| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+) Less (-) Tender Inviting Authority: Chief Engineer, Civil Engineering Group, GSO, Kalpakkam. Name of Work: Revamping of various types of Feeder Pillars, Energy Meter Distribution Boards and associated works including construction of masonry enclosure for the feeder pillars in Kalpakkam Township. Tender No: GSO/CTC/ESD/291/2026 Name of the Bidder/ Bidding Firm / Company : PART-II (FINANCIAL BID) Note : 1) This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. 2) Bidders are allowed to enter the Bidder Name and Values only.3) Rates quoted should be inclusive of GST @ 18% and any other taxes as applicable. NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Item.No. Item Description Item Code / Make Quantity Units Estimated RateinRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE including all taxes in Figures to be entered by the Bidder inRs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Rates in words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category Unit for Rate TOTAL AMOUNT Without Taxes in Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Design, manufacturing, supply, testing at manufacturer’s works, transportation, safe delivery, installation testing and commissioning of following types of outdoor, floor mounted, IP 54 protected, 415 Volts, 50 Hz, AC, TPN aluminium busbar, form 2b segrigated, cubical feeder pillars as per the drawing, detailed specification and as directed by Engineer-in-Charge. |
| 3 | Type A Feeder Pilllar (12 O/G) consisting of : a) Incoming Feeder consisting of 2 Nos. of 630 Amps, 4 Pole, 36kA, 415 Volts rated, 50 Hz, MCCBs with mechanical interlock and Thermal Magnetic trip release including O/C, SC and 0.03 to 10 A, Earth Leakage relay with CBCT, MFM, RYB and ON/OFF/Trip LED Indication lamps, 16A DP MCB For Panel Illumination. b) Outgoing feeder consisting of 4 Nos., 400 Amps, 4P, 36kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lapms. c) Outgoing feeder consisting of 8 Nos., 160 Amps, 4P, 25kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lamps. d) 630 Amps, 36 kA, 4 Pole MCCB as Spare (Loose item) - 1 No. |
| 4 | Type A Feeder Pilllar (10 O/G) consisting of : a) Incoming Feeder consisting of 2 Nos. of 630 Amps, 4 Pole, 36kA, 415 Volts rated, 50 Hz, MCCBs with mechanical interlock and Thermal Magnetic trip release including O/C, SC and 0.03 to 10 A, Earth Leakage relay with CBCT, MFM, RYB and ON/OFF/Trip LED Indication lamps, 16A DP MCB For Panel Illumination. b) Outgoing feeder consisting of 2 Nos., 400 Amps, 4P, 36kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lapms. c) Outgoing feeder consisting of 8 Nos., 160 Amps, 4P, 25kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lamps. d). 400 Amps, 36 kA, 4 Pole MCCB as Spare (Loose item) - 1 No. |
| 5 | Type A Feeder Pilllar (8 O/G) consisting of : a) Incoming Feeder consisting of 2 Nos. of 630 Amps, 4 Pole, 36kA, 415 Volts rated, 50 Hz, MCCBs with mechanical interlock and Thermal Magnetic trip release including O/C, SC and 0.03 to 10 A, Earth Leakage relay with CBCT, MFM, RYB and ON/OFF/Trip LED Indication lamps, 16A DP MCB For Panel Illumination. b) Outgoing feeder consisting of 3 Nos., 400 Amps, 4P, 36kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lapms. c) Outgoing feeder consisting of 5 Nos., 160 Amps, 4P, 25kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lamps. d). 400 Amps, 36 kA, 4 Pole MCCB as Spare (Loose item) - 1 No. |
| 6 | Type B Feeder Pilllar (12 O/G) consisting of : a) Incoming Feeder consisting of 2 Nos., 400 Amps, 4 Pole, 36kA, 415 Volts rated, 50 Hz, MCCBs with mechanical interlock and Thermal Magnetic trip release including O/C, SC and 0.03 to 10 A, Earth Leakage relay with CBCT, MFM, RYB and ON/OFF/Trip LED Indication lamps, 16A DP MCB For Panel Illumination. b) Outgoing feeder consisting of 12 Nos., 160 Amps, 4P, 25kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lamps. c). 160 Amps, 25 kA, 4 Pole MCCB as Spare (Loose item) - 1 No. |
