| 1 | Electrification |
| 2 | OD18904/2024-2025:Supply, erection and fixing of 175x85 RSJ poles on the existing foundation for placing transformer using suitable size bolt and nuts including lifting, welding etc as required as per directions of departmental officers |
| 3 | OD18905/2024-2025:Supply and fixing of channel iron 100mm X 50 mm X 6 mm (9.56 kg per meter) for placing and fixing CT-PT unit / ABS/ Lightning arrestor using suitable size u clamp, bolt and nuts etc as required as per directions of departmental officers |
| 4 | OD18906/2024-2025:Charges for painting the pole, channel etc with 2 coat epoxy paint over a coat of primer as required |
| 5 | OD18907/2024-2025:Supply and fixing of wall fencing to the transformer yard with appropriate area including(50mmx50mmx6mm size) angle iron support in all leg fixed with concrete base and(35mmx35mmx5)angle iron frame in the outer frame area of the each side of the fencing and (25mmx25mmx3mmsize) angle iron support in each side not more than 1.2 meter interval and one door provided in the front side of the yard with the same material and all side of the fencing covered with weld iron net mesh with supported by 25*3 flat iron. All the structures are welded and fabricated using suitable nut and bolt , and painted 2 coats of epoxy paint over a coat of primer as required. The bottom of the fencing shall be 150 mm for which brick work 225 mm thick shall be around the fencing including plastering as required. |
| 6 | OD18908/2024-2025:supply and spreading 40mm hard granite broken stone in transformer yard |
| 7 | OD18909/2024-2025:Supply and spreading of fine sand in transformer yard |
| 8 | 13.1:Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 9 | 13.10:Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required |
| 10 | 13.11:Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 11 | OD18910/2024-2025:Supply and providing 11KV 400 A AB switch with handle set fixed on the existing MS channel frame work. |
| 12 | OD18911/2024-2025:Supply and fixing 11KV DO (drop out) fuse unit with fuse element with iron base insulators on the existing MS channel frame work. |
| 13 | 13.13:Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire. 11 KV overhead lines with rated voltage 9 kV (rms) with a nominal discharge current rating of 5 kA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 14 | OD307749/2025-2026: Providing and drawing 8.00 mm (0 SWG)copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 15 | 90.16.5.8:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.8 mm (0 SWG) |
| 16 | OD18912/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box , earth bus, earthing system etc. as required including drilling necessary holes as required - 25 x 6 mm brass bolt & nut |
| 17 | OD21848/2024-2025:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 11 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments |
| 18 | 10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm |
| 19 | 10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit completewith all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductorcable of 11 KV grade as required :300 sq. mm |
| 20 | OD33970/2024-2025:Supply, installation, testing and commissioning of Outdoor type 11kV, 630A, 26.3kA for 3 sec Horizontal Draw out VCB fitted with Manual/Motor operated spring charging mechanism with 230V AC motor and motor control switch, shunt trip coil of 24V DC, closing coil of 24V DC, Auxiliary Contact 2NO + 2NC,Mechanical ON/OFF indicator, mechanical operation counter, protection CT, (--/5A, 5P10,15VA , 11kV/110V, Cl-0.2, 25VA PT Instantaneous IDMT relay with Microprocessor based 3O/C + and 1EF Protection relay, Strip Heater with thermostat, Digital Ammeter and Digital Voltmeter, Power pack 230V AC-24V DC emergency OFF push button |
| 21 | OD18913/2024-2025:Supply, 400 K.V.A out door oil type transformer, transformer Portion consists of 400 K.V.A ,11000V/433V, 50 Hz, Delta/Star connected ,insulated copper wound oil filled ,natural cooled transformer out door minimum IP 65/66 Protection, Bushing on HT side, cable box with provision of terminating suitable AYFY cable on LT side, The core shall be made of laser scribed core Class 'F' insulation level shall be maintained. OFF load tap changing facility shall be incorporated so as to achieve tap position +-5% in steps of 2.5% with all standard fittings (make : Unipower/ KEL /Resitech/Unitech). |
| 22 | OD18914/2024-2025:Fabrication of stand for KSEB meter box using angle iron/channel etc fix it on earth |
