted with PVC 4 way connector 63 amp and 1-6amp MCB and clear painting coat. Dewarka (DBL-103, 90 CM) /Karrarie-Mujasame or equivalent standard make as directed by engineer incharge. the job also includes LED Lamp 20-25 Watt to be installed in the bollard with suitable no. of dash fasteners to be grouted in the cement concrete for holding the bollard.Mentioned dimensions are proposed dimensions, which may vary with actual measurements (Tolerance of ±5%) Further the pole shall be got approved by the concerned engineering wing after providing a sample before execution of work and the test certificate to be provided by the manufacturer. the job also includes Spiral Earthing through 10 swg GI wire after driving in ground up to a depth of 3' in the ground from the base of the pole. |
| 13 | Providing of Reinforced cement concrete foundation as per specifications/enclosed drawing including foundation nuts & bolts of required size welded together firmly with reinforcement properly, cement concrete to be carried in 1:2:4 mix. |
| 14 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (50-60 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 15 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 16 | Supply and installation of Earthing through 10 swg GI wire after driving in ground up to a depth of 3' in the ground from the base of the pole, with g.i rod to be embedded in the pit. |
| 17 | S/L , testing and commissioning of LT Power Cable , copper conductor ,XLPE Insulated,unarmoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Copper cable Havell/Eq. standard make as desired by the engineer incharge and making end termination with brass compression gland and copper lugs of required size. |
| 18 | a) 4 sq.mm 4 core(un-armoured) |
| 19 | Providing of service connection and earthings to luminaire from the junction box in 1.5 mm PVC insulated, multicolour copper wire . Please Enable Macros to View BoQ information |