| 7 | Type B Feeder Pilllar (8 O/G) consisting of : a) Incoming Feeder consisting of 2 Nos., 400 Amps, 4 Pole, 36kA, 415 Volts rated, 50 Hz, MCCBs with mechanical interlock and Thermal Magnetic trip release including O/C, SC and 0.03 to 10 A, Earth Leakage relay with CBCT, MFM, RYB and ON/OFF/Trip LED Indication lamps, 16A DP MCB For Panel Illumination. b) Outgoing feeder consisting of 8 Nos., 160 Amps, 4P, 25kA, 415 Volts rated, 50 Hz, MCCBs with Thermal Magnetic trip release and ON/OFF/Trip Indication lamps. c). 160 Amps, 36 kA, 4 Pole MCCB as Spare (Loose item) - 1 No. |
| 8 | Design, manufacturing, supply, testing at manufacturer’s works, transportation, safe delivery, installation testing and commissioning of Floor mounted / Wall mounted, IK10 rated, IP 66 protected, Fire retardant, non-metallic, compartmentalised, vermin proof, GFRP enclosed, 415 Volts, 50Hz, AC, Copper Busbars, Cubical Energy Meter Distribution Board as per the drawings, detailed specifications and as directed by Engineer-in-Charge. |
| 9 | Energy Meter Distribution Board (Floor Mounting) consisting of a) 125 A, 25 kA, 4 Pole MCCB with thermal magnetic O/C & S/C protection and 0.03 A -10 A ELR with suitable CBCT, 3+1 - Type 2 SPD, RYB and ON/OFF,Trip LED Indication Lamps etc., as incomer. b) 6 Nos. Outgoing (For Houses), each outgoing compartment consisting of 4 Pole, 63A, 100mA, Type AC, RCBO -1 No. 10-60A, Three phase whole current (4 wire) static energy meter-1 No. c) 1 No, Common compartment consisting of 2 Pole, 25A, 30mA, Type A, RCBO -1 No., 5-30A Single phase whole current Static energy meter -1 No. with outgoing circuits of 2 Pole, C10 A, 10kA, MCB -2 Nos. for Staircase lighting including LDR with Cast Aluminium JB and Common services. d) 100 Amps rated RYB Phase and Neutral Bus Bars, 80 A, 4 Way stud type terminal blocks etc including removal of existing EMDB, cables and outgoing run off mains etc and re-connecting them after completion of the work. |
| 10 | Energy Meter Distribution Board (Floor Mounting) consisting of a) 125 A, 25 kA, 4 Pole MCCB with thermal magnetic O/C & S/C protection and 0.03 A -10 A ELR with suitable CBCT, 3+1 - Type 2 SPD, RYB and ON/OFF,Trip LED Indication Lamps etc., as incomer. b) 4 Nos. Outgoing (For Houses), each outgoing compartment consisting of 4 Pole, 63A, 100mA, Type AC, RCBO -1 No. 10-60A, Three phase whole current (4 wire) static energy meter-1 No. c) 1 No. Common compartment consisting of 2 Pole, 25A, 30mA, Type A, RCBO -1 No., 5-30A Single phase whole current Static energy meter -1 No. with outgoing circuits of 2 Pole, C10 A, 10kA, MCB -2 Nos. for Staircase lighting including LDR with Cast Aluminium JB and common services. d) 100 Amps rated RYB Phase and Neutral Bus Bars, 80 A, 4 Way stud type terminal blocks etc including removal of existing EMDB, cables and outgoing run off mains etc and re-connecting them after completion of the work. |
| 11 | Energy Meter Distribution Board (Floor Mounting) consisting of a) 125 A, 25 kA, 4 Pole MCCB with thermal magnetic O/C & S/C protection and 0.03 A -10 A ELR with suitable CBCT, 3+1 - Type 2 SPD, RYB and ON/OFF,Trip LED Indication Lamps etc., as incomer. b) 6 Nos. Outgoing (For Houses), each outgoing compartment consisting of 2 Pole, 63A, 100mA, Type AC, RCBO -1 No. 10-60A, Single phase whole current (2 wire) static energy meter-1 No. c) 1 No, Common compartment consisting of 2 Pole, 25A, 30mA, Type A, RCBO -1 No., 5-30A Single phase whole current Static energy meter -1 No. with outgoing circuits of 2 Pole, C10 A, 10kA, MCB -2 Nos. for Staircase lighting including LDR with Cast Aluminium JB and common services. d) 100 Amps rated RYB Phase and Neutral Bus Bars, 80 A, 4 Way stud type terminal blocks etc including removal of existing EMDB, cables and outgoing run off mains etc and re-connecting them after completion of the work. |