| 23 | OD34021/2024-2025:Supply and installation of dust and vermin proof wall mounting , sintex make meter box of size850x350X230 mm GSMB 8535 ( IP65 ) or equivalent suitable for fixing KSEB meter,fuseunits,CT etc hinged door construction for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry and exit IP65 withneutral CT as required including fixing it and making good the damages etc. as required.providing vision panel for the meter compartment knock out for cable entry and exit IP65 withneutral CT as required including fixing it and making good the damages etc. as required. |
| 24 | OD18916/2024-2025:Supply conveyance ,installation testing and commissioning of 5-30/5A, class 0.2S, 11KV/110V 4 wire HT TOD meter with terminal block , fuses including Wiring of ToD meter. |
| 25 | OD18917/2024-2025:Supply, installation , testing and commissioning of 11kV Outdoor type CT-PT Unit,3 Phase 4 wire system of metering with 3 No of CTs of accuracy class 0.2S, CT ratio 10 or 15 or 20/5 as per KSEBL Specifications S and 3Ph.PT of 0.2 Accuracy class ;Voltage Ratio :11kV/110V, as per KSEBL Specifications and with required amount of transformer oil |
| 26 | OD18918/2024-2025:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper control cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 12 core 2.5 sq mm with factory made clamp |
| 27 | 1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm |
| 28 | OD18919/2024-2025:Supply and providing plate earthing with 1200x1200x12 mm GI/CI earth plate, 50mm GI watering pipe, GI funnel with weld mesh, 25 x 3mm GI clamps, charcoal etc., including providing brick work masonry enclosure at the top (450 x 450 x 450 mm inside) with Gully trap with covering box in CI/GI but excluding earth continuity conductor, test joint |
| 29 | 90.16.2.4:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.40 mm dia G.I. pipe ( medium class) |
| 30 | OD18920/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate using test joint using suitable size nut and bolt etc as required.32 x 6 mm GI strip |
| 31 | 90.16.3.5:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 6 mm GI strip |
| 32 | 90.16.4.5:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).32 x 6 mm GI strip |
| 33 | OD18921/2024-2025:Supply of Adjustable spanner 305 mm Taparia make or equivalent |
| 34 | OD18922/2024-2025:supply of 250 mm black tip 2 in 1 screw driver Taparia make or equivalent |
| 35 | OD18923/2024-2025:supply of 180 mm Neon Tester Taparia make or equivalent |
| 36 | OD18924/2024-2025:Supply of fuse puller up to 630 Amp |
| 37 | OD18925/2024-2025:Supply and providing First Aid Chart duly framed and placed in a conspicuouslocation for clear vision. |
| 38 | OD18926/2024-2025:Supply of Class 2 (yellow) electrical insulating Gloves packaged in an individual container or package of sufficientstrength to protect properly the gloves from damage, conforming to IS 13774/IEC 60903 suitable for working voltage upto 17 K V and shall be marked as per standard. |
| 39 | OD18927/2024-2025: Supply of Class 1 (white ) electrical insulating Gloves packaged in an individual container or package of sufficient strength to protect properly the gloves from damage, conforming to IS 13774/IEC 60903 suitable for working voltage upto 7.5 K V and shall be marked as per standard. |
| 40 | OD18928/2024-2025:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS15652/2006 to withstand 3.3 KV dielectric strength near panel/substation. |
| 41 | OD18929/2024-2025:Supply and providing 6/5 Kg. Dry Chemical Powder type Fire Extinguisher withhose and clamps including fixing it to wall as required. |
| 42 | OD313182/2025-2026:Supply and providing 9 litre capacity Galvanized mild steel Fire bucket conforming to IS 2546-1974. The bucket shall be galvanized and painted with two coats of white paint on the inside and two coats of red paint on the outside.The handles and ears shall be painted with two coats of black paint.The word 'FIRE" shall be painted in black centrally on the outside,its letters shall be 75 mm high and approximately 12 mm thick.The bucket shall be water tight.The bucket shall be fixed on MS angle frame work/ wall bracket filled with fine sand . |
| 43 | OD18931/2024-2025:charges for scheme for the EI for additional copies |
| 44 | OD18932/2024-2025:Charges for preparation of scheme for the Electrical Installation for sheet of A3 size. |
| 45 | OD18933/2024-2025:Supply and fixing Neutral CT for up to 400 kva transformer and giving connection etc as requred |
