| 1 | Supplying, Installation, testing and commissioning of indoor type floor mounted cubical panel board made of not less than 1.0 mtr X 0.70 mtr X 0.50 mtr. non extendable type L.T - 3 phase 440V , 100A with both side open i/c front double hang shutter with locking arrangement made of 2 mm thick CRCA sheet in different compartment to accommodate various sizes of switch gear, busbar i/c supplying and fixing of following items i/c inter connection with 10 sq. mm copper cable. The panel should have inner earthing, one coat of primer and 2 coat of finishing water proof paint & danger plate etc.as required and its four legs made of equal angle 40 mm x 40 mm x 4 mm and embeded in the groung at the depth of 50 .00 cm with in cement concrete 1: 3 : 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) etc. as required. |
| 2 | MCCB 100 A/TPN (Four Pole) -25 KA breaking capacity with an adustable thermal settings --- 01 No. |
| 3 | Analog Ammeter (0 to 100 A) - 01 No. |
| 4 | Analog Voltmeter (0 to 500 V) - 01 No. |
| 5 | C.T. Coil, Class \\"B\\", with ratio of 100/5A - 03 Nos. |
| 6 | Three Phase Selector switch (for Voltmeter and Ammeter) -- 02 Nos. |
| 7 | Indicating lamp with backup fuse (RYB) - 01 Set. |
| 8 | MCCB- 200 A/TPN (Four pole) 16 KA,breaking capacity - 01 Nos. |
| 9 | MCCB- 63 A/TPN (Four pole) 10 KA,breaking capacity - 02 Nos. |
| 10 | MCCB - 40 A/ TPN (Four Pole)- 10 KA, breaking capacity - 01 Nos. |
| 11 | Copper bus bar strip of size 40 X 5 X 600 mm length for RYBN - 01 Set |
| 12 | Rewirable procelain fuse unit with neutral link 100A (RYBN) - 01 Set |
| 13 | Inter connection with 10 Sq.mm PVC copper cable etc. as required. |
| 14 | Complete set including installation charges. (Make: Havells/L&T/Legrand) or equivalent to ISI Standard. |
| 15 | Earthing with copper earth wire plate 600mm x 600mm x 3mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required. |
| 16 | Proving and fixing 25mm x 5mm copper strip in 40mm dia G.I pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 17 | Providing and fixing 25mm x 5mm strip on surface or in recess for loop earthing as required. |
| 18 | Supplying and fixing of 3.5 Core X 35 Sq.mm Armoured Copper Cable XLPE insulated core laid up, PVC tape inner sheathed for multicored cables armour galvanized wire for under ground cable extruded PVC type ST2 sheathed 650 /1100V grade as pe IS 7098 (PART-I) 1988 as required. (Make: Havells/Polycab/Standard or equivalent to ISI Standard). |
| 19 | 3.5 Core X 35 Sq.mm (32mm) PVC insulated Electrical UG Cable |
| 20 | Supplying and laying of following size (DWC HDPE) double walled corrugated high density polyethylene pipe ISI marked alongwith all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc direct in ground (75 cm below ground level) including excavation and re-filling the trench but excluding sand cushioning and protective covering etc as required. |
| 21 | 40 mm dia (OD-40mm & ID-35mm nominal) details of cost for 50 meter |
| 22 | Supplying and fixing rewirable porceline with Kit Kat fuse unit of 100 Amps, 415 Volts on energy meter board or in separate wooden board. Make: Havells/Standard/Legrand or equivalent to ISI Standard. |
| 23 | Providing and fixing wooden board of size 400mm X 400mm for fixing of energy meter or Kit Kat Fuse item etc. As required. |
| 24 | Supplying and fixing of 50mm dia ISI marked PVC Conduit complies with electrical codes and standards set by NEC ensuring fire-resistance nad electrical insulation properties etc. as required. |
| 25 | Supplying and fixing of 50mm or 55mm dia ISI marked PVC Clamp complies with electrical codes and standards set by NEC ensuring support and hang cable, wire, conduit etc. as required. |
| 26 | Supplying and fixing of 50mm metal dry wall screws for fixing of clamps, wire, cables, conduit etc. as required. Please Enable Macros to View BoQ information |