| 12 | Energy Meter Distribution Board (Wall Mounting) consisting of a) 125 A, 25 kA, 4 Pole MCCB with thermal magnetic O/C & S/C protection and 0.03 A -10 A ELR with suitable CBCT, 3+1 - Type 2 SPD, RYB and ON/OFF, Trip LED Indication Lamps etc., as incomer. b) 6 Nos. Outgoing (For Houses), each outgoing compartment consisting of 2 Pole, 63A, 100mA, Type AC, RCBO -1 No. 10-60A, Single phase whole current (2 wire) Static energy meter-1 No. c) 1 No, Common compartment consisting of 2 Pole, 25A, 30mA, Type A, RCBO -1 No., 5-30A Single phase whole current Static energy meter -1 No. with outgoing circuits of 2 Pole, C10 A, 10kA, MCB -2 Nos. for Staircase lighting including LDR with Cast Aluminium JB and common services. d) 100 Amps rated RYB Phase and Neutral Bus Bars, 80 A, 4 Way stud type terminal blocks etc including removal of existing EMDB, cables and outgoing run off mains etc and re-connecting them after completion of the work. |
| 13 | Design, manufacturing, supply, testing at manufacturer’s works, transportation, safe delivery and testing of 415 Volts, 50Hz, AC, TPN, IP 65 protected, outdoor type, powder coated, sheet steel enclosed, panel board with stand consisting of: a) Incoming feeder consisting of 4 Pole, 63A, 10kA, MCB - C series with RYB indication lamps etc -1 Set. b) Outgoing feeder consisting of 1 No. 2 Pole 40A, 10kA, MCB - C series & 1 No. 2 Pole, 40A, 100 mA, Type A, RCCB - 7 Set. c) 100 Amps rated Aluminium Bus bars and 63A Stud type terminal blocks etc., - 1 Set |
| 14 | Supply, Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of 1.1 KV grade of following size of the cable through direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required.(Refer Sec VI, Clause No.3) |
| 15 | 4C x 10 sqmm 1.1kV grade Aluminium conductor XLPE insulation round wire armour FRLSH PVC outersheath |
| 16 | Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade following sizes of cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Refer Sec VI, Clause No.3) |
| 17 | 4C x 10 sqmm 1.1kV grade Aluminium conductor XLPE insulation round wire armour FRLSH PVC outersheath |
| 18 | Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of one number PVC/HRPVC/XLPE insulated and PVC sheathed Stranded Aluminium/copper conductor power cable of 1.1 KV grade of following sizes direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 19 | 3/3.5/4 Core upto 25 Sqmm |
| 20 | 3/3.5/4 Core above 25 to 3/3.5/4 Core x up to 120 sqmm |
| 21 | 3/3.5/4C above 120 Sq.mm but not exceeding 3.5/4C x 240 sq.mm |
| 22 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 23 | 3/3.5/4Core Upto 25 sqmm |
| 24 | 3/3.5/4Core above 25 & up to 120 sqmm |
| 25 | 3/3.5/4Core above 120 & up to 240 sqmm |
| 26 | Retrieval of the existing one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following sizes laid direct in ground including Removal of end termination, excavation of trenches, retrieving of bricks and back filling as per the detailed specification.(Refer Sec VI, Clause No.5) |
| 27 | 3/3.5/4 Core Up to 25 Sqmm |
| 28 | 3/3.5/4 Core above 25sqmm & upto120 sqmm |
| 29 | 3/3.5/4 Core above120sqmm & upto 240 sqmm |
| 30 | Retrieval of the already laid one number 1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etc as per the detailed specification. (Refer Sec VI, Clause No.5) |
| 31 | 3/3.5/4 Core up to 25 Sqmm |
| 32 | 3/3.5/4 Core above 25 & Up to 120 Sqmm |
| 33 | 3/3.5/4 Core above 120 & Up to 240 Sqmm |
| 34 | Relaying of one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of grade 1.1 KV of following sizes direct in ground including transportation of cables, excavation and backfilling of soil, supply of sand etc as per the detailed specification.(Note: Cable & Brick will be supplied by department as free issue item) (Refer Sec VI, Clause No.6) |
| 35 | 3/3.5/4 Core Up to 25 sqmm |
| 36 | 3/3.5/4 Core above 25 Sqmm & up to 120 Sqmm |
| 37 | 3/3.5/4 Core above 120 Sqmm & up to 240 Sqmm |
| 38 | Relaying of one number 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches on walls, poles and through embedded pipes using the retrieved spacer & clamps as per the detailed specification. (Note: Cable will be supplied by department as free issue item) (Refer Sec VI, Clause No.6) |
| 39 | 3/3.5/4C X Upto 25 Sqmm |
| 40 | 3/3.5/4 Core above 25 & Up to 120 Sqmm |
| 41 | 3/3.5/4 Core above 120 & Up to 240 Sqmm |
| 42 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately (Refer Sec VI, Clause No.10.6). |
| 43 | Straight through joint ( crimping type ) for 4 core, 10-16 Sq. mm |