| 46 | OD18934/2024-2025:Supply and fixing earth fault relay (L &K MC 12 or equivalent) and giving connection etc as required |
| 47 | 7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 48 | 90.12.5.37:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 400 sq mm |
| 49 | OD312026/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required.3.5x400 sqmm (clamped with 40x3mm MS flat clamp) |
| 50 | 90.12.10.5:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation90/75 mm or nearest size |
| 51 | 9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) |
| 52 | 9.2.28:Supplying and making outdoor end termination with cast resin compound including aluminiumlugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 400 sq. mm |
| 53 | OD312087/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required . 2x10sqmm |
| 54 | OD312119/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on cable tray as required.2x10sqmm (clamped with 1mm thick saddle) |
| 55 | 9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 56 | OD18935/2024-2025:Supplying and providing earth clamps for siemens/ tropodur type cable glands ofsuitable length and other dimensions noted along with each size ofglands for thefollowing sizes of cables as required.(4 sq - 16sq mm with 12 mm wide x 1.20 mmthick clip) |
| 57 | OD19128/2024-2025:Supplying and providing earth clamps made out of copper strips of the followingsizes including cutting and bending the flat exactly to the shape of thegland,drilling necessary holes for nut & bolt, tinning the points of contacts and givingconnections to the main earthing system as required.(25 x 3 mm for earthingglands of size 240 sq mm to 300 sq mm) |
| 58 | OD18937/2024-2025:Supplying and installation including all manner of supports/ suspenders, anchorbolts etc for cable trays made out of suitable size channel sections, slotted angles,flats, MS plates etc as required including painting with 2 coats of synthetic enamelpaint over a coat of zinc chromate primer, making good the damages, colourwashing etc as required. |
| 59 | OD18939/2024-2025:Fabrication, supply, conveyance and fixing frame work made out of suitable sizeangle iron cut and welded to shape of suitable size painted with 2 coats ofsynthetic enamel paint over a coat of red oxide primer & with drilled holes tomount the switch gear, fixed to wall using suitable size anchor bolts or grouted towall, making good the damages, colour washing etc as required |
| 60 | OD18940/2024-2025:Fabrication, supply, conveyance and fixing cable entry/ wire way box made out1.60 mm CRCA sheet of suitable size to match the switch gear and enabling thecables to be connected without strain, painted with 2 coats of synthetic enamelpaint over a coat of red oxide primer & with drilled holes and mounting to theswitch gear etc as required |
| 61 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 62 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 63 | 90.14.11.4:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 630A to 800A with CBCT. |
| 64 | 90.14.11.9:MCCB AccessoriesSupply and fixing auxiliary switch (1 NO + 1 NC) in the existing MCCB of rating up to 630 A. |
| 65 | 90.14.11.11:MCCB AccessoriesSupply and fixing one number under voltage release for all voltage range up to 630A MCCB. |
| 66 | 90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A. |
| 67 | 90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A |
| 68 | OD18941/2024-2025:Supply and fixing of Spreader/ terminal adapter kit with shroud in the existingmicroprocessor based 4 pole MCCB of rating up to 400 TO 630 A(8 pieces) |
| 69 | OD18942/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps forinterconnecting the control devices/ equipments including providingsuitable sizeinsulated sockets at the termination points or soldered properly, providingnumbering ferrules for the proper identification of the wiring,keeping the wiringfirm by suitable tie/ tie mounts/ PVC duct etc as required.-1.50 sq mm single runwith required sockets. |
| 70 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 71 | 2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N |
| 72 | 2.1.5:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.160 Amp TP&N |
| 73 | OD18944/2024-2025:S & F CURRENT TRANSFORMER - 400/5 A, 5 VA, accuracy class 1, Tape woundMetering CT |
| 74 | OD18945/2024-2025:Supply,fixing and installation of Three Phase Ammeter accuracy class 1-digitaltype |
| 75 | OD18946/2024-2025:Supply,fixing and installation of Three Phase Voltmeter accuracy class 1-Digitaltype |
