| 1 | ERECTION WORK |
| 2 | Stringing of 03 nos. 33KV R,Y and B phase AAC Tarantulla conductor (approximate 24mtr.) with tension fitting which is connected with 33kv main bus. The Job includes shifting of material working site to S/S store at 132 KV S/S Jainpur. |
| 3 | Dismantling of old & used 03 nos. LA with structure after opening of all jumpering, earthing and control cable work. The job includes shifting of material working site to strore at 132 KV S/S Jainpur |
| 4 | Erection of structure/equipment along with all accessories as per technical specification and instruction manual including shifting of equipment and material from store to working site. |
| 5 | Structure (02 nos. CCM and 01 nos. CGM) |
| 6 | 36 KV Vaccum Circuit Breaker with structure |
| 7 | 36 KV CT with structure |
| 8 | 36 KV Line Isolator with Structure |
| 9 | 36 KV Bus Isolator with Structure |
| 10 | 33 KV CT Junction Box |
| 11 | 36 KV PT with structure |
| 12 | 36 KV PI with structure |
| 13 | 33 KV PT Junction Box |
| 14 | 33 KV Lightening Arrester with structure |
| 15 | 33 KV feeder Bay wise interconnection of equipments alongwith 33 KV Bus and 33 KV Bus PT which are connected to main bus specified conductors (Jumpering Panther, Zebra) |
| 16 | Erection of new 33 KV Tripple feeder C&R Panel as per proper alignment & instruction of S/S incharge with making earthing by MS flat 25x6/50x6mm in control room after shifting of new 33 KV above panel from S/S strore to control room safely & carefully at 132 KV S/S Jainpur Kanpur Dehat |
| 17 | Laying of 1.1 KV Copper Control Cable including dressing along with all associated work to complete the job |
| 18 | 2 Core X 2.5 Sq. mm |
| 19 | 4 Core X 2.5 Sq. mm |
| 20 | 6 Core X 2.5 Sq. mm |
| 21 | Termination of Control cable for above 33 KV bay with control panel including hole in gland required supply and fixing of suitable cable gland of approximate size supply and providing ferrule in is core of cable and its termination with lugs and all other associated work to complete the work satisfactory for 33 KV bay. |
| 22 | Making of earthing of above S/S Structure, CCR/CCM. Isolator, C.T., VCB, Junction Box by M.S. flat as per site requirement, M.S. flat provide by the UPPTCL as per actual consumpution |
| 23 | Earthing by 25x6mm MS flat |
| 24 | Earthig by 50x6 mm MS flat |
| 25 | Laying of 40/36mm dia M.S. Round bar as per available of department 600mm below ground level including cutting, straigtening, welding & painting at joints and connecting the substation grid after execavation of trench its back filling and all other associated work to complete the work satisfactory as per tecnical specification. |
| 26 | Fabrication of 50cmm long cleat with 50x6mm angle & welding at cross joints including cutting, welding work etc. |
| 27 | Fabricate 40/36 ion of 3M long electrode with round bar having 150mm long conical shape as per availble of department and then its piecing vertically inside the ground with top 500mm below ground level and its connecting & welding with substation grid earth mat, excluding the cost of MS bar as per technical specification. |
| 28 | Painting of MS Flat 50X6mm and 25x6mm by one coat red oxide and two coat bus green colour after cleaning work |
| 29 | Providing & fixing of 1” dia JINDAL make G.I. Pipe with 2C, 2.5Sqmm control cable including plumbering work with elbo, socket, cutting, welding and jointing work etc. at 132 KV S/S Jainpur. (As per required cable provided by department free of cost) |
| 30 | Laying of 2/4Cx2.5 sqmm. PVC control cable for periphery lighting. The job also including the excavation of trench below 0.5mtr. and laid the cable in the trench and filling the sand on the cable then covering the same by using first class brick and completion of work. (cable provided by department free of cost) |
| 31 | providing and fixing of Energy merter in iron box fixed in near 33 KV CT junction box. The job includes iron box prepared by contractor in the supervise of S/S incharge and iron box painted one coat red oxide and two coat enamel paint. (Energy meter provided by department free of cost) and sealing of cable of CT & PT installed at 33 KV Astral bay at 132 KV S/S Jainpur, Kanpur Dehat. |
| 32 | Providing and fixing of new gerneration energy & environment friendly long aluminium outdoor beam street light with high power 120 watt LEDs as light source & exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 230volt AC input supply of Havells/Surya/Philips including wiring from junction box to light fitting point and checking of healthiness fo LED light. |
| 33 | Fixing of 6 to 10 amp single phase MCB in lighting cubical junction box. The job include proper wiring work etc including cost of all material labour T&P etc for proper completion work. |
| 34 | Providing and fixing of double door type junction box MCB type with the structure for cable lighting termination work. |
| 35 | Providing and fixiing of 33 KV feeder name plate of 2 mm thick aluminium sheet plate size 400x200 mm with covering retro reflection sheet base yellow colour & write feeder name in black colour |
| 36 | Loading, unloading and safe carriage of various materials i.e. VCB, CT, BSI, LSI, MS-Flat, ALP, 33KV C&R Panel , MS round bar, MS flat near about 100 Km. approx the job includes shorting, Counting, Spacking, Loading and Unloading the same at 132 KV S/S Jainpur, Kanpur Dehat Under ETC-I Kanpur via suitable private carriar. |
| 37 | Modification of Various type substation structure by cutting and drilling of holes with welding work etc. as per site requirement. |
| 38 | Supply of Materials |
| 39 | Single tension fitting suitable for AAC Tarantulla |
| 40 | PG clamps suitable for Tarantulla to Panther |
| 41 | PG clamps suitable for Panther to Panther |
| 42 | PG clamps suitable for Tarantulla to Tarantulla |
| 43 | Copper Bond 16mm dia 500mm long with both end copper punched |
| 44 | 36 KV PT Clamp |
| 45 | 36 KV Bus Isolator Terminal connector suitable for panther |
| 46 | 36 KV Line Isolator Terminal connector suitable for panther |
| 47 | 36 KV Post Insulator |
| 48 | 36 KV CT clamp suitable for twin panther conductor |
| 49 | MS Round bar dia 40mm |
| 50 | MS Electrode dia 40mm (3 mtr long) |
| 51 | MS Flat 25X6 mm |
| 52 | MS Flat 50X6 mm Please Enable Macros to View BoQ information |