| 44 | Straight Through Joint (Crimping type) for 3.5 Core, 25- 50 Sq. mm |
| 45 | Straight Through Joint (Crimping type) for 3.5 Core, 70-95 Sq. mm |
| 46 | Straight Through Joint (Crimping type) for 3.5 Core 120- 185 Sq. mm |
| 47 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 48 | 4 Core x 10 Sqmm |
| 49 | 4 Core x 16 Sqmm |
| 50 | 3.5/4 C x 35 sq.mm |
| 51 | 3.5/4C x 50/70 sq.mm |
| 52 | 3.5/4C x 95/120 sq.mm |
| 53 | 3.5/4C x 185 sq.mm |
| 54 | Supply, installation and testing of GI Pipe Earth Electrode as per IS: 3043 including RCC Chamber and RCC cover slab as per Drawing No. IGC/ESD/5060/1007/1 & IGC/ESD/5060/1008/1 are enclosed. (50 Kg. Each Bentonite & Charcoal shall be provided for each earth pit). (Refer Sec VI, Clause No.12.4). |
| 55 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats including excavation and refilling as per the detailed specification. No cutting or drilling permitted after galvanisation.Refer Sec VI, Clause No.12.9). |
| 56 | 50 x 6 mm GI flat |
| 57 | 25 x 6 mm GI flat |
| 58 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. (Refer Sec VI, Clause No.12.9). |
| 59 | 50 x 6 mm GI flat |
| 60 | 25 x 6 mm GI flat |
| 61 | Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting / galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11). |
| 62 | MS fabrication 1 coat primer & 2 coats synthetic enamel paint |
| 63 | Supply and embedment of concealed type MS boxes of the following types and as specified in RCC/Brick/Concrete Block Masonry with finishing and making good as per the detailed specification. (Refer SecVI, Clause No.15.10). |
| 64 | 300 (W) x 300 (H) x 120 (D) mm, 1.8mm thick sheet MS Box including supply and fixing of 20 Nos. of 10 Sq.mm M4 stud type terminal blocks |
| 65 | Supply and installation of following sizes of Heavy Duty, PVC circular rigid Conduits for Electrical & Communication System with required Solid Long Bends, Couplings, GI Wire etc, in Floor, Walls, Brick, Block Masonry, etc. including chasing & replastering as per the detailed specification.(Refer Sec VI, Clause No.27). |
| 66 | 25mm Dia, 2mm wall thickness PVC heavy duty round rigid conduits with 50mm deep Junction boxes. |
| 67 | 32mm Dia, 2.5mm wall thickness PVC heavy duty round rigid conduits with 50mm deep Junction boxes. |
| 68 | Supply and installation of 25mm Dia of steel wire reinforced, flexible UPVC, Conduit pipe as per the detailed specification. |
| 69 | Supply and Embedment of 50mm Deep, Square/Rectangular Concealed type and GI double earthed modular metal boxes of the following types and as specified in RCC/Brick/Concrete Block Masonry with finishing and making good as per the detailed specification. (Refer Sec VI, Clause No.15.12). |
| 70 | One / Two Module box |
| 71 | Six Module box |
| 72 | Supply and fixing following Modular front cover plate on existing modular metal/plastic boxes etc. as required. (Refer Sec VI, Clause No.15.7). |
| 73 | One Module Plate |
| 74 | Six Module Plate |
| 75 | Supply and Installation of following Wiring Accessories as per the detailed specification (Refer Sec VI (MNC), Clause No.5). |
| 76 | 1 No. 6A Switch on modular plate and termination of wires to the switches |
| 77 | 1 No. 16A Switch on modular plate and termination of wires to the switches |
| 78 | 1 No 6A 3 Pin shuttered type Socket on modular plate and termination of wires to the switches. |
| 79 | 1 No. 6/16A 3 Pin combined shuttered type socket on modular plate and termination of wires to the switches. |
| 80 | Wiring for lights / fans /sensors/ power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ Exposed PVC / ERW / Flo-coated Metal conduits as per the detailed scope of work, including supply of Wires, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 81 | Wiring with 2 Runs of 6.0 Sq.mm Copper wires for Phase, Neutral and 2 Runs of 2.5 Sq.mm Copper wires for Earth from Energy Meter Distribution Boards to Pull Boxes / SPN Distribution Boards. |
| 82 | Wiring with 3 Runs of 2.5 Sq.mm copper wire |
| 83 | Wiring with 2 Runs of 1.5 Sq.mm for Phase, Neutral and 1 Run of 2.5 Sq.mm copper wires for Earth |
