| 1 | Internal Wiring & Light Fittings |
| 2 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casing capping and Switch board both on surface] |
| 3 | b) Average run 6 mtr |
| 4 | c) Average run 8 mtr |
| 5 | Distribution Wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. with S & F 6A 5 pin Modular type plug socket and switch (Brand approved by EIC) fixed on 4 Module GI / PVC switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works [PVC casing-capping and plug box both on surface] |
| 6 | (a) On Board |
| 7 | (d) Average Run 3 mtr. |
| 8 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 9 | Wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc. |
| 10 | (c) 2 x 56/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) |
| 11 | (d) 2 x 56/0.3 (4 sqmm) + 1 x 22/0.3 (1.5 sqmm) |
| 12 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. |
| 13 | Legrand Make 2+8 way |
| 14 | S & F 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. |
| 15 | Legrand Make 6-32A SP |
| 16 | Legrand Make 40A DP |
| 17 | Supply & fixing sheet steel main switches on angle frame on wall 32A 240V (Havells Make) |
| 18 | Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling. |
| 19 | Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling by screws etc. |
| 20 | Fixing only bulk head ceiling fitting on wall/ceiling by screws etc. |
| 21 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required |
| 22 | Fixing exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing 2 * 1/1. 40 P.V.C. insulated and sheathed wire and making connection for exhaust fan of dia:- |
| 23 | b) 30 cm . ( 12\\" ) |
| 24 | Fixing only cabin fan on wall/ceiling by S&F rag bolt, nuts & washer (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length |
| 25 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 26 | Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts.long and 1 x 19/8 stranded GI (Hot Dip) wire (4 Mts. long), 25mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm diaGI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts |
| 27 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages (ii) No.6 SWG |
| 28 | Supplying & fixing 50mm dia x 5.24 metre long (incl. bends) GI pipe vertical type service bracket on wall for carrying 2 wires and an earth wire complete with Galv. MS clamps for stay, insulators and earth wire, 7/14 SWG stranded GI (Hot Dip) Stay wire with 230x31 mm dia straining screws, 75x88 mm porcelain shackle insulators with Galv. (Hot Dip) strips, bolts, bush etc. incl. painting |
| 29 | Supply only 9W LED Bulb (Make - Havells/Philips) |
| 30 | Supply only 20W LED tube light (Make - Havells/Philips) |
| 31 | Supply only LED recess light round15W (Make - Havells/Philips) |
| 32 | Supply only LED recess light square15W (Make - Havells/Philips) |
| 33 | Supply only decorative wall lamp (Make - Havells/Philips) |
| 34 | Supply only 50W LED flood light (Make - Havells/Philips) |
| 35 | Supply only 50W LED street light (Make - Havells/Philips) |
| 36 | Supply only LED bulkhead light (Make - Havells/Philips) |
| 37 | Supply only Chandilier (Make - Philips/Havells) |
| 38 | Supply only Ventilating fan (Havells - Ventil Air DX HS white) |
| 39 | Supply only wall fan (Havells make - 450 mm Tornado - Wall II) |
| 40 | Supply only stand fan 450mm (Make - Havell/Philips) |
| 41 | Supply only 2 core 10 sqmm aluminium unarmoured cable |
| 42 | Add GST @ 18% |
| 43 | Add Labour Cess @ 1% Please Enable Macros to View BoQ information |