Name of Work:- PROVN OF SPLIT TYPE AIR CONDITION AT AF STN FEROZPUR UNDER GE (AF) BHISIANA
Sl. No.
Item Description
1
Material and labour for surface sub main wiring (Three run i.e. 1 x phase and 1 x neutral and one run for continues as earth wire connected to earth dolly etc., using red, black and green colour wires as colour coding) with 4 Sqmm single core, FRLSH PVC insulated multistrand copper conductor drawn through and including PVC conduit medium mechanical stresses class PVC conduit as per IS 9537 (Part-III): 1983 of suitable nominal dia as required at site but not less than 25 mm nominal size, with all fittings and all accessories i.e. pipe bend, elbow, pipe hook/PVC clamps etc., for independent circuit from panel/DB to sheet metal enclosure complete all as specified and as directed.Note :-Three run of copper wire and one run conduit shall be measured as one RM length for payment but extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
2
Supply and fixing (concealed in wall or as directed) single pole and neutral sheet metal enclosure with a two pin and earth (3-pin, 2P+E) plug and socket, designed with IP-54 protection (protection against dust and splashing water), complete with one single pole MCB of capacity 20/25 Amps (C-Curve, 10kA breaking capacity), 240 volts, AC supply complete all as specified and as directed.
3
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Over & low voltage cutout and timer delay function etc digital display of IP & OP voltage, copper wound single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA with wall mounting bracket complete all as specified and as directed.
4
Supply and fixing SPN MCB ‘C’ curve, 32 Amps, 240 volts AC supply, with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in existing DB after removing blanking plate complete all as specified and as directed. Please Enable Macros to View BoQ information
5
Supply and fixing SPN MCB ‘C’ curve, 32 Amps, 240 volts AC supply, with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in existing DB after removing blanking plate complete all as specified and as directed. Please Enable Macros to View BoQ information