| 84 | Supply, transportation, installation, testing and Commissioning of Surface mounted luminaires.(Refer Sec VI, Clause No.16.1). - Catalogue No : BN021 LED 12S 12W or equivalent and Lamp Type LED |
| 85 | Supply and Installation of laminated Hylam sheet of 3mm thickness over the boxes and as per the detailed specification. |
| 86 | Supply, cleaning the floor, proper pasting and installation of following insulating mat as per specification. (Refer Sec VI, Clause No.25). |
| 87 | 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kV for 3 minutes, AC dielectric strength 30kV RMS Insulating Mat confirming to IS:15652 |
| 88 | Supply and installation of following sizes of Heavy Duty, Hot Dip Galvanised GI pipes with required accessories on Floor, column, beams etc including chasing and replastering as per the detailed specification.(Refer Sec VI, Clause No.28). |
| 89 | 80 mm NB, 4.8mm, wall thickness Heavy Duty GI pipe |
| 90 | Earthwork in open Excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sqm on plan) in all types of soil, mixture of gravel, disintegrated rock, hard stiff clay, soft rock, hard rock including bailing of water, if necessary, dressing of sides, shoring, benching, levelling and ramming the bottom surfaces, with lift as given below and disposal of excavated earth within a lead of 50 metres, etc., all complete as per specifications and as directed by the Engineer-in-Charge. |
| 91 | All kinds of soil - Upto 1.5 mtr depth from AGL |
| 92 | Providing and laying in position of plain cement concrete using hard granite broken stone for all insitu levelling courses in foundations, floor, roof screeding, encasing pipes, etc., including mechanical mixing, ramming, compaction, levelling, curing, dewatering, if any including the cost of formwork etc., all complete as per specifications. |
| 93 | 1: 4 : 8 (1 cement : 4 sand : 8 graded stone aggregate 40mm nominal size) |
| 94 | Providing and constructing brick masonry at all lifts in cement mortar 1:5 using well cured flyash bricks of class 5 (non-modular) made up of using Flyash + Sand + Lime + additves (Gypsum/Cement) with waterproofing chemicals and accelerators confirming to IS-12894 or latest edition including suitable scaffolding, raking out joints, continuous curing for specified period, etc., all complete as per specifications and drawings. |
| 95 | 230mm brickwork |
| 96 | Providing and casting insitu Reinforced Cement Concrete of the following grades of design mix by Weigh batching using machine crushed hard broken granite stone of nominal size 20mm including cost of admixtures in recommended proportion wherever required, mechanical mixing, transporting, placing at all lifts, vibrating, consolidation, curing, finishing smooth all exposed faces, for all insitu concrete items, etc., as per drawings and specifications.Note :1) The rate quoted shall be exclusive of reinforcement and formwork which will be paid for separately under relevant items.2) The rate of concrete shall include the cost of admixture in recommended proportions as per IS 9103 as per direction of Engineer-in-charge.3) Cement proportion for Concrete Mix shall be on the basis of weigh batching only as per design mix.4) The cost towards any upward / downward variation required to obtain the specified strength over the minimum cement content will be paid for or deducted at the rate specified in Schedule 'F'. |
| 97 | M 25 Grade Concrete (The Cement content considered is 350 Kg per Cu.m) |
| 98 | Providing, cutting, bending, placing and binding steel reinforcement using TMT bars of Fe-500 / Fe-500D grade in all reinforced cement concrete works including cutting, bending, fixing, tieing in position with 1.6 mm dia soft drawn annealed binding wire, cost of cover blocks in C.M 1:2, etc., complete as per specifications and drawings. Important Note: The required quantity of steel reinforcement as mentioned in the schedule should be procured by the contractor only of SAIL, Rashtriya Ispat Nigam Limited (VIZAG), TATA Steel & JINDAL from authorised dealers which shall conform to IS: 1786 (Latest Edition). |
