| 1 | Supply, Installation, Testing and commissioning of 4 M Arm Single arm pole from the ground level, pole material shall be pre galvanized mild steel complied with BS 1139/ 1161 made up of ERW 'B' class pipes. The bottom pipe shall be of diameter 114.3mm & top pipe shall be 76.1mm in diameter with wall thickness of 3.5mm & 3.0mm respectively. The Base Plate size shall be 300 X 300mm with thickness of 12mm MS material duly PU painted. Decorative Cast Iron base of 700mm giving an aesthetic look to the pole. Embellishment shall be placed at the bottom & intersection of the 2 pipes & properly bolted to withstand distortion. The pole shall also be provided with a single straight arm bracket with 38mm diameter and a span of 850mm with a cast iron bracket of 600mm suitable for suspended fixture. The pole shall be properly cleaned, machine polished and coated with epoxy zinc rich penetrating etch primer and finished with polyurethane base paint for a long-lasting finish with 45-micron coat in required colour as approved of Premium make. The Pole shall be provided with a maintenance window of size 300mm length & 95mm width with Allen bolt locking arrangement. Loop in Loop out connector mounted on appropriate size Bakelite sheet with stud terminals along with 1no. 6A SP MCB to be provided with each pole. The Pole shall be packed with shrink wrapping along with bubble paper wrap for avoiding scratches during transportation & installation. The Poles shall be supplied with foundation bolts M16 X 600mm made up of mild steel and threaded portion to be hot dip galvanized along with 2 nuts & 1 vicer per bolt. Factory test reports along with PDI & test certificates of galvanization & material TC to be attached along with the supply. The Pole shall withstand the wind speed of 75KMPH as per IS 875. Pole life span must be minimum 10 years. Pole Design will be finalized as per site condition as per Directives by Engineer In charge. |
| 2 | SITC of 50W decorative luminaire made of spun aluminium body with pressure die-cast heat management (PDCHM) and the IP65 optical compartment with high power LED/s is comprised of a deep drawn chemically polished and co-extruded, thermoformed polycarbonate protector stabilized agent UV rays suitable for 50W LED. Fitting should be suspended mounting type fixture. System Wattage:50W LED, Protection class: IP65, Driver Integral: Constant Current, Input Voltage: 230-240 Vac, Frequency: 50-60Hz, Operating Voltage:1200-277Vac, Operating Temperature: 0deg to +50deg C, single phase ac supply. light Source: Bridegelux, LED Lumens:5500lm, CRI(Ra):>80, LED Colour Temperature: 3000K to 6000k Life Span:>59,000 Hours, Physical Body: Die cast Aluminium Base, Body Spun Aluminium, Diffuser: Convex Type Translucent / V Translucent, mounting: Suitable for 50mm OD Pipe, Finish: Powder Coated Black, Driver Power Factor:>0.95, THD:<7.8%, Surge Protection:4KV, Efficiency:>87%. Fitting should have inbuilt driver with efficiency >0.9 and having surge protection device of 4KVA and external surge protection device of 10KVA. LED's of Bridgelux& driver to be of make Philips. IP66 and LM79-2019 report to be provided with 3 Years warranty. |
| 3 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 4 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 5 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 6 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 7 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formedwire armoured (strip) cable 1100 V, 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 8 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 9 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete. |
| 10 | Providing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.l. Rod complete with all materials as per specification no. EA-EP |
| 11 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. |
| 12 | Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 13 | Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation, fixing provided nut bolts with the help of template, duly plastered as per design complete (for 3 to 5m octagonal / conical GI pole). |
| 14 | Supplying & erecting three phase, 415V, street light control panel up to the max load of 12kW, TPN MCB 63A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation, with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation. |
| 15 | Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose). |
| 16 | Supplying and erecting triple pole mini feeder pillar with 500V, 200A FPMCCB as incomer and 2 outgoing circuits with HRC fuse base and cartridge of 100A with aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket having IP54,IK10 protection and slanting top to be erected on provided foundation complete as per specification no. SW-SWR/MFP Please Enable Macros to View BoQ information |