| 76 | OD18947/2024-2025:Supplying and fixing .5 amps to 4 amps rating, 240/415 volts, C curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections, testing and commissioning etc. as required. Singlepole |
| 77 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 78 | OD18949/2024-2025:S/F Bus bar chamber, 100 x 40 mm aluminium anodised legend plates |
| 79 | OD18950/2024-2025:S/F Cable alley, 100 x 40 mm aluminium anodised legend plates |
| 80 | OD18951/2024-2025:Supply and providing LED indicators for all voltage ranges - Blue Colour |
| 81 | OD18952/2024-2025:Supply and providing LED indicators for all voltage ranges - Red, Green, Black,Yellow or Orange Colour |
| 82 | OD18953/2024-2025:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required in Panel board/DB's- 2.50 cm, 4 cm or 5 cm height |
| 83 | OD18954/2024-2025:Providing and fixing following capacity switch disconnector unit in sheetenclosure, making connections, etc. as required.25/32 amps 3 pole |
| 84 | OD308108/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x185 sqmm (clamped with 25/40x3mm MS flat clamp) |
| 85 | 90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size |
| 86 | OD308119/2025-2026:Providing and drawing 3.15 mm (10 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 87 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 88 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 89 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 90 | OD313279/2025-2026:Supplying and laying 32 mm X 6 mm GI strip at 0.50 metre below ground including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 91 | OD18967/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box ,earth bus, earthing system etc. as required including drilling necessary holes as required - 25 x 3 mm brass bolt & nut. |
| 92 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 93 | 14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 94 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 95 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 96 | 14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. |
| 97 | OD18968/2024-2025:Steel reinforcement for RCC Work including straightening, cutting, bending,placing in position and binding all complete. |
| 98 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 99 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 100 | OD308526/2025-2026:Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 101 | OD18969/2024-2025:Supply and fixing of 9W B22 LED bulb |
| 102 | OD18970/2024-2025:Supply, conveyance, installation, testing and commissioning of the following sizesof exhaust fans in the existing opening, fixing necessary bolt and nuts, makinggood the damages etc. as required including giving connections with requiredlength of 24/0.20mm PVC insulated and PVC sheathed 3 core round copperconductor flex wire conforming to relevant ISS. - 225 mm sweep Light DutyExhaust fan in metal frame working on 230 V A/C. |
| 103 | 90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps |
| 104 | 90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture |
| 105 | 90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 106 | 90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 107 | OD308518/2025-2026:Supply ,installation,testing and commissioning of 2400 lumen LED, efficacy >=120 Lm/watt, IP 66 street light fitting with die-cast aluminium housing, polycarbonate cover complete with THD 0.95, RoHS compliant, duly wired up for use on 230 V AC supply, IK >=7, with internal surge protection 4k above. Chip make Cree/Osram/lumilled/Nichea/Bridgelux.(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 108 | 1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 109 | 1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 110 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 111 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 112 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 113 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 114 | 1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm |
| 115 | 1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 116 | OD308523/2025-2026:Providing and drawing 2.65 mm (12 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 117 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 118 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 119 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 120 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps Please Enable Macros to View BoQ information |