| 99 | Providing, erecting, placing in position and removing Formwork for all insitu concrete works at all lifts and all shapes such as circular works, chamfers, splays, etc., using Steel / Plywood shuttering including centering, scaffolding, strutting, propping with necessary bracing in all areas, fixing of EPs, cutting holes and fixing pipe sleeves, applying of approved form oil over surface in contact with concrete, de-shuttering after specified curing period, etc., all complete as per drawings and specifications.Note: Measurement for the formwork shall be the area of forms in contact with concrete surfaces. Stop boards for construction joints will not be measured separately for payment. Centering and shuttering where exceeding 3.5m height in one floor shall be measured and paid for separately. |
| 100 | Providing plastering to the Internal/ external surfaces of brickwork/concrete at all elevations in cement mortar 1:5 using crushed stone sand, 12mm thick admixed with cementitious waterproofing admixture of approved make at 400gms per bag of cement or approved water proofing chemical as with ratio as per manufacturer recommendation and including hacking of concrete surfaces with pointed tool, scaffolding, finishing, curing, forming grooves wherever necessary, all as per specifications and as directed by the Engineer-in-Charge. |
| 101 | Plastering the ceiling / exposed surfaces of concrete with CM 1:3, 6mm thick to make the surface uniform, free from undulations and imperfections including hacking pock marking of surfaces with pointed tool, scaffolding, curing at all lifts etc., all complete as per specifications and as directed by Engineer-incharge. |
| 102 | Providing Painting over all exposed surfaces at all heights over rough cast plaster/plain plaster with Two Coats of premium exterior emulsion paint of make Asian (APEX - Dust proof exterior emulsion) / Berger (Anti dustt weather coat) or other approved equivalent make of approved shade over a coat of exterior wall primer of make Asian / Berger or other approved equivalent make including preparation of surfaces, curing, scaffolding etc., all complete as per specifications. |
| 103 | Supplying laying and jointing of RCC hume pipes with collars of class NP-2 as per IS specifications including aligning to proper level and line as directed at site, jointing with Cement Mortar 1:2, curing, etc., complete as per specification. |
| 104 | 150mm dia. RCC hume pipes |
| 105 | Providing and fixing in position Aluminium partitions, doors, windows, ventilators, louvers, fixed glazing, sliding windows north light glazing, sliding shutter 'E' Channel, trellis, etc., using heavy duty standard anodized aluminium extruded sections, anodized aluminium sheets as per relevant IS code of \\"JINDAL\\" or approved equivalent make including pivots, approved door and window handles, door stopper, EPDM gasket, neoprene gasket lining, stainless steel screw, mastic filling, weather strips, washers, reinforcing the door shutters at top and bottom with MS rod threaded and fixed to vertical members, etc., as required and as per drawing etc., all complete at all heights and as directed by the Engineer in charge.NOTE:- 1. Payment shall be made on the basis of weight of aluminium members/section fabricated and actually installed in position without extra allowance for wastage no extra payment shall be made for non-aluminium consumable items like screws, gasket, weather strips PVC/Neoprene lining, sliding wheels for windows, in built tower bolt, reinforcing rods, etc., 2. Glazing, particle boards, Aluminium grills, mesh etc., will be paid separately under relevant items.3. All fittings like door handles, hinges, tower bolt, aldrop are inclued in this item and the fittings shall be of matching colour anodized aluminium sections. 4. The aluminium section shall be smooth, rust free, straight, mitred and jointed mechanically wherever required cleat angles at no extra cost.5. The aluminium section shall be anodized with \\"MATT FINISH\\" (15 micron thick) finishing and of approved shade/colour with the approval of Engineer-In-Charge. |
