| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. a) Group-C |
| 2 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 2.5 sq. mm |
| 3 | b) 3 x 4 sq. mm |
| 4 | c) 3 x 6 sq. mm |
| 5 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm. |
| 6 | b) 25 mm. |
| 7 | c) 32 mm. |
| 8 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. a) 3 Module |
| 9 | b) 4 Module |
| 10 | c) 6 Module |
| 11 | d) 8 Module |
| 12 | e) 12 Module |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 A switch |
| 14 | b) 3 pin 5/6 A socket outlet |
| 15 | c) 15/16 A switch |
| 16 | d) 6 pin 15/16 A socket outlet |
| 17 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnection, powder painted including earthing etc. as required (But without MCB/RCCB/Isolator)a) 8 way, Double door |
| 18 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).a) 8 way (4 + 24), Double door |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 20 | b) Double pole |
| 21 | c) Single pole and neutral |
| 22 | c) Triple pole and neutral |
| 23 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. a) 100 A, 30 KA,FPMCCB |
| 24 | b) 125 A, 36 KA,FPMCCB |
| 25 | Supply, installation, testing and commissioning of Wall mounted L.T. cubical panel suitable for 415 V, 3 phase, 4 wire, 50 Hz, A.C. supply, with locking arrangement, made out of 2 mm thick CRCA MS sheet, front operated , duly compartmentalized with 4 Nos. Aluminium bus bars of suitable size, cable alleys, IP 54 protection rating, having suitable dimensions, having two spare compartments, with earthing arragement, should be mounted on MS angle iron frame of 50 mm x 50 mm x 6 mm of suitable dimensions, duly painted, with properly grouted in wall surface with adequate size of nut and bolts etc as as required as per site conditions including rebate for dismentled panel material. The panel should be suitable for accomodation of incoming and outgoing switchgears along with other items.a) 250 A, 36KA, FPMCCB -- 1 No. (Incomer)b) 200 A ,36KA, FPMCCB -- 4 No. (Outgoing)c) 250 A, 4 strip Aluminiumbusbar -- 1 setd) Phase indication lamps (R, Y, B) -- 1 sete) Voltmeter (0- 500V) 96 Sq.mm. with selector switch -- 1 No.f) Ammeter (0- 250 A) 96 Sq.mm. with selector switch and CT -- 1 No.g) Danger Notice plate -- 1 No. |
| 26 | Supply, installation, testing and commissioning of Wall mounted L.T. cubical panel suitable for 415 V, 3 phase, 4 wire, 50 Hz, A.C. supply, with locking arrangement, made out of 2 mm thick CRCA MS sheet, front operated , duly compartmentalized with 4 Nos. Aluminium bus bars of suitable size, cable alleys, IP 54 protection rating, having suitable dimensions, having two spare compartments, with earthing arragement, should be mounted on MS angle iron frame of 50 mm x 50 mm x 6 mm of suitable dimensions, duly painted, with properly grouted in wall surface with adequate size of nut and bolts etc as as required as per site conditions including rebate for dismentled panel material. The panel should be suitable for accomodation of incoming and outgoing switchgears along with other items.a) 200 A, 36KA, FPMCCB -- 1 No. (Incomer)b) 125 A ,36KA, FPMCCB -- 3 No. (Outgoing)c) 250 A, 4 strip Aluminiumbusbar -- 1 setd) Phase indication lamps (R, Y, B) -- 1 sete) Voltmeter (0- 500V) 96 Sq.mm. with selector switch -- 1 No.f) Ammeter (0- 250 A) 96 Sq.mm. with selector switch and CT -- 1 No.g) Danger Notice plate -- 1 No. Please Enable Macros to View BoQ information |