| 106 | Providing and fixing of Stainless Steel (Grade 304) wire gauge of 1.0 mm dia wire and 5.0 mm aperture on both sides of approved quality and make over Partly panelled Door / Grill door including fixing with Aluminium frame work, cost of screws, nails, rawl plug, etc., all complete as per specification. [Note: Cost of frame work i.e., aluminium or MS will be paid separately under relevant item] |
| 107 | Dismantling Brick work in cement mortar at all lifts including clearing and depositing the debris within a distance of 100 metres all as directed by Engineer-in-charge. |
| 108 | Removing Existing wooden/ Metal door at all lifts including clearing and depositing the door material within a distance of 1km all as directed by Engineer-in-charge. |
| 109 | Supplying, fabricating and fixing Steel work welded in built up sections and framed work at all lifts comprising Chequered plates, MS angles, other structural steel sections, etc., of TATA or SAIL or approved equivalent make including cutting, welding, bending to shape, painting exposed faces with two coats of anti-corrosive paint of approved colour over a coat of red oxide zinc chromate primer / zinc phosphate primer, embedding with Cement concrete, if necessary, etc., all complete as per specifications and drawings.[Note: The rate shall be inclusive of lifting arrangements if any required to hoist and concrete embedment's for fixing the steel works. ] |
| 110 | Channal, Angle, Trench cover etc., using of 6 mm thick or more Chequered plates wherever required. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Less (-) 0.0 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Government of IndiaDepartment of Atomic EnergyGeneral Services Organization Centralised Tender Cell TENDER DOCUMENT FOR Revamping of various types of Feeder Pillars, Energy Meter Distribution Boards and associated works including construction of masonry enclosure for the feeder pillars in Kalpakkam Township. Tender No: GSO/CTC/ESD/291/2026 Part – II : Financial Bid (Section - VIII) INDEX S.No. Title Page No. |
| 111 | GENERAL INFORMATION FOR GUIDANCE OF TENDERERS |
| 112 | The schedule of quantities is to be read for the purpose of pricing in conjunction with the special conditions, general rules for the guidance of contractors, conditions of contract, specifications, scope of work (Section V), and General Specification (Section VI, VI MNC), drawings, schedule of supply of materials and the appendices for complete interpretation of this scope of work quantity wise. |
| 113 | The prices inserted in the schedule of quantities shall be inclusive of value of the work described including all cost and expenses, which may be required in and for the construction of the work described together with the general risks, liabilities and obligations not forth or implied in the documents on which the tender is to be based. |
| 114 | The quantities stated are to be considered approximate only and the unit prices entered in the schedule of quantities and prices shall apply only to the actual quantities measured in the completed work in accordance with the specifications. |
| 115 | Items of work described in brief are detailed under specification of Work.The scope of work will not be estimated from the brief description of this schedule. |
| 116 | Rate quoted must include all components required for meeting the specification and performance requirements of the item irrespective of whether they are specifically brought out in this schedule or not. |
| 117 | All the materials other than those shown in schedule of supply of materials in section VII are to be arranged by the contractor and his rates should account for the same. |
| 118 | Rates quoted for all items in this tender shall include cost of all materials. Department will not supply any materials other than materials stipulated in Section - VII of the tender and as such the rates quoted must be all inclusive. |
| 119 | If contractors need any clarification they are required to contact the ‘Head, CTC, GSO, Kalpakkam – 603 102, Chengalpattu district, Tamilnadu (Ph – 044 - 27481238 and 044-27480500 Extn. 84299,87345,85803,85532) during office hours. Please Enable Macros to View BoQ information |